Lennox Compressor Cutting Out

HVAC Discussions - Heating, ventilation and air conditioning. 

Bookmark this page:  YahooMyWeb Yahoo!  Google Google  Windows Live Favorites Windows Live  del.icio.us del.icio.us  digg digg  Add to Netscape Netscape
Subject Author Date
Lennox Compressor Cutting Out jsherman 09-03-2006
If you were  Registered and logged in, you could reply and use other advanced thread options
Posted by jsherman on September 3, 2006, 12:23 pm
My 10-year old, 5-ton Lennox A/C system started giving me problems
recently. For some time, we have heard a gurgling sound coming from
the attic (where the evaporator/blower is). The sound kept getting
louder and longer. Finally, a couple of weeks ago, the compressor
started overheating and shutting off in mid-cycle; I also noticed the
connections to the outside unit icing up. A repair man came out and
replaced the expansion valve, which seemed to help for a few days, but
now the compressor is occasionally shutting off in mid-cycle again, and
I have noticed ice buildup outside. Is there anything else that could
be causing the problem? Thanks.


Posted by udarrell on September 3, 2006, 12:53 pm
jsherman wrote:

>My 10-year old, 5-ton Lennox A/C system started giving me problems
>recently. For some time, we have heard a gurgling sound coming from
>the attic (where the evaporator/blower is). The sound kept getting
>louder and longer. Finally, a couple of weeks ago, the compressor
>started overheating and shutting off in mid-cycle; I also noticed the
>connections to the outside unit icing up. A repair man came out and
>replaced the expansion valve, which seemed to help for a few days, but
>now the compressor is occasionally shutting off in mid-cycle again, and
>I have noticed ice buildup outside. Is there anything else that could
>be causing the problem? Thanks.
>
>
Gurgling sounds, freeze-up - Symptoms indicate a possible refrigerant leak.
That is only a guess, we can not diagnosis problems from here!
I am NOT responsible for what you & your tech do.
There is a problem that needs to be addressed!
Read all, you can & get you tech to do the same!
If he uses all of the diagnostic tests available, he will locate the
problem(s)!
- udarrell

--
Air Conditioning's Affordable Path to the "Human Comfort Zone Goal"
(Revised - Solving ESP)
http://www.udarrell.com/external_static_pressure_readings.html
http://www.udarrell.com/udarrell-air-conditioning.html

Posted by Bubba on September 3, 2006, 1:28 pm
wrote:

>My 10-year old, 5-ton Lennox A/C system started giving me problems
>recently. For some time, we have heard a gurgling sound coming from
>the attic (where the evaporator/blower is). The sound kept getting
>louder and longer. Finally, a couple of weeks ago, the compressor
>started overheating and shutting off in mid-cycle; I also noticed the
>connections to the outside unit icing up. A repair man came out and
>replaced the expansion valve, which seemed to help for a few days, but
>now the compressor is occasionally shutting off in mid-cycle again, and
>I have noticed ice buildup outside. Is there anything else that could
>be causing the problem? Thanks.

You need to have the same guy come out. He needs to change the
expansion valve again. Those go bad pretty often and once in a while
they get a bad batch of them. That should take care of it.
Be prepared to pay for it again though. Its not his fault the valve
went bad.
Bubba

Posted by Dido on September 4, 2006, 9:50 am

> My 10-year old, 5-ton Lennox A/C system started giving me problems
> recently. For some time, we have heard a gurgling sound coming from
> the attic (where the evaporator/blower is). The sound kept getting
> louder and longer. Finally, a couple of weeks ago, the compressor
> started overheating and shutting off in mid-cycle;

"I also noticed the connections to the outside unit icing up. "
It sounds and looks like overcharge to me
and possible not enough air across cooling coil
DIDO

A repair man came out and
> replaced the expansion valve, which seemed to help for a few days, but
> now the compressor is occasionally shutting off in mid-cycle again, and
> I have noticed ice buildup outside. Is there anything else that could
> be causing the problem? Thanks.
>



Similar ThreadsPosted
Will non-lennox brands work for independent humidity control in a Lennox system May 2, 2007, 4:34 pm
Updated replacement Compressor Model Number for a 21 year old dead compressor(s) September 12, 2007, 12:34 am
lennox a/c June 29, 2007, 7:41 pm
Why (again) would you own a Lennox? February 15, 2007, 6:37 pm
Lennox pulse 21 December 30, 2006, 6:56 pm
Lennox Heater Fan.. April 15, 2007, 11:55 am
Central Air- Lennox? May 25, 2007, 4:05 pm
LENNOX L Connection October 22, 2007, 3:39 pm
Lennox Condensor fan-Capacitor July 26, 2006, 12:04 pm
Help with Lennox coil sizing August 30, 2006, 8:50 pm

Contact Us | Privacy Policy

XML SitemapXML Sitemap