Air in Oil Feed Line to Furnace jablakeman 12-15-2007
If you were  Registered and logged in, you could reply and use other advanced thread options
Posted by on December 15, 2007, 11:20 am
Furnace technician spent 5 hours trying to fix this problem (to no
avail):

At start of season, I purge my single-line oil system by turning on
pump and open the bleed value, to fill the line with oil and get rid
of any air.

I have a tank about 4 ft below the pump at the furnace, with the
single copper supply line going across the top of the basement, about
6 feet above the pump. A standard filter is in the line 3 ft from the
pump. The filter was changed, along with the rubber lid gasket.

But somehow, air gets in the line. After purging, it's OK and starts
nicely and always and continues to run. But when left overnight, air
enters the line and the shutoff kicks in.

When I then open the air bleed to purge the line (with the pump turned
back on), foam comes out for a lengthy period of time.

I'm presuming that during the night oil is draining back down the
supply line into the tank, which is below the level of the pump,
filling the 20 ft supply line with air.

Worse, when I try to bleed or purge the air out of the pump and line,
what comes out is intermittently foam, then some fuel oil with a bit
of air, and occassionally straight, clear tawny fuel. I can bleed out
a half gallon of fuel, but the problem remains.

Can the problem be solved by putting some sort of check valve on the
supply line near the pump, to stop the back flow of oil back into the
lower tank? Where do I get one of these check valves? What do I ask
for?

And of course, from reading the literature on this, many are going to
say that I need to simply create a two-line system, to send the excess
air back into the tank.

But since the system runs well when there is no air in the feed line
(after extensive purging), I'd like to at least try a supposedly
cheaper check-valve in the line first..

The tech guy said that this was the weirdest, most difficult and
enigmatic problem he's ever encountered.

What are the (probably many) soutions to be tried? I'm at whit's end.

--John

Similar ThreadsPosted
2 line oil line hook up.DOMESTIC. November 18, 2006, 9:53 pm
R22 TO 410: HAVE TO REPLACE LINE?? July 6, 2007, 8:46 am
R22 TO 410: HAVE TO REPLACE LINE?? again July 6, 2007, 8:53 am
line set replacement help May 31, 2007, 10:51 pm
Chimney line and flue August 9, 2006, 4:30 pm
liquid line in condensate June 27, 2007, 7:56 am
Re-use R22 line set for Puron system November 4, 2006, 6:24 pm
water line air test September 17, 2007, 8:19 pm
Primary AC Drain Line vent July 28, 2006, 2:36 pm
Trane DLR wants new Mid Price/Quality line October 9, 2006, 6:13 pm

Contact Us | Privacy Policy

XML SitemapXML Sitemap