|
Posted by Al Bundy on July 21, 2006, 6:54 pm
>
> Al Bundy wrote:
>> Not even sure if it's OK to do and, of course, local codes prevail.
>>
>> OK, so you need to run a 15A 14/2 line to a load. All you have is
>> 14/3. In general, is it ok to use 14/3. Of course it's the same
>> capacity but what is the right thing to do with the red wire?
>>
>> I'm thinking:
>>
>> - Snip it off at both ends right at the sheathing leaving and using
>> the b/w/g as usual.
>>
>> - Tape and mark as Not COnnected at both ends or something.
>>
>> - I saw once where they took the red wire, bent it back to the
>> sheathing and curled it around it. Maybe some universal wiring
>> message.
>>
>> I know this is not clean and pro to do but why not? I thought about
>> it and said what if I were running cable to a ceiling fan on a wall
>> switch. The fan has no light. If one were to think ahead they would
>> run 3-wire so in the future addding a light kit or replacing the fan
>> with one that has a light would make it easy to change the wall
>> switch setup to control light & fan.
>
>
> Andy writes:
> As long as you're fudging a little on the code anyway, I'd
> connect the
> red and black together, wrap it with tape so that only the black
> comes out,
> and then use the black and white as a normal 14/2.
> Nothing dangerous about this, except it violates "convention", but
> reduces
> the voltage drop a little. Obviously you would still use a 15A
> breaker.....
>
> Peraonally, I don't see the point in completely wasting a
> perfectly
> good
> extra run of copper.....
>
> I would welcome any comments or criticism on this, just in case I
> have overlooked something....
>
> Andy in Eureka, Texas
>
> Peraonally, I don't see the point in completely wasting a perfectly
> good extra run of copper.....
Neither do I. But when you're starting something, pull everything out and
see you have no 14/2 but a shitload of 14/3...that you got for free
anyway...it's time to git 'er done!
Thanks for the reply.
|