Carrier 58MVP blower motor control. Mr. Fix It 02-11-2007
If you were  Registered and logged in, you could reply and use other advanced thread options
Posted by Mr. Fix It on February 11, 2007, 1:23 pm
My Carrier 58MVP120F15120 HVAC mulfuntioned. Blower would not start.
I
found responsible for failure component as thermistor or varistor
(not
sure) TR01 on the PCB board inside control unit of the blower motor.
Unit is mounted in the round steel case on the face of the motor.
Part
number of this element is SG348 and looks like disc, size of a dime
with 2 legs. One of them disconnected. Part number of complete
control
unit is DG02 0200GX made by GE for 3/4 HP motor.
1. Does anyone know specs for SG348?
2. Any sugestions for replacement.
3. Availability of spare part or control unit.


Posted by danger@heat.com on February 11, 2007, 4:00 pm
Sounds like you just need a ecm module, the piece that sits on the end of the
motor. Make sure you get the right part from GE. I order them from any
Carrier wholesaler. Make sure you have the model and serial number, and also
the series and product number, before you have them cross reference parts.

-Canadian Heat


--
--------------------------------- --- -- -
Posted with NewsLeecher v3.8 Final
Web @ http://www.newsleecher.com/?usenet
------------------- ----- ---- -- -


Posted by Mr. Fix It on February 17, 2007, 5:46 pm
On Feb 11, 4:00 pm, DANgER (dan...@heat.com) wrote:
> Sounds like you just need a ecm module, the piece that sits on the end of the
> motor. Make sure you get the right part from GE. I order them from any
> Carrier wholesaler. Make sure you have the model and serial number, and also
> the series and product number, before you have them cross reference parts.
>
> -Canadian Heat
>
> --
> --------------------------------- --- -- -
> Posted with NewsLeecher v3.8 Final
> Web @http://www.newsleecher.com/?usenet
> ------------------- ----- ---- -- -

It is a follow up to my own post.
I did not need complete control module to blower motor.
I fixed this module by replacing NTC Thermistor, which opened.
Temporarily you can just jump this across but remember newer test
furnace with open inspection door or filter door.
Open door will cause 50% increase of load on motor power supply.
The thermistor is surge-gard type made by RTI.




Similar ThreadsPosted
Problem replacing blower control board October 20, 2007, 1:50 am
Re: Blower Fan Motor April 11, 2006, 10:21 pm
replacing blower motor October 20, 2007, 10:38 am
Amana 4 ton condenser blower motor July 11, 2007, 1:37 am
BLOWER MOTOR DUNHAM SPACE PAK December 13, 2007, 11:05 pm
Replacement for Carrier multi-zone control September 8, 2006, 4:42 pm
Carrier 48SS locks out with "internal control fault" when cold outside January 20, 2007, 4:53 pm
Goodman GMS 90904CX Furnace issue with squirrel cage/blower motor January 23, 2007, 11:35 am
Carrier variable speed motor, duct transitions - any problems? September 14, 2006, 4:01 pm
looking for humidistat control November 8, 2006, 10:48 am

Contact Us | Privacy Policy

XML SitemapXML Sitemap