Posted by jamesgangnc on December 17, 2006, 11:52 am
Fill the loops with auto antifreeze. It has corrosion inhibitors.
Purge all the air. Close them off really good, preferably with
threaded caps, not just valves. Remove the piece of the firplace loop
that is in the fireplace and cap it's end's off. The metal was
previously cooled by the water in it. Depending on the pipe material
it can become brittle with repeated higher heating.
auctoron wrote:
> Due to changing household requirements, I have decided to mothball my
> custom hydronic heating system. This includes removing the "boiler,"
> which is uninsulated and occupies a huge amount of precious living
> space. A large wood-burning fireplace wrapped with large iron water
> pipes heats the boiler; there's a backup LP gas heater, too. All the
> water pipes are embedded in the concrete slab; no pipes are ever
> exposed to temperatures lower that 40 degrees F. Well, I suppose that,
> if the house were unoccupied and all heat sources shut off, a prolonged
> extremely cold period could result in mild freezing exposure to one
> small section in a closet in the garage.
>
> My questions:
>
> 1. Once the boiler is removed, what should I do with the remainder of
> the system? I mainly want to prevent corrosion in the pipes and pumps
> because I'd like to retain the option to replace the boiler and
> upgrade the system. But I realize that this may not be possible after
> years of disuse.
>
> 2. Is it possible to simply close each of the three zone loops? This
> would allow me to run all the pumps occasionally to prevent them from
> becoming 'frozen.' Somewhere I read that draining the system is a bad
> idea because you can't ever get all the water out and the added air
> will accelerate corrosion.
>
> 3. Should I add a corrosion inhibitor?
>
> 4. What should I do with the fireplace loop if I want to continue
> burning wood? I suppose I must remove all the water from that loop and
> leave it open or else the water will boil and burst a pipe. Then I
> suppose that the extreme heat will boil away any remaining moisture and
> thereby prevent corrosion.
|