80% gas furnace RUUD in a icyenene foamed attic - Need a combustion air vent solution mross 03-15-2009
If you were  Registered and logged in, you could reply and use other advanced thread options
Posted by on March 15, 2009, 9:26 pm
Inspector is telling me that the furnace needs access to fresh air. If
I put a vent in the attic it will defeat the whole purpose of the
upgraded insulation. Please give me your thoughts.

Mark

Posted by on March 15, 2009, 10:35 pm
On Sun, 15 Mar 2009 18:26:59 -0700 (PDT), mross@moderntechhomes.com
wrote:

>Inspector is telling me that the furnace needs access to fresh air. If
>I put a vent in the attic it will defeat the whole purpose of the
>upgraded insulation. Please give me your thoughts.
>Mark

        Stop playing DIY'r and get a pro to do it. Done RIGHT, there
is no problem.


--
Click here every day to feed an animal that needs you today !!!
www.theanimalrescuesite.com/

Paul ( pjm @ pobox . com ) - remove spaces to email me
'Some days, it's just not worth chewing through the restraints.'
'With sufficient thrust, pigs fly just fine.'
HVAC/R program for Palm PDA's
Free demo online at www.pmilligan.net/palm/
Free 'People finder' program now at www.pmilligan.net/finder.htm

Posted by Stormin Mormon on March 15, 2009, 10:46 pm
So, run a tube from the outdoors to the furnace. Like the 90
percenters.

--
Christopher A. Young
Learn more about Jesus
www.lds.org
.


Inspector is telling me that the furnace needs access to
fresh air. If
I put a vent in the attic it will defeat the whole purpose
of the
upgraded insulation. Please give me your thoughts.

Mark



Posted by Alexander on March 16, 2009, 12:10 am
mross@moderntechhomes.com wrote:
> Inspector is telling me that the furnace needs access to fresh air. If
> I put a vent in the attic it will defeat the whole purpose of the
> upgraded insulation. Please give me your thoughts.
>
> Mark

Put the furnace outside.

Posted by Lefty on March 16, 2009, 6:53 am
Two things;

1.) You needed someone else to inform you that fire needs air to burn??

2.) You foamed your attic to the point of removing *ALL* ventilation.

Please clarify. I think much bigger problems may lie ahead for you.


> Inspector is telling me that the furnace needs access to fresh air. If
> I put a vent in the attic it will defeat the whole purpose of the
> upgraded insulation. Please give me your thoughts.
> Mark



Page 1 of 2       1 2 > last >>
Similar ThreadsPosted
HVAC man uses condenser fan to vent attic October 21, 2006, 4:59 pm
Does an attic vent need a firestat switch? January 30, 2009, 12:14 pm
furnace vent tube in wall and stove hood vent March 13, 2007, 11:12 pm
Ruud UGPL Gas Furnace problem July 15, 2006, 1:39 pm
Dirty Sock Syndrome-Is there a solution? November 28, 2007, 11:03 pm
Re: Dirty Sock Syndrome-Is there a solution? December 4, 2007, 7:20 pm
Re: A solution to one of the major problems faced in the automated HVAC domain - APC (Aftek’s Protocol Converter) August 12, 2009, 11:31 am
Trane Nat. Vent furnace December 1, 2006, 9:13 am
Furnace vent question ... July 4, 2008, 9:30 pm
High eff furnace vent May 11, 2009, 1:10 pm

Contact Us | Privacy Policy

XML SitemapXML Sitemap