|
Posted by Moe Jones on July 20, 2006, 6:38 pm
After reading your post and seeing that you had to have it topped off every
year, that may be a problem.
My advise to call another A/C company other that the company that installed
the system in the first place.
Pay the money and have them come out and to check the duct work, the
operation of the total system. You might be surprised on what they find.
Heck I have even found systems when a part of the strip heater staying on
while the A/C was running and have found holes in the return duct in the
attic so the system was sucking in hot air from the attic. There could be
allot wrong with your system so like I said get another company out there to
check.
--
Moe Jones
HVAC Service Technician
Energy Equalizers Inc.
Houston, Texas
>I just bought a new home about 1.75 years ago, and have been having AC
> problems ever since. My AC seems to run constantly, (set on auto).
>
> My electric bills have been in the $400 range and I think my unit is
> too small for the house.
>
> Quick Description:
>
> 3150 SqFt
> Supposedly "Energy Star" Certified, although you can see daylight
> through some doors, attic had to have insulation added 3 times, etc.
>
> There is an "owners retreat" above the master, that is isolated from
> the rest of the house. This room is constantly in the 79-81 range, no
> matter what the AC is set on.
>
> 5 ton unit on house now, 6 SEER I believe.
>
> I am in Houston, where it's hot as hell, but I keep the unit set on 77.
> At 10pm it goes to 75 until about 7am just so we can sleep.
>
> The builder says the unit is the right size. Their AC company agrees.
> Everyone else I know does not experience the same problems I do. They
> keep their AC much lower, and their bills are much lower as well. All
> of my appliances are new. I work from home, and just about the only
> thing on is my computer/monitor/printer and ceiling fans. I work out
> of the home office or the "master's retreat".
>
> The TSTAT is located upstairs. The temps listed are in the "Masters
> retreat/office".
>
> I was logging the AC cycle the other day for about 4 hours and this is
> what happened:
>
> It is now 10:22am and it is 81.5 degrees in this office, (masters
> retreat). It has been hovering at this temperature for over 30
> minutes.
>
> The AC has just kicked on. The thermostat is set on 77.
>
> It's now 11:00am and the AC has just stopped. It has not stopped since
> 10:22am. The temperature in the office (master's retreat) is now 78.3.
>
> It took the AC 38 minutes of continous blowing to drop the temperature
> (when set an at uncomfortable 77deg) in the house back to 77. The temp
> in the retreat went from 81.5 to 78.3, a difference of 3.2 degrees.
>
> It's now 11:15am and the temperature in the master's retreat is once
> again 79.6 degrees. That's just 15 minutes after the AC stopped
> blowing.
>
> It's now 11:36 the temperature is 80.8 in the retreat and the AC has
> just kicked on again. (NOTE: Today at 12:00 the TSTAT is set to go to
> 76 deg for a few hours, just so I can work without sweating.)
>
> It's now 12:53 and the AC just shut off. The temperature is 77 in the
> retreat. The AC ran for 1 hour and 17 minutes STRAIGHT, just to get
> the the house to 76 from the moment it went over 77 and turned on.
>
> So to sum up, the temperature at the TSTAT went above 77 and caused the
> AC to start at 11:36. The AC blew constantly until 12PM at which time
> it still had not lowered the house temp to 77 (24 minutes), at 12PM the
> TSTAT setting went to 76, causing the AC to continue to blow, to try
> and bring the house down one more degree. It took until 12:53pm to get
> to that extra degree of 76. That was a continuous cycle of 1 hour and
> 17 minutes to blow, to get the house to go from the moment it went over
> 77 (setting off the AC) to 76 degrees.
>
> It's now 1:15pm and the temp is 78.6 in the retreat.
> It's now 1:20pm and the temp is 79.2 in the retreat. The AC has just
> kicked on.
>
> It's now 2:15 pm and the temp is 77.2 in the retreat. The AC just
> turned off. It ran for 55 minutes straight.
>
> So from 10:22am - 2:15pm - that's 3 hours and 53 minutes. In that
> 3hours and 53 minutes, the AC ran for 2 hours and 50 minutes.
> (2:38pm and it's on again)
> <<<<< END OF LOG>>>>>>>
>
> Is this normal? The builder, in an effort to fix the hot owner retreat
> problem has done the following to no avail:
>
> Repairing ac leak 03/28/05
> Adding a straight run to master's retreat 05/26/05
> Adding Insulation (I was told the insulation was WAY too low to begin
> with) 06/28/05
> Changing out the thermostat 06/28/05
> Checking the AC system 08/18/05
> Engineers come out to check system 05/23/2006
> Checking / Recharging AC (tech said it was a bit low) 07/05/06
> Adding Insulation 07/12/06
> Adding Insulation to attic door, (there was never any from day 1)
> 07/12/06
>
> None of this has worked (it's 80.1 in the office now). When the unit
> kicks on, it always runs for a long, long time. The engineers have
> said the system is working at 100%. The AC company says the AC is
> working at 100%.
>
> I say, if the house was run off of a single window unit, the window
> unit would run at 100% but it would run all the time. I think the AC
> is too small for this house.
>
> We have window coverings on all windows. We have ceilling fans.
> Others with the same floorplan are experiencing this same problem. I
> am about ready to sue the builder under the DTPA.
>
> Am I way off, or is this unit too small for the house?
>
> THanks,
>
> please copy any response to scott@houstonpi.com so that I can be sure
> to see it.
>
> Scott
>
|