Feeling Robbed out of $5,000 - New 13 Seer inferior to 18 year old 10 Seer

HVAC Discussions - Heating, ventilation and air conditioning. 

Page 4 of 12       < 1 2 3 > last >> Bookmark this page:  YahooMyWeb Yahoo!  Google Google  Windows Live Favorites Windows Live  del.icio.us del.icio.us  digg digg  Add to Netscape Netscape
Subject Author Date
Feeling Robbed out of $5,000 - New 13 Seer inferior to 18 year old 10 Seer ebay 08-23-2006
If you were  Registered and logged in, you could reply and use other advanced thread options
Posted by zero on August 23, 2006, 3:12 pm
On 23 Aug 2006 08:01:31 -0700, ebay@spxchrome.com wrote:

>Well here was the 2nd opinion diagnosis. He says the the line should
>have been changed out. The current line is 1/4 and he says the 13 Seer
>needs to be on a 3/8 line. He also believes that maybe the dryer maybe
>stopped up or were the dryer was welded onto the old line it may have a
>kink from the weld. It really isn't leaking freon he added a little to
>keep it from freezing up. The gauges read 68 and 360 and he said they
>are suppose to read around 68 and 250 - whatever in the hell that
>means.


Before the original installer charged your system, did you see him
connect a vacuum pump to the system?
It would have sounded like a small air compressor running for quite
a few hours?


-zero

AppliancePartsPros.com, Inc.
Posted by tech on August 23, 2006, 3:21 pm

> On 23 Aug 2006 08:01:31 -0700, ebay@spxchrome.com wrote:
>
> >Well here was the 2nd opinion diagnosis. He says the the line should
> >have been changed out. The current line is 1/4 and he says the 13 Seer
> >needs to be on a 3/8 line. He also believes that maybe the dryer maybe
> >stopped up or were the dryer was welded onto the old line it may have a
> >kink from the weld. It really isn't leaking freon he added a little to
> >keep it from freezing up. The gauges read 68 and 360 and he said they
> >are suppose to read around 68 and 250 - whatever in the hell that
> >means.
>
>
> Before the original installer charged your system, did you see him
> connect a vacuum pump to the system?
> It would have sounded like a small air compressor running for quite
> a few hours?
>
>
> -zero

Can we say "what's a micron?" :-)



Posted by zero on August 23, 2006, 4:03 pm

>
>> On 23 Aug 2006 08:01:31 -0700, ebay@spxchrome.com wrote:
>>
>> >Well here was the 2nd opinion diagnosis. He says the the line should
>> >have been changed out. The current line is 1/4 and he says the 13 Seer
>> >needs to be on a 3/8 line. He also believes that maybe the dryer maybe
>> >stopped up or were the dryer was welded onto the old line it may have a
>> >kink from the weld. It really isn't leaking freon he added a little to
>> >keep it from freezing up. The gauges read 68 and 360 and he said they
>> >are suppose to read around 68 and 250 - whatever in the hell that
>> >means.
>>
>>
>> Before the original installer charged your system, did you see him
>> connect a vacuum pump to the system?
>> It would have sounded like a small air compressor running for quite
>> a few hours?
>>
>>
>> -zero
>
>Can we say "what's a micron?" :-)

Yep, no doubt.

And a "kink on the weld" of the LL dryer...Unfortunately it
wouldn't be the first time a 5/16" or 3/8" filter was pinched down
over a ¼" line.

This is what happens when they pass out the keys to the vans, to
bullshiters who are just knowledgeable enough to get the job ticket
signed.


-zero

Posted by on August 23, 2006, 6:06 pm
> And a "kink on the weld" of the LL dryer...Unfortunately it
> wouldn't be the first time a 5/16" or 3/8" filter was pinched down
> over a =BC" line.
>
> This is what happens when they pass out the keys to the vans, to
> bullshiters who are just knowledgeable enough to get the job ticket
> signed.
>

He thought this as well, that or a clogged dryer, either way how else
would you attach the dryer or you just saying he was a shitty welder?


Posted by tech on August 23, 2006, 6:33 pm

> > And a "kink on the weld" of the LL dryer...Unfortunately it
> > wouldn't be the first time a 5/16" or 3/8" filter was pinched down
> > over a ¼" line.
> >
> > This is what happens when they pass out the keys to the vans, to
> > bullshiters who are just knowledgeable enough to get the job ticket
> > signed.
> >

> He thought this as well, that or a clogged dryer, either way how else
> would you attach the dryer or you just saying he was a shitty welder?

Bad work ethics, poor training, lack of concern, etc...



Page 4 of 12       < 1 2 3 > last >>
Similar ThreadsPosted
Match 13 Seer Compressor with 10 Seer Coil? April 29, 2007, 1:07 pm
Seer rating help August 19, 2006, 5:43 pm
COP/SEER question June 23, 2007, 10:30 am
13 SEER Splits not cooling!??! August 8, 2006, 9:40 pm
power consumption, SEER, etc. April 10, 2007, 2:12 pm
Arcoair 13 Seer R410A 3 Ton July 28, 2008, 12:01 pm
New high SEER compressor compatibility November 2, 2006, 9:25 am
Goodman 14 seer CLQ series condensers June 21, 2007, 11:23 pm
Mobile home units / 13 seer April 14, 2006, 8:50 am
Feeling like Noon :-) August 11, 2006, 5:06 pm

Contact Us | Privacy Policy

XML SitemapXML Sitemap