Posted by MindOvrX on July 7, 2006, 3:54 am
I am trying to help someone find a good contractor to put in a hood system
for a small cafe, and have a couple of questions to clear up first.

The furnace was just replaced, and someone has mentioned that the furnace
needs exhaust air to be relieved. The contractor said that this will be
taken care of by the hood system, but will need to be ganged with the
furnace to work properly.

Is this true? How does that work?

The contractor said to make sure the hood installer wires up the system to
work with the furnace, the make up air for the hood and the exhaust system.
What exactly are we looking at?

Thanks



Posted by Stormin Mormon on July 7, 2006, 10:31 am
When you put an exhaust hood in, it pumps air out of the building.
That air has to come from some where. Often from cracks around the
door, or windows.

If there isn't enough "make up air", or air coming in, the building
air pressure is lower than the outdoors. Then, air can come down the
furnace or water heater chimney. Drawing the fumes and monoxide into
the building instead of up the chimney.

The question which troubles me. Is there enough provision to bring
fresh air in from the outside?

--

Christopher A. Young
You can't shout down a troll.
You have to starve them.
.

I am trying to help someone find a good contractor to put in a hood
system
for a small cafe, and have a couple of questions to clear up first.

The furnace was just replaced, and someone has mentioned that the
furnace
needs exhaust air to be relieved. The contractor said that this will
be
taken care of by the hood system, but will need to be ganged with the
furnace to work properly.

Is this true? How does that work?

The contractor said to make sure the hood installer wires up the
system to
work with the furnace, the make up air for the hood and the exhaust
system.
What exactly are we looking at?

Thanks




Posted by MindOvrX on July 7, 2006, 12:13 pm
Ok, here's what I found. The furnace is supposed to be getting around 1500
cfm fresh air with up to 1800 cfm when the a/c is in free cooling mode (?).

They also said the hood exhausts something like 4000 cfm but will have a
fresh air fan that provides some outside air too.

The contractor is saying that it's better to just make sure that the outside
air for the hood is the difference between 1500 cfm and 4000 cfm, and don't
worry about wiring the systems together. This doesn't make sense to me,
because I think that the systems will run at different times most of the
time. I think they have to put in shut-off dampers when the systems aren't
running, don't they?

Thanks for helping with this.


> When you put an exhaust hood in, it pumps air out of the building.
> That air has to come from some where. Often from cracks around the
> door, or windows.
> If there isn't enough "make up air", or air coming in, the building
> air pressure is lower than the outdoors. Then, air can come down the
> furnace or water heater chimney. Drawing the fumes and monoxide into
> the building instead of up the chimney.
> The question which troubles me. Is there enough provision to bring
> fresh air in from the outside?
> --
> Christopher A. Young
> You can't shout down a troll.
> You have to starve them.
> .
> I am trying to help someone find a good contractor to put in a hood
> system
> for a small cafe, and have a couple of questions to clear up first.
> The furnace was just replaced, and someone has mentioned that the
> furnace
> needs exhaust air to be relieved. The contractor said that this will
> be
> taken care of by the hood system, but will need to be ganged with the
> furnace to work properly.
> Is this true? How does that work?
> The contractor said to make sure the hood installer wires up the
> system to
> work with the furnace, the make up air for the hood and the exhaust
> system.
> What exactly are we looking at?
> Thanks



Posted by aka-SBM on July 7, 2006, 8:10 pm

> Ok, here's what I found. The furnace is supposed to be getting around 1500
> cfm fresh air with up to 1800 cfm when the a/c is in free cooling mode
> (?).

Ummm....you mean MOVING?

> They also said the hood exhausts something like 4000 cfm but will have a
> fresh air fan that provides some outside air too.

Some? Better provide 4000CFM when its on.

> The contractor is saying that it's better to just make sure that the
> outside
> air for the hood is the difference between 1500 cfm and 4000 cfm, and
> don't
> worry about wiring the systems together.

Bullshit.

>This doesn't make sense to me,
> because I think that the systems will run at different times most of the
> time. I think they have to put in shut-off dampers when the systems aren't
> running, don't they?

If you dont know, then no. Sure dont.

> Thanks for helping with this.

The closest Chris has gotten to a make up air unit, is when he goes to
Wendys for a burger.

>> When you put an exhaust hood in, it pumps air out of the building.
>> That air has to come from some where. Often from cracks around the
>> door, or windows.
>> If there isn't enough "make up air", or air coming in, the building
>> air pressure is lower than the outdoors. Then, air can come down the
>> furnace or water heater chimney. Drawing the fumes and monoxide into
>> the building instead of up the chimney.
>> The question which troubles me. Is there enough provision to bring
>> fresh air in from the outside?
>> --
>> Christopher A. Young
>> You can't shout down a troll.
>> You have to starve them.
>> .
>> I am trying to help someone find a good contractor to put in a hood
>> system
>> for a small cafe, and have a couple of questions to clear up first.
>> The furnace was just replaced, and someone has mentioned that the
>> furnace
>> needs exhaust air to be relieved. The contractor said that this will
>> be
>> taken care of by the hood system, but will need to be ganged with the
>> furnace to work properly.
>> Is this true? How does that work?
>> The contractor said to make sure the hood installer wires up the
>> system to
>> work with the furnace, the make up air for the hood and the exhaust
>> system.
>> What exactly are we looking at?
>> Thanks
>



Posted by on July 8, 2006, 10:37 am

>Ok, here's what I found. The furnace is supposed to be getting around 1500
>cfm fresh air with up to 1800 cfm when the a/c is in free cooling mode (?).
>They also said the hood exhausts something like 4000 cfm but will have a
>fresh air fan that provides some outside air too.
>The contractor is saying that it's better to just make sure that the outside
>air for the hood is the difference between 1500 cfm and 4000 cfm, and don't
>worry about wiring the systems together. This doesn't make sense to me,
>because I think that the systems will run at different times most of the
>time. I think they have to put in shut-off dampers when the systems aren't
>running, don't they?
>Thanks for helping with this.

More important than what the contractor has to say, and more important
than any internet advice is the actual building code requirements for
your local juristiction.

In this neck of the woods, if you are exhausting 4000 cfm, you will
also be providing 4000 cfm of fresh air, and the make up air fan will
be interlocked with the exhaust fan.

You should educate yourself on the differences between fresh air,
return air, and combustion air requirements for any fossil fuel
burning appliance, and the specific rerquirements for each as per the
building codes for your area.

If you're in an area with no building codes, smart money would hire a
mechanical engineer to engineer the specifics of your situation.

Page 1 of 2       1 2 > last >>
Similar ThreadsPosted
furnace vent tube in wall and stove hood vent March 13, 2007, 11:12 pm
Securing range hood ductwork to the wall? April 3, 2007, 8:27 am
Quietest inline fan for range hood exhaust September 14, 2007, 7:58 pm
Does range hood need damper if roof vent already has one? October 6, 2007, 4:57 am
need help with a commercial ice machine January 2, 2008, 12:11 pm
reduce range hood vent size or elbow it all over the place? August 18, 2006, 3:49 pm
question for the commercial guys January 9, 2007, 12:37 am
What are commercial hvac systems like? April 1, 2007, 4:03 am
commercial carbon monoxide detectors... September 12, 2006, 8:21 pm
Is a rooftop commercial HVAC R22 still usable? May 23, 2007, 1:50 pm

Contact Us | Privacy Policy

XML SitemapXML Sitemap