|
Posted by Graham Campbell on September 5, 2006, 4:29 pm
Thanks. Like I said, I set it up per the manual. Lochinvar had people
there today - they couldn't figure it out. A real confidence builder.
>
> Graham Campbell wrote:
>> Has anybody had problems with the Lochinvar Energy Rite 2? I have 2 of
>> them - one doing pool water and the other one doing the spa water.
>> Neither
>> will lite. I have the box pressure at 1.2-1.4" wc with the draft inducer
>> running, and a total of 3.2" wc with LP gas pressure. The boiler is
>> clean,
>> as are the burners, the HSI is glowing - but these things simply won't
>> fire.
>> I have tried increasing both air and gas to 3.8-4.0" wc gross without
>> success. In addition to the hi/lo hoses running to the air proving
>> switch
>> from the pressure box, there is a hose running from the box to the inlet
>> side of the honeywell smart valve - the manual calls it a reference hose.
>> If I pull this hose from the barbed fitting on the gas valve, cover the
>> fitting with my finger, the boiler lights every time. Lochinvar's tech
>> support does even recognize this particular hose - even though it is
>> clearly
>> referenced in their I&O Manual.
>>
>> Baffled here.
>> Graham Campbell
>
> If I were you id double check the inlet and outlet gas pressure and the
> air pressure exactly the way that the I&O Manual suggests.
>
|