Home Page link

Armstrong EG6A125DC15-13 Roll Out Switch

HVAC Discussions - Heating, ventilation and air conditioning. 

Page 1 of 3       1 2 3 > last >> Bookmark this page:  YahooMyWeb Yahoo!  Google Google  Windows Live Favorites Windows Live  del.icio.us del.icio.us  digg digg  Add to Netscape Netscape
Subject Author Date
Armstrong EG6A125DC15-13 Roll Out Switch Bob Shuman 02-14-2008
If you were  Registered and logged in, you could reply and use other advanced thread options
Posted by Bob Shuman on February 14, 2008, 10:52 am
Sorry in advance for the length of this post, but I wanted to try to be as
specific as possible on this problem.

I have two 16+ year old Armstrong natural gas furnaces (model number in
subject line above) for my residence. Both identical spark ignition,
125,000 BTU 5-burner units.

I had a soot build up problem with the lower level unit (the one that is
used most frequently) that caused the flame on the left-most burner to
slightly roll out from the heat exchanger chamber, so I called a reputable
local service company to come out and clean both of the units.

They removed the flue and front panel and then thoroughly cleaned the sooted
up heat exchanger and flue vent. (They found the heat exchange cavity by
the leftmost burner completely blocked with soot). They also removed and
cleaned all the burners too and then re-assembled everything. In this
process, they also discovered that the air mixture controls for the 5
burners were shut down completely and opened them up (all the way to max
settings) to let the burners "breathe" properly. The flame tip color turned
a much deeper blue and the dark blue "inner" flame mantles appeared to go
down to about 3/4" long. The good news here was that this stopped the
orange tipped flame from rolling out of the combustion chamber and resulted
in a noticeably hotter flame. (I've also been monitoring CO in the area
around the furnaces and it has gone from 20+ PPM when the furnace was
running to 0 PPM now.)

Unfortunately, changing the air mixture seems to have introduced a new
problem. Now during extended runs of this furnace (for example when coming
up to temperature in the AM after a setback period the previous night), the
flue roll out switch trips shutting down the system. When this happens it
requires a manual reset of the roll out switch button. If the furnace is
simply "cycling" to maintain temperature, then it does not seem to trip and
everything is fine. The drafting on the furnace seems to be good so I
suspected that it was just burning too hot for the switch.

Thinking this was possibly a weak/old/failing roll out switch, I swapped the
switch with the one in my upstairs furnace, but this did not fix the problem
and it still tripped just the same (and the upstairs unit which now has the
switch from the downstairs unit did not trip). At this point, I have tried
backing off the air mixture to about 50% from being wide open on all 5
burners, but this too seems to have had no affect.

The only thing that I've found that does seem to prevent this switch from
tripping is to manually feather the gas shut off valve to the point where I
can observe a noticeable reduction in the flame height on the 5 burners.

I'd appreciate thoughts on what is happening here. I do not believe it is
an issue with a blocked flue since both furnaces were thoroughly cleaned and
share the same flue stack/chimney and the upstairs unit does not have this
same problem. I suspect it may be that the air/fuel mixture is still not
correct or possibly that the gas pressure from the gas valve to the burner
orifices on the lower level furnace may be set too high. (I am not sure how
these are set.) My service company is stumped and after being charged for
two trips, I am not anxious to have them come back till I understand what is
happening here.

Thoughts and ideas on what I can look at or try are very much appreciated.
I know these units are only about 65% efficient and getting old, but
replacement at this time is not an option since they are otherwise still
running well!

