Intercity Products intermittently cooling tpcolson 07-14-2006
If you were  Registered and logged in, you could reply and use other advanced thread options
Posted by on July 14, 2006, 3:56 pm
I have a Intercity Products PGAA29C1K1 that recently started cutting on
and off, intermittently, in cool mode. The blower motor runs
continuously. I inititally thought it was the thermostat...a digitial
hi-tech model with all the timers and programs, swithched that to a
regular single temperature thermostat with a thermistor...no
help...then put the original, 10 year old, old school sping and mercury
thermostat back on. Still no deal. Yes I changed the batteries in the
first two. It's a 4 wire system. Often, when I turn the thermo to cold
(fan is set to auto), the compressor won't kick on, but the blower
will. This is usually the case. Rarely, the compressor will kick on,
and run anywhere from 5 minutes to 2 hours. Here I sit typing this, in
my house temp is up to 110, damn thing hasn't run since 9 am (in
Raleigh, NC, no shade on house). I suspect something is over heating,
and the heat of the day accelerates that.

I post here, because I'm getting kind of desparate. I've had 3
contractors here, all smelling a quick and easy kill, telling me a) the
whole thing needs to be replaced and b) do I want to get on their list
for an appointment (4 weeks). The compressor was replaced in 2000. I'm
also...err....in a little cash flow situation...work for the
state...and I just got switched to bi-weekly pay, so I'll only get a
1/4 pay check at the end of this month (it all got pushed forward in
some kinda accounting scam that I'm sure is going to scew me at the end
of the year). So if there's any secret "stick a piece of copper pipe
between the terminals" fix....i'd love to hear it. Death by 240 V shock
will be a welcome relief from the hell I'm sweltering in now. I'm
hoping there's a simple, obvious fix like a run capicitor or something
like that....thanks.


Posted by Al Moran on July 14, 2006, 7:19 pm
On 14 Jul 2006 12:56:36 -0700, tpcolson@gmail.com wrote:

>Death by 240 V shock
>will be a welcome relief from the hell I'm sweltering in now. I'm
>hoping there's a simple, obvious fix like a run capicitor or something
>like that....thanks.


I can help you with that. Turn the system on, Take the cover off, find
any piece with wires on them and grab hold. That'll be 99.99, you're
welcome.

Posted by Bubba on July 14, 2006, 7:38 pm
On 14 Jul 2006 12:56:36 -0700, tpcolson@gmail.com wrote:

>I have a Intercity Products PGAA29C1K1 that recently started cutting on
>and off, intermittently, in cool mode. The blower motor runs
>continuously. I inititally thought it was the thermostat...a digitial
>hi-tech model with all the timers and programs, swithched that to a
>regular single temperature thermostat with a thermistor...no
>help...then put the original, 10 year old, old school sping and mercury
>thermostat back on. Still no deal. Yes I changed the batteries in the
>first two. It's a 4 wire system. Often, when I turn the thermo to cold
>(fan is set to auto), the compressor won't kick on, but the blower
>will. This is usually the case. Rarely, the compressor will kick on,
>and run anywhere from 5 minutes to 2 hours. Here I sit typing this, in
>my house temp is up to 110, damn thing hasn't run since 9 am (in
>Raleigh, NC, no shade on house). I suspect something is over heating,
>and the heat of the day accelerates that.
>
>I post here, because I'm getting kind of desparate. I've had 3
>contractors here, all smelling a quick and easy kill, telling me a) the
>whole thing needs to be replaced and b) do I want to get on their list
>for an appointment (4 weeks). The compressor was replaced in 2000. I'm
>also...err....in a little cash flow situation...work for the
>state...and I just got switched to bi-weekly pay, so I'll only get a
>1/4 pay check at the end of this month (it all got pushed forward in
>some kinda accounting scam that I'm sure is going to scew me at the end
>of the year). So if there's any secret "stick a piece of copper pipe
>between the terminals" fix....i'd love to hear it. Death by 240 V shock
>will be a welcome relief from the hell I'm sweltering in now. I'm
>hoping there's a simple, obvious fix like a run capicitor or something
>like that....thanks.

Simple fix, usually. Change the stat again. Its almost always the
stat. If that doesnt work, go outside, take your shoes off, stand in a
puddle of water, open the electrical disconnect and grab the bare
wires with a good tight grip.
Oh, by the way. Your story is wonderful. You are what you are. If you
dont like your life, wife or job, Change them. Dont whine to us. We
dont care.
Bubba

Similar ThreadsPosted
Oil Boiler fires intermittently March 9, 2007, 9:48 pm
Compressor operates intermittently throughout the day August 23, 2007, 11:33 pm
Convert a cooling thermostat to a cooling September 29, 2006, 9:00 pm
upstiars cooling August 1, 2006, 8:25 am
Window AC unit not cooling August 1, 2006, 12:48 pm
Radiator use as a cooling coil August 3, 2006, 11:24 pm
13 SEER Splits not cooling!??! August 8, 2006, 9:40 pm
datacenter cooling question.... October 23, 2006, 3:45 pm
Wine Cooling Unit December 28, 2006, 1:12 pm
HVAC Cooling Coil July 13, 2007, 1:26 pm

Contact Us | Privacy Policy

XML SitemapXML Sitemap