Posted by Mr. Fix It on February 17, 2007, 5:46 pm
On Feb 11, 4:00 pm, DANgER (dan...@heat.com) wrote:
> Sounds like you just need a ecm module, the piece that sits on the end of the
> motor. Make sure you get the right part from GE. I order them from any
> Carrier wholesaler. Make sure you have the model and serial number, and also
> the series and product number, before you have them cross reference parts.
>
> -Canadian Heat
>
> --
> --------------------------------- --- -- -
> Posted with NewsLeecher v3.8 Final
> Web @http://www.newsleecher.com/?usenet
> ------------------- ----- ---- -- -
It is a follow up to my own post.
I did not need complete control module to blower motor.
I fixed this module by replacing NTC Thermistor, which opened.
Temporarily you can just jump this across but remember newer test
furnace with open inspection door or filter door.
Open door will cause 50% increase of load on motor power supply.
The thermistor is surge-gard type made by RTI.
|