Hello all,

I have a thermostat that's going to a cooling only box above an office
in an eleven story building that's reading a temperature of -327.68
degrees, and I'm pretty sure that's not quite right. Any idea what the
cause is, and what the fix might be?

Thanks


Posted by daytona° on December 1, 2006, 12:55 pm
Sounds like it took an electrical spike and blew out the eprom


> Hello all,
>
> I have a thermostat that's going to a cooling only box above an office
> in an eleven story building that's reading a temperature of -327.68
> degrees, and I'm pretty sure that's not quite right. Any idea what the
> cause is, and what the fix might be?
>
> Thanks
>



Posted by on December 1, 2006, 12:56 pm
wrote:



>Sounds like it took an electrical spike and blew out the eprom

Nah - you'd have no comm at all.


>
>
>> Hello all,
>>
>> I have a thermostat that's going to a cooling only box above an office
>> in an eleven story building that's reading a temperature of -327.68
>> degrees, and I'm pretty sure that's not quite right. Any idea what the
>> cause is, and what the fix might be?
>>
>> Thanks
>>
>

--
Click here every day to feed an animal that needs you today !!!
http://www.theanimalrescuesite.com/

Paul ( pjm @ pobox . com ) - remove spaces to email me
'Some days, it's just not worth chewing through the restraints.'
'With sufficient thrust, pigs fly just fine.'
HVAC/R program for Palm PDA's
Free demo now available online http://pmilligan.net/palm/

Posted by Jake on December 1, 2006, 6:55 pm
.p.jm@see_my_sig_for_address.com wrote:
> wrote:
>
>
>
>> Sounds like it took an electrical spike and blew out the eprom
>
> Nah - you'd have no comm at all.
>

Seems that... as I recall... a 'no-count' at an analog input will give
you a number very similar....

A scaled but open 4-20 on a 8 bit processor, perhaps?

Jake

Posted by on December 1, 2006, 7:06 pm

>.p.jm@see_my_sig_for_address.com wrote:
>> wrote:
>>
>>
>>
>>> Sounds like it took an electrical spike and blew out the eprom
>>
>> Nah - you'd have no comm at all.
>>
>
>Seems that... as I recall... a 'no-count' at an analog input will give
>you a number very similar....
>
>A scaled but open 4-20 on a 8 bit processor, perhaps?
>
>Jake

        It's a simple thermistor in a stock pre-configured VAV box
controller, I forget the specs offhand. I seem to recall it does that
-327 on open, and will show 999 on short. All depends on how the
point is mapped in software, of course - you could scale it any way
you want. So, 'open' is most likely, as you say.


--
Click here every day to feed an animal that needs you today !!!
http://www.theanimalrescuesite.com/

Paul ( pjm @ pobox . com ) - remove spaces to email me
'Some days, it's just not worth chewing through the restraints.'
'With sufficient thrust, pigs fly just fine.'
HVAC/R program for Palm PDA's
Free demo now available online http://pmilligan.net/palm/

Page 1 of 4       1 2 3 > last >>
Similar ThreadsPosted
No AC functions18-5 to Tstat and an 18-2 to compressor May 28, 2007, 10:39 am
Would like opinions on the Infinity Air Purifier August 13, 2007, 10:47 am
Should my house reach 75 degrees? June 10, 2008, 6:28 am
Carrier Infinity and Thermal cutouts August 20, 2006, 9:42 pm
Upstairs is 5 degrees warmer than downstairs June 18, 2007, 1:46 pm
Using water at 57 degrees to cool house September 5, 2008, 12:40 am
Carrier Infinity furnace low heat option? January 18, 2007, 2:35 pm

Contact Us | Privacy Policy

XML SitemapXML Sitemap