Posted by ATJaguarX on January 25, 2008, 4:39 pm
I have a 3200 sqft house with a 117k BTU furnace. The 3 kids bedrooms
are at the ends of the trunk line (usually with 9-10 branches before
them) and always seem to be 1-3 degrees colder then the thermostat.
This 1-3 degree difference was only achieved by closing almost ALL of
the dampers 1/2 way. My concern is that I have too many of the
dampers closed off too much and was concerned that I would be hurting
the system. My thought was to add a duct booster fan to the baby's
room (and possibly the other 2 kids rooms) so that I could open up the
other dampers more. At the very least, I want the baby's room to be
the same temperature as the main living area.

Any thoughts?

Posted by jamesgangnc on January 26, 2008, 8:57 am
I agree, it is better to improve flow by lowering resistance than it is by
increasing resistance. That said you may be able to compensate by bumping
up the fan speed. There is a temp range you need to stay inside of. You
should be able to find a sealed hole a little ways down from the system
where the installer put a temp meter to check. If you're going to fool
around with it much you should find out the range it is supposed to be in
and check it. You can cause big problems by straying outside that range.

How big is the main line? Is it solid walled? (sheet metal/duct board or a
bigger piece of flex?) What size flex is running from the main line? What
is the R of the lines?

Sometimes you can improve flow by upping to 8 inch flex on 6 inch runs that
have problems. You can put an 8 to 6 reducer at the vent but you do want to
change the takeoff to 8 inch. Lowers the resistance.

Also long runs can lose a lot of heat. Switch to r6 if you have r4 at the
same time you go to 8". Wrap the main line if it is solid walled.

A lot of people consider those booster fans to be a crutch for a badly setup
or installed system.

You an also call your service guy and see what suggestions he has.

>I have a 3200 sqft house with a 117k BTU furnace. The 3 kids bedrooms
> are at the ends of the trunk line (usually with 9-10 branches before
> them) and always seem to be 1-3 degrees colder then the thermostat.
> This 1-3 degree difference was only achieved by closing almost ALL of
> the dampers 1/2 way. My concern is that I have too many of the
> dampers closed off too much and was concerned that I would be hurting
> the system. My thought was to add a duct booster fan to the baby's
> room (and possibly the other 2 kids rooms) so that I could open up the
> other dampers more. At the very least, I want the baby's room to be
> the same temperature as the main living area.
>
> Any thoughts?



Similar ThreadsPosted
Hydro-air dampers manual vs. electronic December 4, 2007, 1:54 pm
Adjusting an L6006A Aquastat April 7, 2008, 3:30 pm
Zone Control Dampers broken again - need advice March 21, 2007, 9:31 pm
Mini duct connected to 6" ducted system October 26, 2006, 9:30 am
Winter condensation problem in HVAC duct system January 28, 2008, 10:42 am
Re: Intermittent high pressure in hot water heating system system February 3, 2007, 9:46 am
Re: Intermittent high pressure in hot water heating system system February 4, 2007, 3:49 pm
Re: Intermittent high pressure in hot water heating system system February 4, 2007, 3:54 pm
Re: Intermittent high pressure in hot water heating system system February 4, 2007, 3:43 pm
Re: Intermittent high pressure in hot water heating system system February 4, 2007, 3:06 pm

Contact Us | Privacy Policy

XML SitemapXML Sitemap