|
Posted by on December 28, 2008, 10:05 am
> On Sat, 27 Dec 2008 19:13:20 -0800 (PST), jkenne...@gmail.com wrote:
> >> wrote:
> >> >> wrote:
> >> >>>> On Sat, 27 Dec 2008 16:22:45 -0600, "Noon-Air" <Noon-...@comcast.=
net>
> >> >>>> wrote:
s.com...
> >> >>>>>> Hi, I purchased a new high effiency Lennox G61V furnace a year =
ago,
> >> >>>>>> and have had problems ever since. =A0After numerous visits from=
the
> >> >>>>>> installer, we've finally determined that water from the cold he=
ader
> >> >>>>>> box (which sit directly behind the combustion inducer fan), doe=
s not
> >> >>>>>> drain out until the furnace shuts down. =A0So, basically if it =
is cold
> >> >>>>>> outside and the furnace runs for several hours straight, that w=
ater
> >> >>>>>> continues to build up and gets into the inducer fan, which caus=
e all
> >> >>>>>> kinds of problems, and the furnace shuts down.
> >> >>>>>> The service people I've used have called lennox, but can not fi=
gure
> >> >>>>>> out why the water would not drain out until the furnace winds d=
own or
> >> >>>>>> is shut off.
> >> >>>>>> Has anyone run into this issue before? =A0I'm a good $1000 in o=
n
> >> >>>>>> maintenance fees right now and I'm not sure what to do at this =
point.
> >> >>>>>> thanks,
> >> >>>>>> Joe
> >> >>>>>Was it the lowest price?? Seems that one of the first things they=
cut
> >> >>>>>corners on is not putting a proper trap in the drain line. There =
is a
> >> >>>>>reason
> >> >>>>>for the trap being there....looks like you found out about it the=
hard
> >> >>>>>way.
> >> >>>> The trap is incorporated into the furnace at the factory. =A0He i=
s not
> >> >>>> talking about the trap on the a coil. =A0Which BTW isn't needed o=
n a up
> >> >>>> flow furnace you dolt.
> >> >>>Having never worked on that particular model, I'll take you word fo=
r it...
> >> >>>Either way, from the symptoms, there are issues with the trap eithe=
r being
> >> >>>partially blocked or not being deep enough.
> >> >> I agree that it sounds like a trap problem or possibly a venting is=
sue
> >> >> with the pitch of the pipe. =A0Its not a field fabricated trap. =A0=
Like
> >> >> all 90 plus furnaces, the trap comes with the furnace.
> >> >>>Now....as far as a trap on an upflow coil, Rheem/RUUD *REQUIRES* th=
at
> >> >>>there
> >> >>>be a trap that a minimum of 6 inches below the coil pan, and the tr=
ap must
> >> >>>be a minimum of 3 inches deep. There is a reason the factory puts n=
otes in
> >> >>>the installation instructions and puts a sticker on the coil and/or=
coil
> >> >>>casing that gives the dimentions of the required trap. I have seen =
the
> >> >>>same
> >> >>>trap requirements for Carrier and Trane. Not only do they give the
> >> >>>dimentions, but they also include pictures...*just* for you.
> >> >> I don't know why they would make it a requirement since it has noth=
ing
> >> >> to do with condensate drainage on an up flow.
> >> >> Blow thru coils don't need a trap to drain properly. =A0Pull thru c=
oils
> >> >> do.
> >> >I didn't write the installation instructions.... but I do actually *R=
EAD*
> >> >them, and follow them. =A0So far, I have never seen installation inst=
ructions
> >> >that said that traps were only for "pull through coils".
> >> > Maybe you could
> >> >show me where installation instructions say that traps are only requi=
red for
> >> >"blow through" evap coils?? or maybe give me a code site??
> >> It doesn't have anything to do with codes or installation
> >> instructions. =A0It =A0has to do with the static pressure across the c=
oil
> >> and drain pan. =A0As you full well know, or should know, when a blower
> >> is downstream (pull thru) of the evap coil it wont drain until the
> >> blower shuts off. =A0When the blower is upstream of the coil it will
> >> drain just fine regardless of if its trapped or not. =A0
> >> So why do they want a trap on an up flow? =A0I suspect its just over
> >> kill.- Hide quoted text -
> >> - Show quoted text -
> >Alright, since this is a Usenet group, I can't email or load photos
> >(thanks google). =A0King, can I just emial you a picture of the front of
> >the furance so you can see if anything look incorrect? =A0Also can you
> >explain your comment above further (I am rookie on this stuff right
> >now). =A0I have an upflow furnace, the exhaust pipe is above the
> >blower. =A0So I agree with you, why do I even need a trap, I don't see
> >how any fumes would go anywhere but up. thx.
> Were talking two different traps. =A0One for the A/C condensate and the
> one for the furnace condensate. =A0You need the trap for the furnace
> condensate. =A0Make sure the trap is clean, make sure the exhaust is
> pitched back towards the furnace 1/4 inch per liner foot with no sags,
> make sure there are no kinks in any drain lines, make sure there are
> no blockages in any drain lines inside and outside of the furnace.- Hide =
quoted text -
> - Show quoted text -
I see. this situation does not seem to be a problem with the exhaust
condensation/ drainage, and I have check the 1/4 inch decline on the
pipe. The cold header box behind the inducer fan does not drain
(although I can hear water in there) until the furnace shuts down.
|