|
Posted by on October 29, 2007, 5:21 pm
On Mon, 29 Oct 2007 12:39:09 -0700, anthonymmfalcone@yahoo.com wrote:
>On Oct 17, 12:16 am, anthonymmfalc...@yahoo.com wrote:
>> Dear Readers,
>> My Burnham MPO boiler was installed in August. I've an indirect water
>> heater attached as well. The domestic hot water works fine and heats
>> up on demand as expected. Now that heating season has begun, I find
>> hydronic system with very very weak heat output. The new circulator
>> is running fine. The manual says there is a 15degree differential
>> between the "high limit setting" and a call for boiler ignition. I
>> see the high limit is set at 200F. I raise the thermostat to call for
>> heat, but I watch the boiler thermometer go down to under 90deg F and
>> never come on. The only way it does come on is if I run the hot water
>> too.
>>
>> Any ideas or suggestions on what is wrong would be appreciated.
>>
>> Regards,
>> Anthony Falcone
>
>In the end, the DHW was properly wired to the relay. However, the
>hydronic heat loop was not so properly wired. Furthermore, there was
>a TON of air in the system and we had to bleed it out about 5 times
>over 3days.
That would be ~ 27,080 cubic feet, for those who care.
>Thanks very much to all for the advice.
>Regards,
>-Anthony Falcone
--
Click here every day to feed an animal that needs you today !!!
http://www.theanimalrescuesite.com/
Paul ( pjm @ pobox . com ) - remove spaces to email me
'Some days, it's just not worth chewing through the restraints.'
'With sufficient thrust, pigs fly just fine.'
HVAC/R program for Palm PDA's
Free demo now available online http://pmilligan.net/palm/
|