Bob




PexSupply Save 10 468x60
Posted by Noon-Air on February 14, 2008, 3:28 pm

> Sorry in advance for the length of this post, but I wanted to try to be as
> specific as possible on this problem.
>
> I have two 16+ year old Armstrong natural gas furnaces (model number in
> subject line above) for my residence. Both identical spark ignition,
> 125,000 BTU 5-burner units.
>
> I had a soot build up problem with the lower level unit (the one that is
> used most frequently) that caused the flame on the left-most burner to
> slightly roll out from the heat exchanger chamber, so I called a reputable
> local service company to come out and clean both of the units.
>
> They removed the flue and front panel and then thoroughly cleaned the
> sooted up heat exchanger and flue vent. (They found the heat exchange
> cavity by the leftmost burner completely blocked with soot). They also
> removed and cleaned all the burners too and then re-assembled everything.
> In this process, they also discovered that the air mixture controls for
> the 5 burners were shut down completely and opened them up (all the way to
> max settings) to let the burners "breathe" properly. The flame tip color
> turned a much deeper blue and the dark blue "inner" flame mantles appeared
> to go down to about 3/4" long. The good news here was that this stopped
> the orange tipped flame from rolling out of the combustion chamber and
> resulted in a noticeably hotter flame. (I've also been monitoring CO in
> the area around the furnaces and it has gone from 20+ PPM when the furnace
> was running to 0 PPM now.)
>
> Unfortunately, changing the air mixture seems to have introduced a new
> problem. Now during extended runs of this furnace (for example when
> coming up to temperature in the AM after a setback period the previous
> night), the flue roll out switch trips shutting down the system. When
> this happens it requires a manual reset of the roll out switch button. If
> the furnace is simply "cycling" to maintain temperature, then it does not
> seem to trip and everything is fine. The drafting on the furnace seems
> to be good so I suspected that it was just burning too hot for the switch.
>
> Thinking this was possibly a weak/old/failing roll out switch, I swapped
> the switch with the one in my upstairs furnace, but this did not fix the
> problem and it still tripped just the same (and the upstairs unit which
> now has the switch from the downstairs unit did not trip). At this point,
> I have tried backing off the air mixture to about 50% from being wide open
> on all 5 burners, but this too seems to have had no affect.
>
> The only thing that I've found that does seem to prevent this switch from
> tripping is to manually feather the gas shut off valve to the point where
> I can observe a noticeable reduction in the flame height on the 5 burners.
>
> I'd appreciate thoughts on what is happening here. I do not believe it is
> an issue with a blocked flue since both furnaces were thoroughly cleaned
> and share the same flue stack/chimney and the upstairs unit does not have
> this same problem. I suspect it may be that the air/fuel mixture is still
> not correct or possibly that the gas pressure from the gas valve to the
> burner orifices on the lower level furnace may be set too high. (I am not
> sure how these are set.) My service company is stumped and after being
> charged for two trips, I am not anxious to have them come back till I
> understand what is happening here.
>
> Thoughts and ideas on what I can look at or try are very much appreciated.
> I know these units are only about 65% efficient and getting old, but
> replacement at this time is not an option since they are otherwise still
> running well!
>
> Bob

Replacement time is *ALWAYS* an option. From my personal experience with my
customers, its not unusual for their utility bills to drop as much as 60% or
more with a new system. Changing to a correctly sized 80+ furnace will make
a huge difference, and even more so for a 90+ furnace.

You might have to replace it sooner than you anticipated anyway... One or 2
cells sooting up, is a bad thing.. I would suggest that the heat exchanger
be inspected for cracks... bet ya find some. Armstrong's paper thin,
clamshell, heat exchangers(especially the older ones) are not noted for
their longevity. When the cracks are found, then your not gonna have much of
a choice in the matter other than spend the money and replace it or be cold.



Posted by Bob Shuman on February 14, 2008, 6:10 pm
Noon-air (love that handle),

Thanks for your comments. The service company did use a camera and said
there were no obvious cracks and that the unit appeared to otherwise be in
good condition.

I know there would be operating savings, but can't get past the cost
estimate I received (4 figures) since I have two furnaces and 2 central A/C
units to replace and high efficiency costs a lot of money!

What I was really hoping was that someone could shed some light on why the
thing is running "too hot" now that the air mixture has been increased.
Shouldn't the temp still be regulated by the amount of natural gas that is
provided by the electric valve? Why should I need to decrease the air
mixture, and in effect make the unit run LESS efficiently by throwing
unburned fuel up the flue?

All I can figure is that the gas pressure getting to the burners are too
high since the orifices have not changed since it was installed. But the
service company seems to think these are permanently regulated and not
really adjustable in the field. I have accomplished the same end result by
throttling back the main shut off gas valve, but needing to do this means
there is another problem somewhere else. Other thoughts are appreciated.

Bob
> Replacement time is *ALWAYS* an option. From my personal experience with
> my customers, its not unusual for their utility bills to drop as much as
> 60% or more with a new system. Changing to a correctly sized 80+ furnace
> will make a huge difference, and even more so for a 90+ furnace.
>
> You might have to replace it sooner than you anticipated anyway... One or
> 2 cells sooting up, is a bad thing.. I would suggest that the heat
> exchanger be inspected for cracks... bet ya find some. Armstrong's paper
> thin, clamshell, heat exchangers(especially the older ones) are not noted
> for their longevity. When the cracks are found, then your not gonna have
> much of a choice in the matter other than spend the money and replace it
> or be cold.



Posted by Sid on February 15, 2008, 6:59 am

> All I can figure is that the gas pressure getting to the burners are too
> high since the orifices have not changed since it was installed. But the
> service company seems to think these are permanently regulated and not
> really adjustable in the field. I have accomplished the same end result by
> throttling back the main shut off gas valve, but needing to do this means
> there is another problem somewhere else. Other thoughts are appreciated.

Noonie's answer is always to change out the equipment.

Call a company that has the tools and knowledge to check what you
actually have.
Draft gauge, combustion analyzer, manometer etc.

You need to keep your fingers out of the equipment.

