Sizing of Towel Radiator Yaz 10-03-2006
If you were  Registered and logged in, you could reply and use other advanced thread options
Posted by Yaz on October 3, 2006, 12:33 pm
How do I work out the "BTU at 50c degrees Output" needed for a shower.

The size of one of the showers is 3070mm x 1700mm by 2400mm height.

Any advice?

Yaz



Posted by CWatters on October 3, 2006, 4:42 pm

> How do I work out the "BTU at 50c degrees Output" needed for a shower.
>
> The size of one of the showers is 3070mm x 1700mm by 2400mm height.
>
> Any advice?

To work out the size of any rad you need to know a) The U values of the
walls, floor and windows b) The area of all walls and windows c) The
temperature on the other side of those walls and windows d) The desired room
temperature.

Then you feed the lot into a Heat Loss Calculator or similar computer
program that works out the heat flowing into and out of all the walls. It
adds the lot up and works out if you will need to heat (or cool) a room to
maintain a particular temperature. It then calculates how much power that
will take and spits out an answer in BTU or KW.....

...or you use your years of experience and guess.




Posted by Yaz on October 4, 2006, 6:03 am

size of any rad you need to know a) The U values of the
> walls, floor and windows

How does one work out U Values?

>
> Then you feed the lot into a Heat Loss Calculator or similar computer
> program that works out the heat flowing into and out of all the walls. It
> adds the lot up and works out if you will need to heat (or cool) a room to
> maintain a particular temperature. It then calculates how much power that
> will take and spits out an answer in BTU or KW.....
>
Is there such a thing as a free calculater online?

Yaz



Posted by CWatters on October 4, 2006, 6:23 am

>
the
> size of any rad you need to know a) The U values of the
> > walls, floor and windows
>
> How does one work out U Values?

Sorry I think U values (UK) = R values(USA). ...

http://www.ftc.gov/bcp/conline/pubs/alerts/rvaluealrt.htm

It's the thermal resistance. In SI units I think its measured in watts per
degree K per square meter. You should be able to find tables for the
particular construction you have somewhere.








Posted by Bobk207 on October 4, 2006, 10:36 pm

Yaz wrote:
> size of any rad you need to know a) The U values of the
> > walls, floor and windows
>
> How does one work out U Values?
>
> >
> > Then you feed the lot into a Heat Loss Calculator or similar computer
> > program that works out the heat flowing into and out of all the walls. It
> > adds the lot up and works out if you will need to heat (or cool) a room to
> > maintain a particular temperature. It then calculates how much power that
> > will take and spits out an answer in BTU or KW.....
> >
> Is there such a thing as a free calculater online?
>
> Yaz

Yaz-

I'm not exactly sure what you're trying to size (towel radiator?) or
what you're trying to heat (a shower stall or an entire bathroom?)

In any case here is a link provided to me by "the all knowing Google"

http://www.hvaccomputer.com/gindex.asp

not free but pretty cheap for what it can do


On the other hand you could do an experiment & see how much heat input
you need to heat your space

recently I had the need to keep a shower stall warm over night with the
bathroom window open. I put a 100watt light bulb in the stall & it
kept the stall at about 75F (the outside temp was about 58F over
night.)

You could do the same but you'll either have to wait until the weather
turns colder

or

ratio the heat demand by the indoor / outdoor temp difference when you
do the experiment to the the indoor / outdoor temp difference for the
coldest day expected.

The size bulb that keeps the shower warm is the constant heat input
that would be required. I would double (or 1.5x) the heat capacity
radiator so that it wouldn't have to run full open all the time plus
it would give you some heating reserve if didn't choose a cold enough
day.


BTW the heat output of the radiator would most likely be expressed in
BTU per hour, watts or kwatts.

cheers
Bob