> > > > I have a gas furnace, comfortmaker RPJ2 and suspect that it needs a
> > > > new controller general 90 50A50-110 replacement number is 50A55-843
> > > > symptom:
> > > > The igniter works and burns bright, but intermittently the burners
> > > > will not ignite and the the blower will just keep blowing as the ho=
use
> > > > gets colder.
> > > > Recycling the power to the unit seems to fix this for a while.
> > > > Is there a good test I should do?
> > > Lets keep this real simple.... How do you know its the board??
> > ----------
> > Sorry I haven't gotten back to all the responses yet.
> > The heat has been working It seems to have only flaked out for a few
> > times there.
> > So I suspect that it will be OK until it gets really cold. :)
> > I don't really know that it is the board,
> > Since the ignitor works (at least visually), and the fan works, and I
> > have checked all the connections, it seems to only leave 2
> > likelyhoods, the gas valve and the controller. (Let me know if you
> > suspect any others that fit the symptoms).
> > From previous posts, it seems to be more likely the controller.
> > I don't have an inline amp meter to "amp test" the ignitor, but I
> > replaced it 2 years ago and it sure is bright, I don't see how that
> > could not ignite gas if it was present.
> > I suppose I will have to wait for the problem to reoccure to test it
> > again, so let me know if there are any tests I can prepare myself
> > for.
> > Also if there is a 75% chance that it is the controller I would be
> > willing to accept that risk and just order it, (because that will take
> > days and I would rather do it now than when the problem crops up
> > again).
> > Thanks,Crzzy1
> > --------
> > =3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D=3D
> > No amp meter...
> > Then you lack the *other* test equipment to properly diagnose your
> > equipment.
> > No problem, that's why there are HVAC companies in your area. They're
> > trained to test and locate problems with heating and cooling equipment.
> > Then
> > after you approve the repair, they repair your equipment so you have a
> > comfortable home to live in... simple as that.
> > If you want to purchase parts... no problem, how many of each component
> > would you like?
> > Might as well change everything and have a spare for the next time. I'm
> > sure
> > this is cheaper.... lol
> haha...
> I kind of knew this would be the reply.
> Replacing several parts is still cheaper than calling a tech. $200 vs
> $700
> I suspect that given the symptoms, there are a few good educated
> guesses out there. and a couple of quick tests.
> Because I am lacking one tool doesn't mean I don't have every other
> tool to do the job. (I was a mechanic for a long time).
> I won't tell a person he can't replace a muffler because he doesn't
> possess an acetylene torch, Nor will I say he lacks the skill
> necessary.
> If I caved every time someone said to call a pro, I would have never
> learned to install water heaters, or fix plumbing/drywall or repair
> cars for that matter.
> Thanks,crzzy1
> ----------------------------------------------------
> You do what you gotta do. We can't *SEE* it through the computer, and I f=
or
> one don't want to be responsible for that kind of liability.
Warning - run-on one sentence answer. :-)
Oh yeah all that liability, like I would jump through your monitor and
sue you over the Internet because I risked a paltry $120 on a part
instead of spending many times that on a pro that will make a guess
(based on what he has in the trunk), and then when he's wrong I will
have to wait for him to come back and pay him to take another guess.
(Don't say it doesn't happen all the time).
Not to diss the pros out there, there are a few amateurs that call
themselves pros though.
|
|
Posted by Steve on December 31, 2008, 7:58 pm
> > > > -----
> > > > I have a gas furnace, comfortmaker RPJ2 and suspect that it needs a
> > > > new controller general 90 50A50-110 replacement number is 50A55-843
> > > > symptom:
> > > > The igniter works and burns bright, but intermittently the burners
> > > > will not ignite and the the blower will just keep blowing as the
> > > > house
> > > > gets colder.
> > > > Recycling the power to the unit seems to fix this for a while.
> > > > Is there a good test I should do?
> > > Lets keep this real simple.... How do you know its the board??
> > ----------
> > Sorry I haven't gotten back to all the responses yet.
> > The heat has been working It seems to have only flaked out for a few
> > times there.
