Loss of Charge Switch Moe Jones 07-26-2006
If you were  Registered and logged in, you could reply and use other advanced thread options
Posted by Moe Jones on July 26, 2006, 10:28 am
I have a question on a loss of charge switch.

There is a equipment manufacture who in the past had a loss of charge switch
which mounted on the liquid line of a R-22 package unit. It would open
around 7 PSI.

We presently use this switch for the building alarm to be set off after
someone tries to steal the copper from the A/C systems. Because scrap copper
is selling for over $3 per pound, thieves have been stealing condensing
coils all around our area. I tell it works, allot of the time we have had to
repair the units but not replace the units.

Now my question:

Would you think the switch would work on a 410a system?

We haven't tried it and I have asked the equipment manufacture and get no
answer. I do not know who makes the switch for the equipment manufacture so
I can not ask them.

I know in the past we first tried some standard low pressure switches and
found they did not last too long but did find the loss of charge switch did
work fine for a R-22 system. With the new refrigerant (410a) we have been
asked to install some of these switches. I have asked the equipment
manufacture if they make the same switch for 410a and they say no.

--
Moe Jones
HVAC Service Technician
Energy Equalizers Inc.
Houston, Texas



Posted by on July 26, 2006, 10:33 pm

>I have a question on a loss of charge switch.
>There is a equipment manufacture who in the past had a loss of charge switch
>which mounted on the liquid line of a R-22 package unit. It would open
>around 7 PSI.
>We presently use this switch for the building alarm to be set off after
>someone tries to steal the copper from the A/C systems. Because scrap copper
>is selling for over $3 per pound, thieves have been stealing condensing
>coils all around our area. I tell it works, allot of the time we have had to
>repair the units but not replace the units.
>Now my question:
>Would you think the switch would work on a 410a system?
>We haven't tried it and I have asked the equipment manufacture and get no
>answer. I do not know who makes the switch for the equipment manufacture so
>I can not ask them.

no guts, no glory.

whats to prevent you from installing one on a 410 system and trying it
out for yourself?


>I know in the past we first tried some standard low pressure switches and
>found they did not last too long but did find the loss of charge switch did
>work fine for a R-22 system. With the new refrigerant (410a) we have been
>asked to install some of these switches. I have asked the equipment
>manufacture if they make the same switch for 410a and they say no.


Posted by Al Moran on July 28, 2006, 10:28 pm
wrote:

>I have a question on a loss of charge switch.
>There is a equipment manufacture who in the past had a loss of charge switch
>which mounted on the liquid line of a R-22 package unit. It would open
>around 7 PSI.
>We presently use this switch for the building alarm to be set off after
>someone tries to steal the copper from the A/C systems. Because scrap copper
>is selling for over $3 per pound, thieves have been stealing condensing
>coils all around our area. I tell it works, allot of the time we have had to
>repair the units but not replace the units.
>Now my question:
>Would you think the switch would work on a 410a system?
>We haven't tried it and I have asked the equipment manufacture and get no
>answer. I do not know who makes the switch for the equipment manufacture so
>I can not ask them.
>I know in the past we first tried some standard low pressure switches and
>found they did not last too long but did find the loss of charge switch did
>work fine for a R-22 system. With the new refrigerant (410a) we have been
>asked to install some of these switches. I have asked the equipment
>manufacture if they make the same switch for 410a and they say no.


Just tie a big, mean, nasty dog to the condenser and don't feed it.
Problem solved.

Similar ThreadsPosted
HVAC Engineering 101 - Question about heat loss through ductwork December 24, 2007, 11:42 am
question about open garage doors and heat loss January 22, 2009, 12:56 pm
help, help, help , halp me, lordy the man gonna charge me !!! July 14, 2007, 11:16 am
Charge Heat Pump in AC mode even in winter?? November 8, 2006, 8:50 pm
Heat Pump Line Set Temperature - bad charge? October 27, 2007, 11:13 am
minisplit evac & reweighing of liquid charge May 13, 2008, 12:00 pm
Fan/ Limit switch November 1, 2006, 10:39 am
Pressure switch March 1, 2008, 9:01 pm
pressure switch on gas furnace October 18, 2006, 1:28 pm
fan short cycles but it isn't the switch November 4, 2006, 6:06 pm

Contact Us | Privacy Policy

XML SitemapXML Sitemap