|
Posted by Les Desser on January 14, 2008, 3:54 am
show/hide quoted text
>On Sun, 13 Jan 2008 01:51:09 +0000, Les Desser
>>I started getting water coming up from my solid floor - concrete with a
>>2 inch screed on top.
>>We opened it up and found a 1/2 inch copper mains pressure pipe running
>>across a live flat pvc electric cable (240V - UK)
>How much seperation between the wire and the pipe?
Zero
show/hide quoted text
>What kind of wire?
Standard 2.5 mm.sq twin & earth leading to and outside 1 KW light which
is hardly ever used.
show/hide quoted text
>>The copper pipe was wrapped in some special tape to stop it corroding.
>>The cable was laid bare in the screed.
>Huh? <g> Never seen such a tape myself, but if you say so...
Apparently standard here - looks a bit like felt impregnated with some
very sticky oily substance. All pipes buried in concrete are wrapped in
it to stop corrosion.
[..]
show/hide quoted text
>>How come this hole? The installation is about 10 years old. The damage
>>could not have been mechanical
>Yes, it could have... Especially if they were touching (which would
>not have been good...)
They were under at least 1.5 inches of sand/cement screed.
[..]
show/hide quoted text
>>Could there have been some interaction between the cable and the pipe.
>>Seems far fetched but what else could it be?
>Not far fetched at all! But not exactly as you expected it. I don't
>know (you didn't say) what kind of cable it was, but clearly it had a
>microscopic flaw in the insulation.
I assume that must be the conclusion, but still a long shot - each
conductor has its own insulation and then there is an outer PVC bonded
sheath. And the fault should be directly under the piper, unless the
fault is more general - in which case I hope there are no more
cross-overs buried under my feet.
show/hide quoted text
>THis is not uncommon or unheard
>of. I'd guess the cable was not rated for direct burrial
Correct
show/hide quoted text
>(I'm unclear
>of whether this was in the cement or below it
Buried in the cement
show/hide quoted text
>, but in either case...
>the result is the same).
>To prevent this from happening again:
A bit late now. I'm digging it all up :(
[...]
show/hide quoted text
>Regardless I'd strongly believe there was simply a micro-pore in the
>wires' insulation which allowed it to fail, and the close proxminity
>to the water pipe gave a good path to ground. THe hole in the pipe was
>elctrolsis which wuold be expected.
Electrolysis sounds right.
[..]
show/hide quoted text
>I'll agree, this is one odd problem! (I've seen it before but not
>exactly the same circumstances, hence the diagnosis of a micro-pore in
>the insulation).
If there is ever a next time, I will watch the contractors!
Thanks for the response.
--
Les Desser
(The Reply-to address IS valid)
|
>2 inch screed on top.
>We opened it up and found a 1/2 inch copper mains pressure pipe running
>across a live flat pvc electric cable (240V - UK)