Intermittent Pilot will not shut down after heat cycle

HVAC Discussions - Heating, ventilation and air conditioning. 

Bookmark this page:  YahooMyWeb Yahoo!  Google Google  Windows Live Favorites Windows Live  del.icio.us del.icio.us  digg digg  Add to Netscape Netscape
Subject Author Date
Intermittent Pilot will not shut down after heat cycle dlopez5 12-02-2006
If you were  Registered and logged in, you could reply and use other advanced thread options
Posted by on December 2, 2006, 12:25 pm
Have an older Carrier Gaspack with the original Dual valve gas assy.
Replaced the original J/C G600XL with a Honeywell S8610 univ
intermittent pilot ignition module. The system still has the same
following problem. After heat cycle the main burner shuts down, but
the intermittent pilot remains burning - with no voltage across the
coil. In this state a further call for heat from the thermostat will
not turn the main burner on. I have tested the valve coils out of
control circuit and both actuate with 24Vac across them.

So at this point I can only beleive that the Valve body has some sort
of leak internally to feed the pilot regardless of the state on the
valve coil.

Any help as to what my next step should be ?? Replace valve ??


Thanks
UpsMan


Posted by on December 2, 2006, 12:38 pm
On 2 Dec 2006 09:25:51 -0800, dlopez5@nc.rr.com wrote:

> Have an older Carrier Gaspack with the original Dual valve gas assy.
>Replaced the original J/C G600XL with a Honeywell S8610 univ
>intermittent pilot ignition module. The system still has the same
>following problem. After heat cycle the main burner shuts down, but
>the intermittent pilot remains burning - with no voltage across the
>coil. In this state a further call for heat from the thermostat will
>not turn the main burner on. I have tested the valve coils out of
>control circuit and both actuate with 24Vac across them.
>
>So at this point I can only beleive that the Valve body has some sort
>of leak internally to feed the pilot regardless of the state on the
>valve coil.
>
>Any help as to what my next step should be ?? Replace valve ??

        Check your pressure.

>
>
>Thanks
>UpsMan

--
Click here every day to feed an animal that needs you today !!!
http://www.theanimalrescuesite.com/

Paul ( pjm @ pobox . com ) - remove spaces to email me
'Some days, it's just not worth chewing through the restraints.'
'With sufficient thrust, pigs fly just fine.'
HVAC/R program for Palm PDA's
Free demo now available online http://pmilligan.net/palm/

Posted by Noon-Air on December 2, 2006, 1:36 pm

> Have an older Carrier Gaspack with the original Dual valve gas assy.
> Replaced the original J/C G600XL with a Honeywell S8610 univ
> intermittent pilot ignition module. The system still has the same
> following problem. After heat cycle the main burner shuts down, but
> the intermittent pilot remains burning - with no voltage across the
> coil. In this state a further call for heat from the thermostat will
> not turn the main burner on. I have tested the valve coils out of
> control circuit and both actuate with 24Vac across them.
>
> So at this point I can only beleive that the Valve body has some sort
> of leak internally to feed the pilot regardless of the state on the
> valve coil.
>
> Any help as to what my next step should be ?? Replace valve ??

How old is this gas pack??
What did your favorite, local, *COMPETENT*, licensed, professionally
trained, HVAC technician say??



Posted by Bubba on December 2, 2006, 4:38 pm
On 2 Dec 2006 09:25:51 -0800, dlopez5@nc.rr.com wrote:

> Have an older Carrier Gaspack with the original Dual valve gas assy.
>Replaced the original J/C G600XL with a Honeywell S8610 univ
>intermittent pilot ignition module. The system still has the same
>following problem.

Hmmm, does that tell you anything?
Ever think maybe that the G60 wasn't your problem?

>After heat cycle the main burner shuts down, but
>the intermittent pilot remains burning - with no voltage across the
>coil. In this state a further call for heat from the thermostat will
>not turn the main burner on. I have tested the valve coils out of
>control circuit and both actuate with 24Vac across them.
>
>So at this point I can only beleive that the Valve body has some sort
>of leak internally to feed the pilot regardless of the state on the
>valve coil.
>
>Any help as to what my next step should be ??

Yes. I have perfect advice for you. You are on the right track. Keep
replacing parts. I can guarantee you 100% that at some point you will
get it fixed with your current method.

>Replace valve ??
>
>Thanks
>UpsMan

Why not? You will be one step closer after replacing it.
Bubba


Posted by on December 2, 2006, 7:07 pm
The G60 worked last year to the extent of the current problem having
to shut the gas feed to extinquish the pilot.I knew the control module
was not the problem but could not understand how the pilot can still be
getting fed gas with no voltage on the coil and additionally pulling
the coil wire - still the pilot burns... At the start of this season it
just would not start the cycle (no spark, no coil voltage)that is why I
replaced it . Hence I wanted to get it working regardless even if I had
to re-set the system (power off-on, manual valve on). The new module
works with the same after heat cycle observations - the pilot refuses
to go out when the valve closes(no voltage)
Back to my orignal question on the valve body , can there be an
internal leak(path) to the pilot line that would cause such a problem
outside of a coil failure??

UpsMan
Bubba wrote:
> On 2 Dec 2006 09:25:51 -0800, dlopez5@nc.rr.com wrote:
>
> > Have an older Carrier Gaspack with the original Dual valve gas assy.
> >Replaced the original J/C G600XL with a Honeywell S8610 univ
> >intermittent pilot ignition module. The system still has the same
> >following problem.
>
> Hmmm, does that tell you anything?
> Ever think maybe that the G60 wasn't your problem?
>
> >After heat cycle the main burner shuts down, but
> >the intermittent pilot remains burning - with no voltage across the
> >coil. In this state a further call for heat from the thermostat will
> >not turn the main burner on. I have tested the valve coils out of
> >control circuit and both actuate with 24Vac across them.
> >
> >So at this point I can only beleive that the Valve body has some sort
> >of leak internally to feed the pilot regardless of the state on the
> >valve coil.
> >
> >Any help as to what my next step should be ??
>
> Yes. I have perfect advice for you. You are on the right track. Keep
> replacing parts. I can guarantee you 100% that at some point you will
> get it fixed with your current method.
>
> >Replace valve ??
> >
> >Thanks
> >UpsMan
>
> Why not? You will be one step closer after replacing it.
> Bubba


Similar ThreadsPosted
What is heat pump cycle rate? September 26, 2007, 5:49 pm
Heat Pump will not shut off November 18, 2007, 6:23 am
Furnace blows but does not heat (intermittent problem) January 15, 2007, 8:19 pm
Furnace will only run one cycle then stops February 21, 2007, 2:35 pm
make dry ice by an absorption cycle? March 28, 2007, 11:52 pm
Re: Lennox Whisperheat G20 with standing pilot October 16, 2006, 12:42 am
Water Heater Pilot Light Keeps Going Out October 17, 2006, 7:52 pm
Carrier 58 furnace pilot gas valve January 24, 2007, 11:23 am
Coleman 7900b Presidential Electronic pilot retrofit , also any service bulletins December 24, 2006, 11:25 am
My AC won't shut off !!!!! August 9, 2007, 4:10 pm

Contact Us | Privacy Policy

XML SitemapXML Sitemap