> > So I suspect that it will be OK until it gets really cold. :)
> > I don't really know that it is the board,
> > Since the ignitor works (at least visually), and the fan works, and I
> > have checked all the connections, it seems to only leave 2
> > likelyhoods, the gas valve and the controller. (Let me know if you
> > suspect any others that fit the symptoms).
> > From previous posts, it seems to be more likely the controller.
> > I don't have an inline amp meter to "amp test" the ignitor, but I
> > replaced it 2 years ago and it sure is bright, I don't see how that
> > could not ignite gas if it was present.
> > I suppose I will have to wait for the problem to reoccure to test it
> > again, so let me know if there are any tests I can prepare myself
> > for.
> > Also if there is a 75% chance that it is the controller I would be
> > willing to accept that risk and just order it, (because that will take
> > days and I would rather do it now than when the problem crops up
> > again).
> > Thanks,Crzzy1
> > --------
> > ====================
> > No amp meter...
> > Then you lack the *other* test equipment to properly diagnose your
> > equipment.
> > No problem, that's why there are HVAC companies in your area. They're
> > trained to test and locate problems with heating and cooling equipment.
> > Then
> > after you approve the repair, they repair your equipment so you have a
> > comfortable home to live in... simple as that.
> > If you want to purchase parts... no problem, how many of each component
> > would you like?
> > Might as well change everything and have a spare for the next time. I'm
> > sure
> > this is cheaper.... lol
> haha...
> I kind of knew this would be the reply.
> Replacing several parts is still cheaper than calling a tech. $200 vs
> $700
> I suspect that given the symptoms, there are a few good educated
> guesses out there. and a couple of quick tests.
> Because I am lacking one tool doesn't mean I don't have every other
> tool to do the job. (I was a mechanic for a long time).
> I won't tell a person he can't replace a muffler because he doesn't
> possess an acetylene torch, Nor will I say he lacks the skill
> necessary.
> If I caved every time someone said to call a pro, I would have never
> learned to install water heaters, or fix plumbing/drywall or repair
> cars for that matter.
> Thanks,crzzy1
> ----------------------------------------------------
> You do what you gotta do. We can't *SEE* it through the computer, and I
> for
> one don't want to be responsible for that kind of liability.
Warning - run-on one sentence answer. :-)
Oh yeah all that liability, like I would jump through your monitor and
sue you over the Internet because I risked a paltry $120 on a part
instead of spending many times that on a pro that will make a guess
(based on what he has in the trunk), and then when he's wrong I will
have to wait for him to come back and pay him to take another guess.
(Don't say it doesn't happen all the time).
Not to diss the pros out there, there are a few amateurs that call
themselves pros though.
---------------------------------------
Sorry, I am an engineer, not an english major. As for the wannabe techs,
yeah, they are everywhere. Look for a company that has been in business for
several years. The wannabes are usually gone by the time their ads hit the
phone book.
|
|
Posted by The King on December 31, 2008, 11:15 pm
wrote:
>> > > > -----
>> > > > I have a gas furnace, comfortmaker RPJ2 and suspect that it needs a
>> > > > new controller general 90 50A50-110 replacement number is 50A55-843
>> > > > symptom:
>> > > > The igniter works and burns bright, but intermittently the burners
>> > > > will not ignite and the the blower will just keep blowing as the
>> > > > house
>> > > > gets colder.
>> > > > Recycling the power to the unit seems to fix this for a while.
>> > > > Is there a good test I should do?
>> > > Lets keep this real simple.... How do you know its the board??
>> > ----------
>> > Sorry I haven't gotten back to all the responses yet.
>> > The heat has been working It seems to have only flaked out for a few
>> > times there.
>> > So I suspect that it will be OK until it gets really cold. :)
>> > I don't really know that it is the board,
>> > Since the ignitor works (at least visually), and the fan works, and I
>> > have checked all the connections, it seems to only leave 2
>> > likelyhoods, the gas valve and the controller. (Let me know if you
>> > suspect any others that fit the symptoms).
>> > From previous posts, it seems to be more likely the controller.
>> > I don't have an inline amp meter to "amp test" the ignitor, but I
>> > replaced it 2 years ago and it sure is bright, I don't see how that
>> > could not ignite gas if it was present.
