Home Page link

Furnace cutss off before temperature is reached

HVAC Discussions - Heating, ventilation and air conditioning. 

Page 1 of 2       1 2 > last >> Bookmark this page:  YahooMyWeb Yahoo!  Google Google  Windows Live Favorites Windows Live  del.icio.us del.icio.us  digg digg  Add to Netscape Netscape
Subject Author Date
Furnace cutss off before temperature is reached Ken 11-19-2007
If you were  Registered and logged in, you could reply and use other advanced thread options
Posted by Ken on November 19, 2007, 4:37 pm
Hi,

Our furnace blower stops before the set temperature is reached. Got a brand
new thermostat

and the same things happens. It will not restart until the Heat/Cool/Off
control on the thermostat

is placed in "Off" and then placed on "Heat", even if the temperture drops
well below

the set temperature. What need to be changed?

thanks Ken



--
Posted via a free Usenet account from http://www.teranews.com


Posted by Noon-Air on November 19, 2007, 4:43 pm

> Hi,
>
> Our furnace blower stops before the set temperature is reached. Got a
> brand new thermostat
>
> and the same things happens. It will not restart until the Heat/Cool/Off
> control on the thermostat
>
> is placed in "Off" and then placed on "Heat", even if the temperture
> drops well below
>
> the set temperature. What need to be changed?

Your service tech



Posted by Bubba on November 19, 2007, 4:51 pm
wrote:

>Hi,
>
>Our furnace blower stops before the set temperature is reached. Got a brand
>new thermostat
>
>and the same things happens. It will not restart until the Heat/Cool/Off
>control on the thermostat
>
>is placed in "Off" and then placed on "Heat", even if the temperture drops
>well below
>
>the set temperature. What need to be changed?
>
>thanks Ken

Ken,
Its almost always the thermostat. They are made so cheaply now that it
usually takes 4 or 5 replacements until you get one that works
correctly. Replace it again.
Bubba

Posted by on November 19, 2007, 6:30 pm
wrote:

>Hi,
>
>Our furnace blower stops before the set temperature is reached. Got a brand
>new thermostat
>
>and the same things happens. It will not restart until the Heat/Cool/Off
>control on the thermostat
>
>is placed in "Off" and then placed on "Heat", even if the temperture drops
>well below
>
>the set temperature. What need to be changed?

        The thermostat.


>
>thanks Ken

--
Click here every day to feed an animal that needs you today !!!
http://www.theanimalrescuesite.com/

Paul ( pjm @ pobox . com ) - remove spaces to email me
'Some days, it's just not worth chewing through the restraints.'
'With sufficient thrust, pigs fly just fine.'
HVAC/R program for Palm PDA's
Free demo now available online http://pmilligan.net/palm/

Posted by HVAC Guy on November 19, 2007, 8:47 pm
Ken wrote:

> Our furnace blower stops before the set temperature is reached.
> Got a brand new thermostat and the same things happens. It will
> not restart until the Heat/Cool/Off control on the thermostat
> is placed in "Off" and then placed on "Heat", even if the
> temperture drops well below the set temperature. What need
> to be changed?

How old is your furnace?

Look on this page:

http://toad.net/~jsmeenen/anticipator.html

There are 2 pictures. The second one is a picture of a thermostat
(the furnace fan-control thermostat) that's mounted to the heat
exchanger inside a furnace (in this picture the cover was removed from
the thermostat). Do you this on your furnace?

The round plate with a slot in it rotates based on the temperature
inside the heat exchanger. It's what turns your furnace fan on and
off, and also has the hi-limit switch.

Your problem could be that your fan is cooling down your heat
exchanger to the point that your fan is turned off even if your
burners are still going. This could be caused by an incorrect Fan-Off
setting, or maybe you need a new furnace fan-control thermostat.

Alternatively, you could be hitting the hi-limit, which means that the
temperature inside the heat exchanger has reached the hi-limit setting
of the fan-control thermostat. When this happens, the burners are
shut off, but the fan will (or should) keep running until it reaches
the Fan-Off setting.

What you should do next is go and watch your furnace (take the front
cover panel off) and see if your fan turns off while the burners are
still on, or if the burners turn off (but the fan is still running).

Page 1 of 2       1 2 > last >>
Similar ThreadsPosted
Furnace fires back up after set temperature reached March 7, 2007, 11:33 pm
High Efficiency gas furnace - return air temperature January 19, 2007, 12:12 am
Discharge temperature August 11, 2006, 11:39 pm
temperature swing value April 15, 2007, 8:26 pm
Temperature of exhaust vents July 30, 2006, 7:02 pm
Re: Temperature of exhaust vents August 2, 2006, 12:53 am
AC Register Discharge Temperature June 28, 2007, 12:09 pm
Temperature alarm in thermostat ... February 13, 2007, 9:40 pm
Re: Lesson on temperature rise April 15, 2006, 12:16 pm
New American Standard not holding temperature August 13, 2007, 4:27 pm

Contact Us | Privacy Policy

XML SitemapXML Sitemap