Evap coils freezing up- Any advice?

HVAC Discussions - Heating, ventilation and air conditioning. 

Page 1 of 7       1 2 3 > last >> Bookmark this page:  YahooMyWeb Yahoo!  Google Google  Windows Live Favorites Windows Live  del.icio.us del.icio.us  digg digg  Add to Netscape Netscape
Subject Author Date
Evap coils freezing up- Any advice? trocketspam 07-28-2007
If you were  Registered and logged in, you could reply and use other advanced thread options
Posted by on July 28, 2007, 1:00 pm
We've been having problem with our A/C for some time now, the blower/
fan/ heating unit is old, but the outside A/C unit is only 1-year old.
I think the inside/ evap coils were also placed new at the time.

We've had problems with charge, which the tech has been out twice to
balance, but it could still be mis-balanced charge I guess. In any
case, we can't run the A/C for more than 2 hours and the coils freeze
up solid, completely iced over. I've taken the cover off to make sure
that is the problem, and it surely is. Of course this means we get no
air flow and have to turn the system off for many hours to let it thaw
out, just to re-freeze when we turn it back on.

I've been reading in this and other groups about possible causes, and
read that it could be the charge is wrong, could be dirty/ clogged
coils, could be bad airflow. To be sure, I've cleaned the outside A/C
unit and coils, but as the unit is still pretty new, there wasn't much
to clean, they are good. I got inside the evap coils and there is no
visible dirt/ clogging, but still sprayed it out with compressed air,
again, no visible sign of it being dirty.

As the fan is old, I suppose it could be going, and it just isn't
providing enough air flow, but it is running, and at least doesn't
sound like it's having any problems.

Even when the coils are thawed out, and the air is running, it still
doesn't feel to me like it should, like I remember it. Furthermore, it
doesn't cool the house down, at best it can keep the temperature the
same, say around 78-80 while running, but in the 2 hours until it
freezes up, I think the air flow is less than it was in the past and
it certainly doesn't cool the house. The air is cold, but the flow is
weak.

This made me suspect the evap coils were clogged and preventing
airflow, but would I see any visible signs if that was the case? Can
the fan be going out or somehow working at a lesser capacity when it
also isn't giving any signs, at least not audibly? I suppose there
could be problems in the vents as well, but I've no idea how to check
that.

Any suggestions or advice is most welcome. I'm willing to replace the
fan unit, or get other work done, I just don't know what needs to
happen. As the A/C unit is still under warranty, I can get the tech
out to balance the charge, but he's already done that twice, and quite
honestly, that company has turned out to be a huge pain to work with,
very unresponsive, very reluctant to do anything and I just want to
get the A/C working for my wife and kid who are home all day.

I hope I described the situation correctly, and used the right terms,
I have very limited knowledge obviously. Thanks much,

Rock


Posted by on July 28, 2007, 1:15 pm
On Sat, 28 Jul 2007 17:00:11 -0000, trocketspam@gmail.com wrote:

        What you have is a hack system installed by a hack, and
'warranteed' by a hack.

        What you NEED is a COMPETENT tech to come out and see what the
HACK fucked up ( which is a long list of options ), and fix it.

        You can't do it yourself, and it can't be done over the
Internet.


>We've been having problem with our A/C for some time now, the blower/
>fan/ heating unit is old, but the outside A/C unit is only 1-year old.
>I think the inside/ evap coils were also placed new at the time.
>
>We've had problems with charge, which the tech has been out twice to
>balance, but it could still be mis-balanced charge I guess. In any
>case, we can't run the A/C for more than 2 hours and the coils freeze
>up solid, completely iced over. I've taken the cover off to make sure
>that is the problem, and it surely is. Of course this means we get no
>air flow and have to turn the system off for many hours to let it thaw
>out, just to re-freeze when we turn it back on.
>
>I've been reading in this and other groups about possible causes, and
>read that it could be the charge is wrong, could be dirty/ clogged
>coils, could be bad airflow. To be sure, I've cleaned the outside A/C
>unit and coils, but as the unit is still pretty new, there wasn't much
>to clean, they are good. I got inside the evap coils and there is no
>visible dirt/ clogging, but still sprayed it out with compressed air,
>again, no visible sign of it being dirty.
>
>As the fan is old, I suppose it could be going, and it just isn't
>providing enough air flow, but it is running, and at least doesn't
>sound like it's having any problems.
>
>Even when the coils are thawed out, and the air is running, it still
>doesn't feel to me like it should, like I remember it. Furthermore, it
>doesn't cool the house down, at best it can keep the temperature the
>same, say around 78-80 while running, but in the 2 hours until it
>freezes up, I think the air flow is less than it was in the past and
>it certainly doesn't cool the house. The air is cold, but the flow is
>weak.
>
>This made me suspect the evap coils were clogged and preventing
>airflow, but would I see any visible signs if that was the case? Can
>the fan be going out or somehow working at a lesser capacity when it
>also isn't giving any signs, at least not audibly? I suppose there
>could be problems in the vents as well, but I've no idea how to check
>that.
>
>Any suggestions or advice is most welcome. I'm willing to replace the
>fan unit, or get other work done, I just don't know what needs to
>happen. As the A/C unit is still under warranty, I can get the tech
>out to balance the charge, but he's already done that twice, and quite
>honestly, that company has turned out to be a huge pain to work with,
>very unresponsive, very reluctant to do anything and I just want to
>get the A/C working for my wife and kid who are home all day.
>
>I hope I described the situation correctly, and used the right terms,
>I have very limited knowledge obviously. Thanks much,
>
>Rock

