How do I mothball my hydronic heating system?

HVAC Discussions - Heating, ventilation and air conditioning. 

Bookmark this page:  YahooMyWeb Yahoo!  Google Google  Windows Live Favorites Windows Live  del.icio.us del.icio.us  digg digg  Add to Netscape Netscape
Subject Author Date
How do I mothball my hydronic heating system? auctoron 12-15-2006
If you were  Registered and logged in, you could reply and use other advanced thread options
Posted by auctoron on December 15, 2006, 1:11 pm
Due to changing household requirements, I have decided to mothball my
custom hydronic heating system. This includes removing the "boiler,"
which is uninsulated and occupies a huge amount of precious living
space. A large wood-burning fireplace wrapped with large iron water
pipes heats the boiler; there's a backup LP gas heater, too. All the
water pipes are embedded in the concrete slab; no pipes are ever
exposed to temperatures lower that 40 degrees F. Well, I suppose that,
if the house were unoccupied and all heat sources shut off, a prolonged
extremely cold period could result in mild freezing exposure to one
small section in a closet in the garage.

My questions:

1. Once the boiler is removed, what should I do with the remainder of
the system? I mainly want to prevent corrosion in the pipes and pumps
because I'd like to retain the option to replace the boiler and
upgrade the system. But I realize that this may not be possible after
years of disuse.

2. Is it possible to simply close each of the three zone loops? This
would allow me to run all the pumps occasionally to prevent them from
becoming 'frozen.' Somewhere I read that draining the system is a bad
idea because you can't ever get all the water out and the added air
will accelerate corrosion.

3. Should I add a corrosion inhibitor?

4. What should I do with the fireplace loop if I want to continue
burning wood? I suppose I must remove all the water from that loop and
leave it open or else the water will boil and burst a pipe. Then I
suppose that the extreme heat will boil away any remaining moisture and
thereby prevent corrosion.


Posted by Bubba on December 15, 2006, 1:43 pm
On 15 Dec 2006 10:11:53 -0800, "auctoron"

>Due to changing household requirements, I have decided to mothball my
>custom hydronic heating system. This includes removing the "boiler,"
>which is uninsulated and occupies a huge amount of precious living
>space. A large wood-burning fireplace wrapped with large iron water
>pipes heats the boiler; there's a backup LP gas heater, too. All the
>water pipes are embedded in the concrete slab; no pipes are ever
>exposed to temperatures lower that 40 degrees F. Well, I suppose that,
>if the house were unoccupied and all heat sources shut off, a prolonged
>extremely cold period could result in mild freezing exposure to one
>small section in a closet in the garage.
>
>My questions:
>
>1. Once the boiler is removed, what should I do with the remainder of
>the system? I mainly want to prevent corrosion in the pipes and pumps
>because I'd like to retain the option to replace the boiler and
>upgrade the system. But I realize that this may not be possible after
>years of disuse.
>
>2. Is it possible to simply close each of the three zone loops? This
>would allow me to run all the pumps occasionally to prevent them from
>becoming 'frozen.' Somewhere I read that draining the system is a bad
>idea because you can't ever get all the water out and the added air
>will accelerate corrosion.
>
>3. Should I add a corrosion inhibitor?
>
>4. What should I do with the fireplace loop if I want to continue
>burning wood? I suppose I must remove all the water from that loop and
>leave it open or else the water will boil and burst a pipe. Then I
>suppose that the extreme heat will boil away any remaining moisture and
>thereby prevent corrosion.

