Posted by Silver Surfer on August 3, 2008, 6:41 pm
Thank you for the information Mr. Zyp. You provided the insight I was
looking for. Much obliged.
> Silver Surfer wrote:
>> The evaporator coil for my daughter's central air conditioning is
>> leaking condensate on the basement floor. The drain line is
>> unobstructed and also flowing some water.
>>
>> This is a Carrier unit and it was installed with the access panel
>> less than a foot from the basement wall, presumably because the
>> refrigerant connections are right below the panel and it's a direct
>> shot from there to the outdoor unit. Whatever, it was a real
>> pleasure taking the panel off and getting it back on.
>>
>> Did not see anything obvious with the panel off, but there wasn't
>> much that could be seen from back there. It looks like the
>> condensate tray is on the opposite side of the unit where there is no
>> panel.
>> Noticed a small cover on one corner. Behind the cover was a drain
>> pipe with a rubber plug in it, from the factory it appears. What is
>> the purpose of this other drain connection? Would it help to also
>> run a drain from it?
>> I'm guessing that the condensate tray may have a leak in it, but I
>> don't see any easy way of accessing it short of cutting a hole in the
>> housing. I don't know what these trays are made of or if they are
>> are prone to rusting out.
>>
>> What can you suggest?
>
> If the coil is older than 15 years, it likely has pin holes in the bottom.
> There's really no remedy other than replacing the complete coil. Since
> it's in the basement, it will likely not allow the newer coils [larger] to
> fit without a newer furnace.
>
> Good luck.
>
>
> --
> Zyp
>
|