An Airflow Question About Merv Ratings (Air-handler Filters) use_a_hammer 07-29-2006
If you were  Registered and logged in, you could reply and use other advanced thread options
Posted by on July 29, 2006, 1:19 am
Is there a difference in the airflow between a Merv 7 -vs- Merv 11?

These are the filters http://www.airguard.com/pleated.html I'm talking
about in case brand makes any difference. I'm looking at the "DP Max"
(merv 7) vs "Powerguard" (merv11)

I see they have an efficiency rating, whatever that is. Does a Merv 11
restrict more air than a Merv 7?

I'm looking for good airflow and a "HEPA type" filter combined.


PexSupply Save 10 468x60
Posted by udarrell on July 29, 2006, 11:59 am
use_a_hammer@yahoo.com wrote:

>Is there a difference in the airflow between a Merv 7 -vs- Merv 11?
>
>These are the filters http://www.airguard.com/pleated.html I'm talking
>about in case brand makes any difference. I'm looking at the "DP Max"
>(merv 7) vs "Powerguard" (merv11)
>
>I see they have an efficiency rating, whatever that is. Does a Merv 11
>restrict more air than a Merv 7?
>
>
A higher static pressure will restrict more of the airflow.

>I'm looking for good airflow and a "HEPA type" filter combined.
>
>
You need to know the air velocity through the filter then look at the
initial resistance or pressure drop.
Hopefully you return air & filter grille were sized so you have 300-FPM
rather than 500-fpm or more!
One for example has .26 pres. drop at 300-fpm but .54 pres. resistance
at 50-fpm air velocity through the filter!
Most residential blower systems are rated at .50-ESP External Static
Pressure.
When the filter begins loading at 500-fpm you will have a big drop off
in airflow!
- udarrell

--
Air Conditioning's Affordable Path to the "Human Comfort Zone Goal"
http://www.udarrell.com/air-conditioning-total-heat-enthalpy-latent-heat.html
For HVAC Techs:
http://www.udarrell.com/ac-trouble-shooting-superheat-subcooling.html

Similar ThreadsPosted
Seeking Opinions on air return filters and air vent filters June 4, 2007, 5:22 pm
Two small fans in series (airflow) better than one bigger one? May 25, 2008, 5:17 pm
Airhandler on continuously / compress not coming on July 20, 2006, 11:36 pm
ARI ratings site? October 17, 2006, 11:39 am
AC Unit Sound Ratings May 21, 2007, 11:51 pm
heat pump kw ratings June 5, 2007, 5:49 am
Filters July 21, 2006, 1:50 pm
CFM Filters August 3, 2006, 11:11 am
TX valve with Amana/Goodman heat pump and ARI ratings August 19, 2006, 3:59 am
Is it bad to use damp filters December 14, 2006, 3:32 pm

Contact Us | Privacy Policy

XML SitemapXML Sitemap