Just jump off a bridge. It would make everything easier.
Bubba

Posted by daytona° on December 15, 2006, 11:34 pm
This giving me a headache to read it. You do have MAJOR problems
Without seeing it...WOW

> Due to changing household requirements, I have decided to mothball my
> custom hydronic heating system. This includes removing the "boiler,"
> which is uninsulated and occupies a huge amount of precious living
> space. A large wood-burning fireplace wrapped with large iron water
> pipes heats the boiler; there's a backup LP gas heater, too. All the
> water pipes are embedded in the concrete slab; no pipes are ever
> exposed to temperatures lower that 40 degrees F. Well, I suppose that,
> if the house were unoccupied and all heat sources shut off, a prolonged
> extremely cold period could result in mild freezing exposure to one
> small section in a closet in the garage.
>
> My questions:
>
> 1. Once the boiler is removed, what should I do with the remainder of
> the system? I mainly want to prevent corrosion in the pipes and pumps
> because I'd like to retain the option to replace the boiler and
> upgrade the system. But I realize that this may not be possible after
> years of disuse.
>
> 2. Is it possible to simply close each of the three zone loops? This
> would allow me to run all the pumps occasionally to prevent them from
> becoming 'frozen.' Somewhere I read that draining the system is a bad
> idea because you can't ever get all the water out and the added air
> will accelerate corrosion.
>
> 3. Should I add a corrosion inhibitor?
>
> 4. What should I do with the fireplace loop if I want to continue
> burning wood? I suppose I must remove all the water from that loop and
> leave it open or else the water will boil and burst a pipe. Then I
> suppose that the extreme heat will boil away any remaining moisture and
> thereby prevent corrosion.
>



Posted by jamesgangnc on December 17, 2006, 11:52 am
Fill the loops with auto antifreeze. It has corrosion inhibitors.
Purge all the air. Close them off really good, preferably with
threaded caps, not just valves. Remove the piece of the firplace loop
that is in the fireplace and cap it's end's off. The metal was
previously cooled by the water in it. Depending on the pipe material
it can become brittle with repeated higher heating.

auctoron wrote:
> Due to changing household requirements, I have decided to mothball my
> custom hydronic heating system. This includes removing the "boiler,"
> which is uninsulated and occupies a huge amount of precious living
> space. A large wood-burning fireplace wrapped with large iron water
> pipes heats the boiler; there's a backup LP gas heater, too. All the
> water pipes are embedded in the concrete slab; no pipes are ever
> exposed to temperatures lower that 40 degrees F. Well, I suppose that,
> if the house were unoccupied and all heat sources shut off, a prolonged
> extremely cold period could result in mild freezing exposure to one
> small section in a closet in the garage.
>
> My questions:
>
> 1. Once the boiler is removed, what should I do with the remainder of
> the system? I mainly want to prevent corrosion in the pipes and pumps
> because I'd like to retain the option to replace the boiler and
> upgrade the system. But I realize that this may not be possible after
> years of disuse.
>
> 2. Is it possible to simply close each of the three zone loops? This
> would allow me to run all the pumps occasionally to prevent them from
> becoming 'frozen.' Somewhere I read that draining the system is a bad
> idea because you can't ever get all the water out and the added air
> will accelerate corrosion.
>
> 3. Should I add a corrosion inhibitor?
>
> 4. What should I do with the fireplace loop if I want to continue
> burning wood? I suppose I must remove all the water from that loop and
> leave it open or else the water will boil and burst a pipe. Then I
> suppose that the extreme heat will boil away any remaining moisture and
> thereby prevent corrosion.


Similar ThreadsPosted
Large Diameter Pipes in Hydronic Heating System January 5, 2007, 1:26 pm
Hydronic Heating in our farm greenhouse April 3, 2008, 12:47 pm
Hydronic Heating in our farm greenhouse April 3, 2008, 1:12 pm
Re: Intermittent high pressure in hot water heating system system February 3, 2007, 9:46 am
Re: Intermittent high pressure in hot water heating system system February 4, 2007, 3:49 pm
Re: Intermittent high pressure in hot water heating system system February 4, 2007, 3:54 pm
Re: Intermittent high pressure in hot water heating system system February 4, 2007, 3:43 pm
Re: Intermittent high pressure in hot water heating system system February 4, 2007, 3:06 pm
Re: Intermittent high pressure in hot water heating system system February 4, 2007, 3:05 pm
Re: Intermittent high pressure in hot water heating system system February 2, 2007, 10:20 am

Contact Us | Privacy Policy

XML SitemapXML Sitemap