Posted by HVACGod on February 16, 2008, 8:30 am

>
>> Sorry in advance for the length of this post, but I wanted to try to be
>> as specific as possible on this problem.
>>
>> I have two 16+ year old Armstrong natural gas furnaces (model number in
>> subject line above) for my residence. Both identical spark ignition,
>> 125,000 BTU 5-burner units.
>>
>> I had a soot build up problem with the lower level unit (the one that is
>> used most frequently) that caused the flame on the left-most burner to
>> slightly roll out from the heat exchanger chamber, so I called a
>> reputable local service company to come out and clean both of the units.
>>
>> They removed the flue and front panel and then thoroughly cleaned the
>> sooted up heat exchanger and flue vent. (They found the heat exchange
>> cavity by the leftmost burner completely blocked with soot). They also
>> removed and cleaned all the burners too and then re-assembled everything.
>> In this process, they also discovered that the air mixture controls for
>> the 5 burners were shut down completely and opened them up (all the way
>> to max settings) to let the burners "breathe" properly. The flame tip
>> color turned a much deeper blue and the dark blue "inner" flame mantles
>> appeared to go down to about 3/4" long. The good news here was that this
>> stopped the orange tipped flame from rolling out of the combustion
>> chamber and resulted in a noticeably hotter flame. (I've also been
>> monitoring CO in the area around the furnaces and it has gone from 20+
>> PPM when the furnace was running to 0 PPM now.)
>>
>> Unfortunately, changing the air mixture seems to have introduced a new
>> problem. Now during extended runs of this furnace (for example when
>> coming up to temperature in the AM after a setback period the previous
>> night), the flue roll out switch trips shutting down the system. When
>> this happens it requires a manual reset of the roll out switch button.
>> If the furnace is simply "cycling" to maintain temperature, then it does
>> not seem to trip and everything is fine. The drafting on the furnace
>> seems to be good so I suspected that it was just burning too hot for the
>> switch.
>>
>> Thinking this was possibly a weak/old/failing roll out switch, I swapped
>> the switch with the one in my upstairs furnace, but this did not fix the
>> problem and it still tripped just the same (and the upstairs unit which
>> now has the switch from the downstairs unit did not trip). At this
>> point, I have tried backing off the air mixture to about 50% from being
>> wide open on all 5 burners, but this too seems to have had no affect.
>>
>> The only thing that I've found that does seem to prevent this switch from
>> tripping is to manually feather the gas shut off valve to the point where
>> I can observe a noticeable reduction in the flame height on the 5
>> burners.
>>
>> I'd appreciate thoughts on what is happening here. I do not believe it
>> is an issue with a blocked flue since both furnaces were thoroughly
>> cleaned and share the same flue stack/chimney and the upstairs unit does
>> not have this same problem. I suspect it may be that the air/fuel
>> mixture is still not correct or possibly that the gas pressure from the
>> gas valve to the burner orifices on the lower level furnace may be set
>> too high. (I am not sure how these are set.) My service company is
>> stumped and after being charged for two trips, I am not anxious to have
>> them come back till I understand what is happening here.
>>
>> Thoughts and ideas on what I can look at or try are very much
>> appreciated. I know these units are only about 65% efficient and getting
>> old, but replacement at this time is not an option since they are
>> otherwise still running well!
>>
>> Bob
>
> Replacement time is *ALWAYS* an option. From my personal experience with
> my customers, its not unusual for their utility bills to drop as much as
> 60% or more with a new system. Changing to a correctly sized 80+ furnace
> will make a huge difference, and even more so for a 90+ furnace.
>
> You might have to replace it sooner than you anticipated anyway... One or
> 2 cells sooting up, is a bad thing.. I would suggest that the heat
> exchanger be inspected for cracks... bet ya find some. Armstrong's paper
> thin, clamshell, heat exchangers(especially the older ones) are not noted
> for their longevity. When the cracks are found, then your not gonna have
> much of a choice in the matter other than spend the money and replace it
> or be cold.
>

Noon is absolutely correct - odds are better than not that there is a crack
in the exchanger(s). We carried Armstrong as a secondary for years until
issues with their heat exchangers outweighed their willingness to correct
them. Just like Janitrol/Goodman/Amana - if I see an Armstrong still in
service any time I'm in the field - irrespective of the season I dig into
the exchanger. If the cells have not already been replaced, a compromise is
found in 3 of 5 pieces of equipment, I would guess.

Aside for that 16 year old equipment is costing you more to operate than it
would be to replace with upgraded equipment in the big picture.



Page 1 of 3       1 2 3 > last >>
Similar ThreadsPosted
Re: Armstrong EG6A125DC15-13 Roll Out Switch November 9, 2008, 11:10 am
Heater Hustlers from Canton again: HEAT SURGE Roll-n-Glow Fireplace December 12, 2007, 11:11 am
Heater Hustlers from Canton again: HEAT SURGE Roll-n-Glow Fireplace December 12, 2007, 11:09 am
Armstrong pump August 12, 2006, 2:41 pm
Baldor/Armstrong#3 October 6, 2006, 1:03 pm
armstrong/baldor update October 3, 2006, 11:19 am
Armstrong gas furnace won't kick off November 20, 2006, 3:49 pm
Fan/ Limit switch November 1, 2006, 10:39 am
Pressure switch March 1, 2008, 9:01 pm
Loss of Charge Switch July 26, 2006, 10:28 am

Contact Us | Privacy Policy

XML SitemapXML Sitemap