--
Click here every day to feed an animal that needs you today !!!
http://www.theanimalrescuesite.com/

Paul ( pjm @ pobox . com ) - remove spaces to email me
'Some days, it's just not worth chewing through the restraints.'
'With sufficient thrust, pigs fly just fine.'
HVAC/R program for Palm PDA's
Free demo now available online http://pmilligan.net/palm/

Posted by Geoman on July 30, 2007, 2:26 pm

> On Sat, 28 Jul 2007 17:00:11 -0000, trocketspam@gmail.com wrote:
>
> What you have is a hack system installed by a hack, and
> 'warranteed' by a hack.
>
> What you NEED is a COMPETENT tech to come out and see what the
> HACK fucked up ( which is a long list of options ), and fix it.
>
> You can't do it yourself, and it can't be done over the
> Internet.


I agree on all points.



Posted by on July 28, 2007, 2:41 pm

> We've been having problem with our A/C for some time now, the blower/
> fan/ heating unit is old, but the outside A/C unit is only 1-year old.
> I think the inside/ evap coils were also placed new at the time.
>
> We've had problems with charge, which the tech has been out twice to
> balance, but it could still be mis-balanced charge I guess. In any
> case, we can't run the A/C for more than 2 hours and the coils freeze
> up solid, completely iced over. I've taken the cover off to make sure
> that is the problem, and it surely is. Of course this means we get no
> air flow and have to turn the system off for many hours to let it thaw
> out, just to re-freeze when we turn it back on.
>
> I've been reading in this and other groups about possible causes, and
> read that it could be the charge is wrong, could be dirty/ clogged
> coils, could be bad airflow. To be sure, I've cleaned the outside A/C
> unit and coils, but as the unit is still pretty new, there wasn't much
> to clean, they are good. I got inside the evap coils and there is no
> visible dirt/ clogging, but still sprayed it out with compressed air,
> again, no visible sign of it being dirty.
>
> As the fan is old, I suppose it could be going, and it just isn't
> providing enough air flow, but it is running, and at least doesn't
> sound like it's having any problems.
>
> Even when the coils are thawed out, and the air is running, it still
> doesn't feel to me like it should, like I remember it. Furthermore, it
> doesn't cool the house down, at best it can keep the temperature the
> same, say around 78-80 while running, but in the 2 hours until it
> freezes up, I think the air flow is less than it was in the past and
> it certainly doesn't cool the house. The air is cold, but the flow is
> weak.
>
> This made me suspect the evap coils were clogged and preventing
> airflow, but would I see any visible signs if that was the case? Can
> the fan be going out or somehow working at a lesser capacity when it
> also isn't giving any signs, at least not audibly? I suppose there
> could be problems in the vents as well, but I've no idea how to check
> that.
>
> Any suggestions or advice is most welcome. I'm willing to replace the
> fan unit, or get other work done, I just don't know what needs to
> happen. As the A/C unit is still under warranty, I can get the tech
> out to balance the charge, but he's already done that twice, and quite
> honestly, that company has turned out to be a huge pain to work with,
> very unresponsive, very reluctant to do anything and I just want to
> get the A/C working for my wife and kid who are home all day.
>
> I hope I described the situation correctly, and used the right terms,
> I have very limited knowledge obviously. Thanks much,
>
> Rock


Ever think about calling a competent HVAC company?



Posted by on July 28, 2007, 2:54 pm

>
> Ever think about calling a competent HVAC company?


Certainly I want to get a competent HVAC company, it seems from some
of the responses though that some of you have also dealt with yuppies
posing as qualified techs, or companies who are lousy to work with. In
truth, to go back before these problems, we went through 3 companies
in trying to get our previous A/C unit fixed before having this one
installed new, so as a whole, I have shaken faith in these and most
companies, all who were all licensed and established.

I'm trying primarily to understand what the problem could be so I have
don't get snowed again by having someone come out and replace
everything, when it could be fixed by cleaning the coils only, or
replacing the blower, ... that kind of thing. Of course I fully
understand and don't expect a completely accurate analysis from some
internet based conversations, just seeing if anyone has experienced
this and have any reasonable guesses.

As for the coils, should I be able to visibly see debris, or does it
junk up inside the fins out of sight? Are there any signs of the
blower going out that I could check for?

Rock


Page 1 of 7       1 2 3 > last >>
Similar ThreadsPosted
Evap Coils not all sweating May 29, 2007, 9:00 pm
Evap Specifications??? May 10, 2007, 9:31 pm
Questions about Fujitsu mini split evap September 13, 2006, 11:43 am
A/C condensor freezing up June 4, 2007, 8:46 am
ac freezing with thermostat off June 19, 2008, 1:57 pm
UV lights in AC coils? March 1, 2008, 9:12 pm
Freezing liquid lines February 13, 2007, 1:56 pm
Revised diagnosis, a/c freezing up June 4, 2007, 9:45 am
Central A/C unit freezing up... September 16, 2007, 12:07 am
Any experince with Aspen coils? July 2, 2007, 7:26 pm

Contact Us | Privacy Policy

XML SitemapXML Sitemap