>> > I suppose I will have to wait for the problem to reoccure to test it
>> > again, so let me know if there are any tests I can prepare myself
>> > for.
>> > Also if there is a 75% chance that it is the controller I would be
>> > willing to accept that risk and just order it, (because that will take
>> > days and I would rather do it now than when the problem crops up
>> > again).
>> > Thanks,Crzzy1
>> > --------
>> > ====================
>> > No amp meter...
>> > Then you lack the *other* test equipment to properly diagnose your
>> > equipment.
>> > No problem, that's why there are HVAC companies in your area. They're
>> > trained to test and locate problems with heating and cooling equipment.
>> > Then
>> > after you approve the repair, they repair your equipment so you have a
>> > comfortable home to live in... simple as that.
>> > If you want to purchase parts... no problem, how many of each component
>> > would you like?
>> > Might as well change everything and have a spare for the next time. I'm
>> > sure
>> > this is cheaper.... lol
>> haha...
>> I kind of knew this would be the reply.
>> Replacing several parts is still cheaper than calling a tech. $200 vs
>> $700
>> I suspect that given the symptoms, there are a few good educated
>> guesses out there. and a couple of quick tests.
>> Because I am lacking one tool doesn't mean I don't have every other
>> tool to do the job. (I was a mechanic for a long time).
>> I won't tell a person he can't replace a muffler because he doesn't
>> possess an acetylene torch, Nor will I say he lacks the skill
>> necessary.
>> If I caved every time someone said to call a pro, I would have never
>> learned to install water heaters, or fix plumbing/drywall or repair
>> cars for that matter.
>> Thanks,crzzy1
>> ----------------------------------------------------
>> You do what you gotta do. We can't *SEE* it through the computer, and I
>> for
>> one don't want to be responsible for that kind of liability.
>Warning - run-on one sentence answer. :-)
>Oh yeah all that liability, like I would jump through your monitor and
>sue you over the Internet because I risked a paltry $120 on a part
>instead of spending many times that on a pro that will make a guess
>(based on what he has in the trunk), and then when he's wrong I will
>have to wait for him to come back and pay him to take another guess.
>(Don't say it doesn't happen all the time).
>Not to diss the pros out there, there are a few amateurs that call
>themselves pros though.
>---------------------------------------
>Sorry, I am an engineer, not an english major.
Isn't english and required course in engineering? :)
Are you in the engineers registerer like Don is?
>As for the wannabe techs,
>yeah, they are everywhere. Look for a company that has been in business for
>several years. The wannabes are usually gone by the time their ads hit the
>phone book.
I doubt any wannabe is going to spend over a grand a month on phone
book ads. In my area every category, a/c, heat, boiler, ect is
separate and costs big bucks for each one per month. Its also a huge
waste of cash.
|
|
Posted by Jim Dandy on January 2, 2009, 10:46 pm
> wrote:
>>> > > > -----
>>> > > > I have a gas furnace, comfortmaker RPJ2 and suspect that it needs
>>> > > > a
>>> > > > new controller general 90 50A50-110 replacement number is
>>> > > > 50A55-843
>>> > > > symptom:
>>> > > > The igniter works and burns bright, but intermittently the burners
>>> > > > will not ignite and the the blower will just keep blowing as the
>>> > > > house
>>> > > > gets colder.
>>> > > > Recycling the power to the unit seems to fix this for a while.
>>> > > > Is there a good test I should do?
>>> > > Lets keep this real simple.... How do you know its the board??
>>> > ----------
>>> > Sorry I haven't gotten back to all the responses yet.
>>> > The heat has been working It seems to have only flaked out for a few
>>> > times there.
>>> > So I suspect that it will be OK until it gets really cold. :)
>>> > I don't really know that it is the board,
>>> > Since the ignitor works (at least visually), and the fan works, and I
>>> > have checked all the connections, it seems to only leave 2
>>> > likelyhoods, the gas valve and the controller. (Let me know if you
>>> > suspect any others that fit the symptoms).
>>> > From previous posts, it seems to be more likely the controller.
>>> > I don't have an inline amp meter to "amp test" the ignitor, but I
>>> > replaced it 2 years ago and it sure is bright, I don't see how that
>>> > could not ignite gas if it was present.
