|
Posted by Dido on August 27, 2006, 10:28 am
System is not balance properly or zone valves do not work
or perhaps you have air the system and you not getting full
circulation "which is most likely"
DIDO
> Working on a previously healthy 4 port manifold radiant system. The
> thermostatic part of the system seems to be working... the pump
> (Grundfos UP 15-42F) & boiler (shows 140) come on & the motoroized
> actuators
> respond correctly.
>
> The mystery is that only 2 zones (closest to the boiler input end of
> the manifold) get flow (both input & return tubes heat up)... even when
> manual depressing the
> actuator valve, there is no discernable heat in either of the other 2
> tubes. The
> manifold & actuators were new 6 months ago and it is reported that
> everything worked fine, until recently.
>
> What could have happened that would cause these 2 zones to not flow????
>
> Any thoughts greatly appreciated.
>
>
> jr
>
|