|
Posted by RicodJour on September 28, 2006, 8:48 am
parkerea wrote:
> Thank you for your response. However, I am more concerned with code than
> with actual strength. Although the wall in question is officially load
> bearing, the load is quite modest -- single story with open beam ceiling,
> and a significant portion of the roof weight is taken by the central beam.
>
> We are planning a significant addition to our house. My plan here is to run
> CAT-5e through the walls while they are still open. According to my plan, on
> at least 1 wall I intend to run under a low window where there is about 2'
> of space between the floor & window. There will be at least 3 things running
> through that space: existing Romex, new CAT-5e, and a new flex conduit
> (which will be empty, put there "just in case" something like fiber optics
> for the home becomes reality the future). That means there will be less than
> 6" between each, depending on where the Romex is.
>
> Since I am the homeowner, not a knowledgeable contractor, I want to be sure
> I don't violate code and cause problems. I confirmed with the Dept of Public
> Works building office that I don't need a permit for the low voltage stuff
> as long as nothing is hard wired into the a/c line. However, I just want to
> be sure that I don't violate any framing code and cause headaches for
> myself.
>
> By the way, yes, I understand that the 40% is much larger than needed for
> wiring. From what I understand, a 7/8" hole is typical, leaving about 1-1/4"
> of stud on each side so you don't need nail stops.
Make the holes no larger than necessary if you're concerned. 3/4" is
large enough for everything except the flex conduit. Electrician's
like to drill larger holes as it makes it easier to pull the wire.
Offset the holes a little bit so they don't line up down the middle of
the stud. Other than that - don't worry about it.
R
|