Re: Actually, it could be a volumetrically compromised compressor?

HVAC Discussions - Heating, ventilation and air conditioning. 

Page 1 of 3       1 2 3 > last >> Bookmark this page:  YahooMyWeb Yahoo!  Google Google  Windows Live Favorites Windows Live  del.icio.us del.icio.us  digg digg  Add to Netscape Netscape
Subject Author Date
Re: Actually, it could be a volumetrically compromised compressor? B-Hate-Me 02-22-2008
If you were  Registered and logged in, you could reply and use other advanced thread options
Posted by B-Hate-Me on February 22, 2008, 6:01 am

>I poped back in to see how this cellar cooler system was doing after
> my repairs.
>
> It's iced again but this time the full charge still exists, subcool
> remains sufficient.
>
> It's design saturated evaporating temperature is about 4 deg C,
> however, surely, due to an inefficient compressor the lower evaporator
> circuit freezes?

Add a hot gas bypass and solenoid.



Posted by Tony on February 22, 2008, 5:07 pm
Taken in consideration what stormin and zyp told you
I believe that EPR valve are still being made
tony


>
>>I poped back in to see how this cellar cooler system was doing after
>> my repairs.
>>
>> It's iced again but this time the full charge still exists, subcool
>> remains sufficient.
>>
>> It's design saturated evaporating temperature is about 4 deg C,
>> however, surely, due to an inefficient compressor the lower evaporator
>> circuit freezes?
>
> Add a hot gas bypass and solenoid.
>



Posted by Zyp on February 25, 2008, 9:29 pm
Tony wrote:
> Taken in consideration what stormin and zyp told you
> I believe that EPR valve are still being made
> tony
>
>
>>
>>> I poped back in to see how this cellar cooler system was doing after
>>> my repairs.
>>>
>>> It's iced again but this time the full charge still exists, subcool
>>> remains sufficient.
>>>
>>> It's design saturated evaporating temperature is about 4 deg C,
>>> however, surely, due to an inefficient compressor the lower
>>> evaporator circuit freezes?
>>
>> Add a hot gas bypass and solenoid.

For the first time in how many month's, I actually understood what Tony
said. An EPR valve might help here.

--
Zyp



Posted by on February 25, 2008, 10:30 pm

>Tony wrote:
>> Taken in consideration what stormin and zyp told you
>> I believe that EPR valve are still being made
>> tony
>>
>>
>>>
>>>> I poped back in to see how this cellar cooler system was doing after
>>>> my repairs.
>>>>
>>>> It's iced again but this time the full charge still exists, subcool
>>>> remains sufficient.
>>>>
>>>> It's design saturated evaporating temperature is about 4 deg C,
>>>> however, surely, due to an inefficient compressor the lower
>>>> evaporator circuit freezes?
>>>
>>> Add a hot gas bypass and solenoid.
>
>For the first time in how many month's, I actually understood what Tony
>said. An EPR valve might help here.

        At the risk of short cycling. I always hesitate to look at
'solutions' that involve re-engineering the system.


--
Click here every day to feed an animal that needs you today !!!
http://www.theanimalrescuesite.com/

Paul ( pjm @ pobox . com ) - remove spaces to email me
'Some days, it's just not worth chewing through the restraints.'
'With sufficient thrust, pigs fly just fine.'
HVAC/R program for Palm PDA's
Free demo now available online http://pmilligan.net/palm/

Posted by Zyp on February 27, 2008, 12:04 pm
Marc O'Brien wrote:
> On Feb 26, 3:30 am, .p.jm@see_my_sig_for_address.com wrote:
>>> Tony wrote:
>>>> Taken in consideration what stormin and zyp told you
>>>> I believe that EPR valve are still being made
>>>> tony
>>
>>
>>>>>> I poped back in to see how this cellar cooler system was doing
>>>>>> after my repairs.
>>
>>>>>> It's iced again but this time the full charge still exists,
>>>>>> subcool remains sufficient.
>>
>>>>>> It's design saturated evaporating temperature is about 4 deg C,
>>>>>> however, surely, due to an inefficient compressor the lower
>>>>>> evaporator circuit freezes?
>>
>>>>> Add a hot gas bypass and solenoid.
>>
>>> For the first time in how many month's, I actually understood what
>>> Tony said. An EPR valve might help here.
>>
>> At the risk of short cycling. I always hesitate to look at
>> 'solutions' that involve re-engineering the system.
>
> Indeed, keep it simple stupid. The irony is that one has to know an
> aweful lot more each time one wants to further simplify something.
> Like the saying "Sorry my letter to you is so long but I didn't have
> the time to write a shorter one".
>
> An EPR reduces evaporator volume flow which is precisely not what you
> want if your problem is already too little evaporator volume flow.

I'm not sure his problem stems from evaporator flow. It seems to me that
when the fixture temperature is just above freeze point, and the evaporator
is below freeze point, you're getting frost no matter what you do. At least
an EPR could keep the evaporator from reaching that point. [Albeit - it is
already a case of refrigeration effect being lost because of the saturation
temperature and flow.] Perhaps just simply execute a defrost every 3-4
hours for 20 minutes would be sufficient. It depends on his load for the
fixture, no?

--
Zyp



Page 1 of 3       1 2 3 > last >>
Similar ThreadsPosted
Re: Actually, it could be a volumetrically compromised compressor? February 22, 2008, 12:24 pm
Updated replacement Compressor Model Number for a 21 year old dead compressor(s) September 12, 2007, 12:34 am
Should AC compressor hum June 8, 2007, 11:06 am
Look Ma... No Compressor August 11, 2008, 5:55 am
Odd Terminals on AC Compressor July 18, 2006, 12:15 am
compressor size? August 7, 2006, 11:30 am
AC compressor shuts off after 20 min April 23, 2007, 3:52 pm
Compressor delay July 22, 2007, 8:29 pm
new coil or new compressor or both? June 20, 2008, 12:20 pm
compressor dead or fixable? July 15, 2006, 12:16 am

Contact Us | Privacy Policy

XML SitemapXML Sitemap