>>> > I suppose I will have to wait for the problem to reoccure to test it
>>> > again, so let me know if there are any tests I can prepare myself
>>> > for.
>>> > Also if there is a 75% chance that it is the controller I would be
>>> > willing to accept that risk and just order it, (because that will take
>>> > days and I would rather do it now than when the problem crops up
>>> > again).
>>> > Thanks,Crzzy1
>>> > --------
>>> > ====================
>>> > No amp meter...
>>> > Then you lack the *other* test equipment to properly diagnose your
>>> > equipment.
>>> > No problem, that's why there are HVAC companies in your area. They're
>>> > trained to test and locate problems with heating and cooling
>>> > equipment.
>>> > Then
>>> > after you approve the repair, they repair your equipment so you have a
>>> > comfortable home to live in... simple as that.
>>> > If you want to purchase parts... no problem, how many of each
>>> > component
>>> > would you like?
>>> > Might as well change everything and have a spare for the next time.
>>> > I'm
>>> > sure
>>> > this is cheaper.... lol
>>> haha...
>>> I kind of knew this would be the reply.
>>> Replacing several parts is still cheaper than calling a tech. $200 vs
>>> $700
>>> I suspect that given the symptoms, there are a few good educated
>>> guesses out there. and a couple of quick tests.
>>> Because I am lacking one tool doesn't mean I don't have every other
>>> tool to do the job. (I was a mechanic for a long time).
>>> I won't tell a person he can't replace a muffler because he doesn't
>>> possess an acetylene torch, Nor will I say he lacks the skill
>>> necessary.
>>> If I caved every time someone said to call a pro, I would have never
>>> learned to install water heaters, or fix plumbing/drywall or repair
>>> cars for that matter.
>>> Thanks,crzzy1
>>> ----------------------------------------------------
>>> You do what you gotta do. We can't *SEE* it through the computer, and I
>>> for
>>> one don't want to be responsible for that kind of liability.
>>Warning - run-on one sentence answer. :-)
>>Oh yeah all that liability, like I would jump through your monitor and
>>sue you over the Internet because I risked a paltry $120 on a part
>>instead of spending many times that on a pro that will make a guess
>>(based on what he has in the trunk), and then when he's wrong I will
>>have to wait for him to come back and pay him to take another guess.
>>(Don't say it doesn't happen all the time).
>>Not to diss the pros out there, there are a few amateurs that call
>>themselves pros though.
>>---------------------------------------
>>Sorry, I am an engineer, not an english major.
> Isn't english and required course in engineering? :)
> Are you in the engineers registerer like Don is?
He's one of the bell-ringing engineers.
|
|
Posted by Steve on January 3, 2009, 7:59 am
>> wrote:
>>>> > > > -----
>>>> > > > I have a gas furnace, comfortmaker RPJ2 and suspect that it needs
>>>> > > > a
>>>> > > > new controller general 90 50A50-110 replacement number is
>>>> > > > 50A55-843
>>>> > > > symptom:
>>>> > > > The igniter works and burns bright, but intermittently the
>>>> > > > burners
>>>> > > > will not ignite and the the blower will just keep blowing as the
>>>> > > > house
>>>> > > > gets colder.
>>>> > > > Recycling the power to the unit seems to fix this for a while.
>>>> > > > Is there a good test I should do?
>>>> > > Lets keep this real simple.... How do you know its the board??
>>>> > ----------
>>>> > Sorry I haven't gotten back to all the responses yet.
>>>> > The heat has been working It seems to have only flaked out for a few
>>>> > times there.
>>>> > So I suspect that it will be OK until it gets really cold. :)
>>>> > I don't really know that it is the board,
>>>> > Since the ignitor works (at least visually), and the fan works, and I
>>>> > have checked all the connections, it seems to only leave 2
>>>> > likelyhoods, the gas valve and the controller. (Let me know if you
>>>> > suspect any others that fit the symptoms).
>>>> > From previous posts, it seems to be more likely the controller.
>>>> > I don't have an inline amp meter to "amp test" the ignitor, but I
>>>> > replaced it 2 years ago and it sure is bright, I don't see how that
>>>> > could not ignite gas if it was present.
