Home Page link

Multiple holes in load bearing studs

Building Construction - Building Construction Industry Discussions. 

Bookmark this page:  YahooMyWeb Yahoo!  Google Google  Windows Live Favorites Windows Live  del.icio.us del.icio.us  digg digg  Add to Netscape Netscape
Subject Author Date
Multiple holes in load bearing studs parkerea 09-24-2006
If you were  Registered and logged in, you could reply and use other advanced thread options
Posted by parkerea on September 24, 2006, 1:00 pm
I want to know the code for boring holes in 2x4 studs in a load bearing
wall.



I have found the reference that says holes can be up to 40% of a the stud's
depth in a load bearing wall, 60% in a non-load bearing wall, but is there
any issue on multiple holes? Is there any code that says how far apart holes
must be or how many are allowed? Can you make swiss cheeze of a stud and
stay within code as long as they all pass the 40% rule?



For example, if a wall will contain 2 water pipes, 110v romex, CAT-5e and
coax, with the CAT-5e & coax can go through the same hole, that makes 4
holes.





Thank you in advance,

parkerea




Posted by RicodJour on September 24, 2006, 6:18 pm
parkerea wrote:
> I want to know the code for boring holes in 2x4 studs in a load bearing
> wall.
>
> I have found the reference that says holes can be up to 40% of a the stud's
> depth in a load bearing wall, 60% in a non-load bearing wall, but is there
> any issue on multiple holes? Is there any code that says how far apart holes
> must be or how many are allowed? Can you make swiss cheeze of a stud and
> stay within code as long as they all pass the 40% rule?
>
> For example, if a wall will contain 2 water pipes, 110v romex, CAT-5e and
> coax, with the CAT-5e & coax can go through the same hole, that makes 4
> holes.

Wiring holes are much smaller than 40%. If you space the holes 15 or
20 diameters (for small holes) away from each other there will be no
appreciable difference in strength.

R


Posted by Glenn on September 24, 2006, 7:00 pm
Also, I try to center the holes where there are almost no bending
moments.

> parkerea wrote:
> > I want to know the code for boring holes in 2x4 studs
> > in a load bearing wall.
> >
> > I have found the reference that says holes can be up to
> > 40% of a the stud's depth in a load bearing wall, 60%
> > in a non-load bearing wall, but is there any issue on
> > multiple holes? Is there any code that says how far
> > apart holes must be or how many are allowed? Can you
> > make swiss cheeze of a stud and stay within code as
> > long as they all pass the 40% rule?
> >
> > For example, if a wall will contain 2 water pipes, 110v
> > romex, CAT-5e and coax, with the CAT-5e & coax can go
> > through the same hole, that makes 4 holes.
>
> Wiring holes are much smaller than 40%. If you space the
> holes 15 or 20 diameters (for small holes) away from each
> other there will be no appreciable difference in strength.
>
> R


Posted by parkerea on September 28, 2006, 12:22 am
Thank you for your response. However, I am more concerned with code than
with actual strength. Although the wall in question is officially load
bearing, the load is quite modest -- single story with open beam ceiling,
and a significant portion of the roof weight is taken by the central beam.



We are planning a significant addition to our house. My plan here is to run
CAT-5e through the walls while they are still open. According to my plan, on
at least 1 wall I intend to run under a low window where there is about 2'
of space between the floor & window. There will be at least 3 things running
through that space: existing Romex, new CAT-5e, and a new flex conduit
(which will be empty, put there "just in case" something like fiber optics
for the home becomes reality the future). That means there will be less than
6" between each, depending on where the Romex is.



Since I am the homeowner, not a knowledgeable contractor, I want to be sure
I don't violate code and cause problems. I confirmed with the Dept of Public
Works building office that I don't need a permit for the low voltage stuff
as long as nothing is hard wired into the a/c line. However, I just want to
be sure that I don't violate any framing code and cause headaches for
myself.



By the way, yes, I understand that the 40% is much larger than needed for
wiring. From what I understand, a 7/8" hole is typical, leaving about 1-1/4"
of stud on each side so you don't need nail stops.





Thanks again,

parkerea



"RicodJour" wrote in message
> parkerea wrote:
> > I want to know the code for boring holes in 2x4 studs in a load bearing
> > wall.
> >
> > I have found the reference that says holes can be up to 40% of a the
stud's
> > depth in a load bearing wall, 60% in a non-load bearing wall, but is
there
> > any issue on multiple holes? Is there any code that says how far apart
holes
> > must be or how many are allowed? Can you make swiss cheeze of a stud and
> > stay within code as long as they all pass the 40% rule?
> >
> > For example, if a wall will contain 2 water pipes, 110v romex, CAT-5e
and
> > coax, with the CAT-5e & coax can go through the same hole, that makes 4
> > holes.
>
> Wiring holes are much smaller than 40%. If you space the holes 15 or
> 20 diameters (for small holes) away from each other there will be no
> appreciable difference in strength.
>
> R



Posted by RicodJour on September 28, 2006, 8:48 am
parkerea wrote:
> Thank you for your response. However, I am more concerned with code than
> with actual strength. Although the wall in question is officially load
> bearing, the load is quite modest -- single story with open beam ceiling,
> and a significant portion of the roof weight is taken by the central beam.
>
> We are planning a significant addition to our house. My plan here is to run
> CAT-5e through the walls while they are still open. According to my plan, on
> at least 1 wall I intend to run under a low window where there is about 2'
> of space between the floor & window. There will be at least 3 things running
> through that space: existing Romex, new CAT-5e, and a new flex conduit
> (which will be empty, put there "just in case" something like fiber optics
> for the home becomes reality the future). That means there will be less than
> 6" between each, depending on where the Romex is.
>
> Since I am the homeowner, not a knowledgeable contractor, I want to be sure
> I don't violate code and cause problems. I confirmed with the Dept of Public
> Works building office that I don't need a permit for the low voltage stuff
> as long as nothing is hard wired into the a/c line. However, I just want to
> be sure that I don't violate any framing code and cause headaches for
> myself.
>
> By the way, yes, I understand that the 40% is much larger than needed for
> wiring. From what I understand, a 7/8" hole is typical, leaving about 1-1/4"
> of stud on each side so you don't need nail stops.

Make the holes no larger than necessary if you're concerned. 3/4" is
large enough for everything except the flex conduit. Electrician's
like to drill larger holes as it makes it easier to pull the wire.
Offset the holes a little bit so they don't line up down the middle of
the stud. Other than that - don't worry about it.

R


Similar ThreadsPosted
Is it a load-bearing wall? April 9, 2007, 11:40 am
Removing Basement wall, load bearing? January 28, 2008, 5:59 pm
Cutting load bearing members - standard practices September 27, 2006, 6:44 am
Load Bearing Partition- wood frame residential March 15, 2007, 9:31 am
Standby Load, Plug Load February 5, 2008, 9:36 pm
Drilling Small Holes in Granite December 18, 2006, 12:02 pm
Code Allowance for Holes in Joists Bob K February 15, 2008, 7:57 am
Re: Code Allowance for Holes in Joists Bob K February 16, 2008, 12:23 pm
Cutting holes in engineered wood rim board? October 15, 2006, 11:18 am
Trusses not over studs? July 10, 2006, 1:26 pm

Contact Us | Privacy Policy

XML SitemapXML Sitemap