Posted by on July 21, 2006, 1:54 pm
I have a split Carrier unit (inside gas furnace/blower & outside
compressor). The inside blower moter (2-speed) will not start as
normal. I have elimated the thermostat (jumpered at the unit), it also
appears the capacitor and motor are OK (I placed jumper from COM to
both HI and LO connectors and the motor runs fine. That leaves the
control board. The transformer seems OK (24V to 120V), but the relays
do not seem to pull in. Any other steps I can take? Is it worth
trying to troubleshoot down to the board level, or just replace? Any
idea where I can acquire a board if needed? Thanks!!


Tankless Water Heaters 468x60
Posted by Noon-Air on July 21, 2006, 10:28 pm

>I have a split Carrier unit (inside gas furnace/blower & outside
> compressor).

I'm sorry.

> The inside blower moter (2-speed) will not start as
> normal.

I guess its broke

> I have elimated the thermostat (jumpered at the unit), it also
> appears the capacitor and motor are OK (I placed jumper from COM to
> both HI and LO connectors and the motor runs fine.

ok.......

> That leaves the
> control board. The transformer seems OK (24V to 120V), but the relays
> do not seem to pull in.

I hate it when that happens...

> Any other steps I can take?

yes

> Is it worth trying to troubleshoot down to the board level,

no

> or just replace?

yes

> Any idea where I can acquire a board if needed?

yes

> Thanks!

your welcome



Posted by Stormin Mormon on July 22, 2006, 9:07 am
If you've got some electronic skills, you can troubleshoot within the
board. Many people don't.

I usually call my wholesale parts house for replacement boards.

--

Christopher A. Young
You can't shout down a troll.
You have to starve them.
.

I have a split Carrier unit (inside gas furnace/blower & outside
compressor). The inside blower moter (2-speed) will not start as
normal. I have elimated the thermostat (jumpered at the unit), it
also
appears the capacitor and motor are OK (I placed jumper from COM to
both HI and LO connectors and the motor runs fine. That leaves the
control board. The transformer seems OK (24V to 120V), but the relays
do not seem to pull in. Any other steps I can take? Is it worth
trying to troubleshoot down to the board level, or just replace? Any
idea where I can acquire a board if needed? Thanks!!



Posted by Bubba on July 24, 2006, 8:58 am
On Sat, 22 Jul 2006 13:07:50 GMT, "Stormin Mormon"

>If you've got some electronic skills, you can troubleshoot within the
>board. Many people don't.

Once again, this leaves Stormy out.
>
>I usually call my wholesale parts house for replacement boards.

Im sure they really love you, Stormy. Cant diagnose a single thing.
Just order up a box full of parts and keep replacing until you find
the right part to make it work again.
Bubba

Similar ThreadsPosted
Opinion on Price Please - $1900 2.5 Ton Air Handler Attic Install 7.5kw Heater December 12, 2007, 1:51 pm
Should condenser fan always run while fan is blowing? May 27, 2008, 6:36 pm
Furnace Problems - Blowing cold air - Please help October 13, 2007, 1:29 pm
thermostat calling for heat, not blowing then thermostat switches to heat 2 October 24, 2008, 8:37 am

Contact Us | Privacy Policy

XML SitemapXML Sitemap