If you were Registered and logged in, you could reply and use other advanced thread options
|
Posted by on November 6, 2007, 12:03 am
Dear Readers,
I've a Burnham MPO boiler. I called Burnham, whose technicians
suggest that I take the most conservative approach and line my
existing exterior-wall, clay-lined brick chimney with a stainless
liner to minimize flue condensation.
Should this liner necessarily be insulated as well? Or is the dead
airspace (although somewhat cold due to exterior wall) in the chimney
a sufficient buffer? I know the most conservative answer is to
insulate the liner too, but your experiences would be appreciated as
this insulation would be yet another expense on top of the liner.
Thank you very much for your responses.
-Anthony
|
|
Posted by Zyp on November 6, 2007, 12:15 pm
anthonymmfalcone@yahoo.com wrote:
> Dear Readers,
> I've a Burnham MPO boiler. I called Burnham, whose technicians
> suggest that I take the most conservative approach and line my
> existing exterior-wall, clay-lined brick chimney with a stainless
> liner to minimize flue condensation.
> Should this liner necessarily be insulated as well? Or is the dead
> airspace (although somewhat cold due to exterior wall) in the chimney
> a sufficient buffer? I know the most conservative answer is to
> insulate the liner too, but your experiences would be appreciated as
> this insulation would be yet another expense on top of the liner.
> Thank you very much for your responses.
> -Anthony
Anthony;
Check with the Burnham Tech's again, I believe they intemnd for you to use a
double wall stainless flue pipe in the chimney opening. Insulation not
needed.
--
Zyp
|
|
Posted by on November 7, 2007, 10:26 am
> Check with the Burnham Tech's again, I believe they intemnd for you to use a
> double wall stainless flue pipe in the chimney opening. Insulation not
> needed.
Just called them again. They expect stack temperatures of below
350F. Considering it's an exterior wall chimney and (I suggested I
may also have a fresh air duct installed in the future), they once
again recommend a stainless liner to prevent condensation from
damaging the existing chimney. As they're not in the liner industry,
they did not want to officially comment on the specific type, although
the individual I spoke with said he's familiar with the single wall
variety.
The double wall stainless liners I'm familiar with would seem like
overkill: they are insulated in between layers and are typically the
type that can be in close proximity to combustibles, like those
metalbestos things. And I do not want to switch to a power vent
situation.
Any 3-pass boiler (Buderus, Burnham MPO, etc) experts out there
familiar with or observe a similar stainless chimney liner
installation??
|
|
Posted by Noon-Air on November 7, 2007, 12:24 pm
>> Check with the Burnham Tech's again, I believe they intemnd for you to
>> use a
>> double wall stainless flue pipe in the chimney opening. Insulation not
>> needed.
> Just called them again. They expect stack temperatures of below
> 350F. Considering it's an exterior wall chimney and (I suggested I
> may also have a fresh air duct installed in the future), they once
> again recommend a stainless liner to prevent condensation from
> damaging the existing chimney. As they're not in the liner industry,
> they did not want to officially comment on the specific type, although
> the individual I spoke with said he's familiar with the single wall
> variety.
> The double wall stainless liners I'm familiar with would seem like
> overkill: they are insulated in between layers and are typically the
> type that can be in close proximity to combustibles, like those
> metalbestos things. And I do not want to switch to a power vent
> situation.
> Any 3-pass boiler (Buderus, Burnham MPO, etc) experts out there
> familiar with or observe a similar stainless chimney liner
> installation??
What does the installation manual say about it??
What do your local codes require??
What did the local building inspector say about it??
What did your insurance company say about it??
We are not here to do your homework for you.
|
|
Posted by on November 7, 2007, 1:25 pm
> > Any 3-pass boiler (Buderus, Burnham MPO, etc) experts out there
> > familiar with or observe a similar stainless chimney liner
> > installation??
> What does the installation manual say about it??
> What do your local codes require??
> What did the local building inspector say about it??
> What did your insurance company say about it??
> We are not here to do your homework for you.- Hide quoted text -
> - Show quoted text -
Thanks for the suggestions.
1. Installation manual says use a liner "if condensation is
observed." Per my earlier post, I called the manufacturer and didn't
get too much advice on what type as it's not their product.
2. I didn't think to check the code! Chapt 8 of Mechanical Code of NY
says to use liner that will resist condensate, and is in accordance
with NFPA31. I'll find NFPA31 and see what it says. Hopefully will
provide guidance on insulated vs. non-insulated.
3. Local building inspector cannot (legally) suggest anything beyond
the building code, so I'll need that NFPA31.
4. I didn't check insurance company. Not sure if they'll even
understand what I'm saying. I'll try.
I have two additional thoughts:
1. if flue gas is cooled too much within liner inside chimney, it may
not create sufficient draft up the 25ft tall, exterior wall chimney.
Is there a way I can estimate if I'll have sufficient draft? Reference
would be appreciated.
2. if flue gas is cooled too much and condensation occurs within the
liner, is it such a big deal? It would just drip down, through the
bottom tee, and into the cleanout chamber. In other words, the system
would work as expected, no?
In the meanwhile, any other suggestions or experience is appreciated.
|
Page 1 of 2 1 2 > last >>
| Similar Threads | Posted | | U.S. National Oil Fired Boiler | October 1, 2007, 9:04 pm |
| Utica Dry Base Oil Fired Boiler | August 19, 2006, 12:10 am |
| Sizing an insulated stainless steel rigid liner | March 25, 2007, 10:46 pm |
| Chimney Questions | December 12, 2007, 6:47 pm |
| second opinion on my chimney | December 15, 2008, 3:01 pm |
| Woodstove chimney danger - help please | July 17, 2006, 2:48 am |
| Chimney line and flue | August 9, 2006, 4:30 pm |
| S/S Replacement Chimney Cost? | August 20, 2006, 1:48 pm |
| Trane XV80 Chimney Question | March 15, 2008, 11:32 am |
| Story time... Roofer says... "I can cap your chimney" | July 9, 2008, 11:55 pm |
|
|
> I've a Burnham MPO boiler. I called Burnham, whose technicians
> suggest that I take the most conservative approach and line my
> existing exterior-wall, clay-lined brick chimney with a stainless
> liner to minimize flue condensation.
> Should this liner necessarily be insulated as well? Or is the dead
> airspace (although somewhat cold due to exterior wall) in the chimney
> a sufficient buffer? I know the most conservative answer is to
> insulate the liner too, but your experiences would be appreciated as
> this insulation would be yet another expense on top of the liner.
> Thank you very much for your responses.
> -Anthony