Posted by Mike on April 18, 2007, 8:14 pm
Hello,
I have a Frigidaire - FG6RA air handler that has been giving me
trouble for about a month.I will try to explain this as best I can.
Things I know:
The pressure switch must be open before the condenser comes on.
It must be closed for the burner to light.

I was having trouble in that the thing would cycle and the pilot would
glow but the flame would go right out. The error message on the board
said the the preasure switch was closed when the condenser started.
Fair enough. I spoke to some people and replaced the PS. It worked for
a few days and now it doesnt.
This is what I tested and the results:
I removed the leads from the PS. I hooked up the MultiMeter to the
leads to check continuity. When I turned on the furnace the meter
would beep intermittently very fast and the condenser would NOT come
on. It should be open, right. Then I pull the leads off and the
condenser DOES start. The only way it would work now is if I jump it
at this point. My Multimeter isnt completing the circuit is it??
I am realy at a loss and any help is appreciated
Thanks,
Mike

Posted by on April 18, 2007, 9:16 pm

>Hello,
>I have a Frigidaire - FG6RA air handler that has been giving me
>trouble for about a month.I will try to explain this as best I can.
>Things I know:
>The pressure switch must be open before the condenser comes on.
>It must be closed for the burner to light.
>
>I was having trouble in that the thing would cycle and the pilot would
>glow but the flame would go right out. The error message on the board
>said the the preasure switch was closed when the condenser started.
>Fair enough. I spoke to some people and replaced the PS. It worked for
>a few days and now it doesnt.
>This is what I tested and the results:
>I removed the leads from the PS. I hooked up the MultiMeter to the
>leads to check continuity. When I turned on the furnace the meter
>would beep intermittently very fast and the condenser would NOT come
>on. It should be open, right. Then I pull the leads off and the
>condenser DOES start. The only way it would work now is if I jump it
>at this point. My Multimeter isnt completing the circuit is it??
>I am realy at a loss and any help is appreciated
>Thanks,
>Mike

        Speak to some people again.

        This time you need to say "When can you come out and fix my
furnace ?"


--
Click here every day to feed an animal that needs you today !!!
http://www.theanimalrescuesite.com/

Paul ( pjm @ pobox . com ) - remove spaces to email me
'Some days, it's just not worth chewing through the restraints.'
'With sufficient thrust, pigs fly just fine.'
HVAC/R program for Palm PDA's
Free demo now available online http://pmilligan.net/palm/

Posted by daytona° on April 18, 2007, 9:33 pm
Nordyne...!!!! isn't that kin to Janitrol

> Hello,
> I have a Frigidaire - FG6RA air handler that has been giving me
> trouble for about a month.I will try to explain this as best I can.
> Things I know:
> The pressure switch must be open before the condenser comes on.
> It must be closed for the burner to light.
>
> I was having trouble in that the thing would cycle and the pilot would
> glow but the flame would go right out. The error message on the board
> said the the preasure switch was closed when the condenser started.
> Fair enough. I spoke to some people and replaced the PS. It worked for
> a few days and now it doesnt.
> This is what I tested and the results:
> I removed the leads from the PS. I hooked up the MultiMeter to the
> leads to check continuity. When I turned on the furnace the meter
> would beep intermittently very fast and the condenser would NOT come
> on. It should be open, right. Then I pull the leads off and the
> condenser DOES start. The only way it would work now is if I jump it
> at this point. My Multimeter isnt completing the circuit is it??
> I am realy at a loss and any help is appreciated
> Thanks,
> Mike



Posted by on April 18, 2007, 10:43 pm

> Nordyne...!!!! isn't that kin to Janitrol


No





Posted by on April 18, 2007, 10:45 pm


> I am realy at a loss

So are your technical troubleshooting skills...

> and any help is appreciated

It's time to call an HVAC repair company.



Page 1 of 2       1 2 > last >>
Similar ThreadsPosted
Is an Old Air Handler Worthless December 26, 2006, 11:27 am
Air Handler and Rep Woes January 8, 2007, 4:15 pm
Trane air handler too noisy July 30, 2006, 9:12 pm
my trane air handler air blower is on 24 hours a day September 2, 2006, 11:26 pm
Best cabinets - Heat Pump/Air Handler November 28, 2006, 10:13 pm
Upgrade air handler Motor to higher RPM January 29, 2007, 4:55 pm
Air handler coil access for cleaning May 4, 2007, 11:53 am
Attic air handler coil cleaning May 4, 2007, 12:09 pm
Excessive moisture on outside surfaces of air handler August 15, 2007, 10:08 pm
Insulation question about air handler and crawl space July 8, 2007, 10:15 pm

Contact Us | Privacy Policy

XML SitemapXML Sitemap