Posted by Steve Barker LT on September 11, 2007, 10:08 pm
ok, after putting on a #4 ground to the outside rods AND to the plumbing
inside, my local city inspector says the wire has to be in conduit anywhere
it's in close contact with concrete. I totally missed this in the code.
Can someone cite this for me? The reason i went with the #4 is because the
book said it didnt' need conduit for physical protection. I never saw any
mention of concrete or electrolisys.

thanks

--
Steve Barker



Posted by Erik Dillenkofer on September 12, 2007, 5:34 am
The inspector may be referrring to NEC 250.62:

Grounding Electrode Conductor Material.

The grounding electrode conductor shall be of copper, aluminum, or
copper-clad aluminum. The material selected shall be resistant to any
corrosive condition existing at the installation or shall be suitable
protected against corrosion. The conductor shall be solid or stranded,
insulated, covered, or bare.

Concrete is corrosive to copper.

> ok, after putting on a #4 ground to the outside rods AND to the plumbing
> inside, my local city inspector says the wire has to be in conduit
> anywhere
> it's in close contact with concrete. I totally missed this in the code.
> Can someone cite this for me? The reason i went with the #4 is because
> the
> book said it didnt' need conduit for physical protection. I never saw any
> mention of concrete or electrolisys.
>
> thanks
>
> --
> Steve Barker
>
>



Similar ThreadsPosted
#6 ground wire directly to xformer? June 2, 2008, 4:03 am
Introducing The Hz2.1 Portable Hot Stamp Wire Marker to Meet Industry's Need for Flexible, Cost-effective Wire Marking April 30, 2007, 4:07 pm
sell building material ,wire mesh ,welded wire mesh December 24, 2006, 12:26 am
sell wire mesh December 6, 2006, 1:46 am
stucco/wire lath question May 6, 2008, 8:19 pm
Aluminum vs Copper Wire for Buried Main Power Line November 11, 2006, 6:22 pm
Ping Bob Morrison November 7, 2006, 3:08 pm
Above ground pool on garage pad. July 5, 2006, 5:30 pm
ground slopes toward foundation September 4, 2007, 12:07 am
PING marson: ball shut-off valve February 28, 2007, 10:21 pm

Contact Us | Privacy Policy

XML SitemapXML Sitemap