|
Posted by Noon-Air on July 21, 2006, 12:18 am
> Help! I have a roof mounted heat pump system. It had a pretty much
> broken honeywell mechanical thermostat installed but had the following
> symptoms:
>
> In order to get the compressor to kick on an cool, I had to crank the
> thermostat down to the min and tap the mercury switch thingy at the end
> of thermo spring to make sure it made good contact. The compressor then
> comes on fine.
>
> The air handler however won't turn off without cutting off the breaker.
> I suspect the person who wired the thermostat didn't have any idea what
> he was doing judging from some of the other wiring in the house.
>
> My handyman tried to wire up a new digital thermostat first by matching
> up colors (nothing worked) then by trying to determine what each wire
> was for and hood them to the correct spot on the thermostat. We are now
> in same the situation as with the mechanical. Airhandler runs
> continuously, and the compress will not come on since I can't manually
> ensure the connection is made as I could with the mechanical one.
>
> I have read some stuff here that say if the air handler is running all
> the time it might be a relay, or control board. Does wiring problems
> seem more likely in this case? Is there a way to wire the thing to
> produce the symptoms I am seeing?
>
> Any help would be GREAT!
>
> Thanks!
A "handy man" IS NOT an HVAC technician, nor is a a proctologist a dentist.
Call a *competent* HVAC tech to 1) correct all the problems 2) clean and
service the system, 3) correctly balance the refrigerant charge and finally
4) write you an invoice.
|