Posted by Yaz on February 27, 2008, 11:24 am
uk
>
>>I actually need a reducer 6" to 3.25"+-. Has anyone done this and how will
>>it affect the performance of the fan?
>
>
> For questions such as this, I usually contact the manufacturer. They
> already know the answers in most cases. What country are you in?
>
>
>
>> Sid
>>> Has anyone come across this. I need to vent out my wetroom extrator fan
>>> that is cieling mounted through the roof. I have a Redland ministonewols
>>> vent out tilethat has a 83mm spigot. However the fan I have has a 150mm
>>> requirment. There is not a redland one available. So I need to secure
>>> something that fits between 150mm spigot to the tile (83mm spigot). The
>>> distance between the two is about 1.2 metres only straight up to roof..
>>>
>>> Any advice.
>>> Sid
>>
>> Sounds like you likely need a larger "vent out" as (US) you have a 6"
>> outlet on the fan and only a 3.5" "vent out". Sounds like you may just
>> need a 4 x 6 IR (increaser reducer). This is in US inches, 4" to 6"
>> round sheet metal increaser/reducer given the metric I am not sure but
>> if you are in the US they are available anywhere. That said, the fan
>> isnt going to perform to it specs being choked down to a 3.5"-4"
>> outlet.
>>
>> Mark
>>
>
|