>>>> > I suppose I will have to wait for the problem to reoccure to test it
>>>> > again, so let me know if there are any tests I can prepare myself
>>>> > for.
>>>> > Also if there is a 75% chance that it is the controller I would be
>>>> > willing to accept that risk and just order it, (because that will
>>>> > take
>>>> > days and I would rather do it now than when the problem crops up
>>>> > again).
>>>> > Thanks,Crzzy1
>>>> > --------
>>>> > ====================
>>>> > No amp meter...
>>>> > Then you lack the *other* test equipment to properly diagnose your
>>>> > equipment.
>>>> > No problem, that's why there are HVAC companies in your area. They're
>>>> > trained to test and locate problems with heating and cooling
>>>> > equipment.
>>>> > Then
>>>> > after you approve the repair, they repair your equipment so you have
>>>> > a
>>>> > comfortable home to live in... simple as that.
>>>> > If you want to purchase parts... no problem, how many of each
>>>> > component
>>>> > would you like?
>>>> > Might as well change everything and have a spare for the next time.
>>>> > I'm
>>>> > sure
>>>> > this is cheaper.... lol
>>>> haha...
>>>> I kind of knew this would be the reply.
>>>> Replacing several parts is still cheaper than calling a tech. $200 vs
>>>> $700
>>>> I suspect that given the symptoms, there are a few good educated
>>>> guesses out there. and a couple of quick tests.
>>>> Because I am lacking one tool doesn't mean I don't have every other
>>>> tool to do the job. (I was a mechanic for a long time).
>>>> I won't tell a person he can't replace a muffler because he doesn't
>>>> possess an acetylene torch, Nor will I say he lacks the skill
>>>> necessary.
>>>> If I caved every time someone said to call a pro, I would have never
>>>> learned to install water heaters, or fix plumbing/drywall or repair
>>>> cars for that matter.
>>>> Thanks,crzzy1
>>>> ----------------------------------------------------
>>>> You do what you gotta do. We can't *SEE* it through the computer, and I
>>>> for
>>>> one don't want to be responsible for that kind of liability.
>>>Warning - run-on one sentence answer. :-)
>>>Oh yeah all that liability, like I would jump through your monitor and
>>>sue you over the Internet because I risked a paltry $120 on a part
>>>instead of spending many times that on a pro that will make a guess
>>>(based on what he has in the trunk), and then when he's wrong I will
>>>have to wait for him to come back and pay him to take another guess.
>>>(Don't say it doesn't happen all the time).
>>>Not to diss the pros out there, there are a few amateurs that call
>>>themselves pros though.
>>>---------------------------------------
>>>Sorry, I am an engineer, not an english major.
>> Isn't english and required course in engineering? :)
>> Are you in the engineers registerer like Don is?
> He's one of the bell-ringing engineers.
bring your candy ass down to south Mississippi, and I will ring your bell.
Now its time for you to go home, I hear your mama calling you from under the
porch.
|
Page 5 of 6 < 1 2 3 > last >>
| Similar Threads | Posted | | Need controller. | July 31, 2008, 1:28 pm |
| Need Blower Controller | July 31, 2006, 2:32 am |
| Industrial chiller replace (redesign) controller? | May 16, 2007, 3:20 pm |
| Re: How cold is "beer-can" cold? | October 3, 2009, 11:35 pm |
| Re: How cold is "beer-can" cold? | October 9, 2009, 10:46 pm |
| Another toy recall in the making ? | October 15, 2007, 7:21 pm |
| Making pretty joints | May 2, 2007, 8:27 am |
| making my air conditioner switch on a fan | June 2, 2008, 7:11 pm |
| Heat pump making a clicking noise | February 13, 2008, 10:21 pm |
| Crews making progress restoring natural gas to Buffalo, MN | October 13, 2006, 6:28 pm |
|
|
> > > > I have a gas furnace, comfortmaker RPJ2 and suspect that it needs a
> > > > new controller general 90 50A50-110 replacement number is 50A55-843
> > > > symptom:
> > > > The igniter works and burns bright, but intermittently the burners
> > > > will not ignite and the the blower will just keep blowing as the ho=