Re: Lennox Whisperheat G20 with standing pilot

HVAC Discussions - Heating, ventilation and air conditioning. 

Bookmark this page:  YahooMyWeb Yahoo!  Google Google  Windows Live Favorites Windows Live  del.icio.us del.icio.us  digg digg  Add to Netscape Netscape
Subject Author Date
Re: Lennox Whisperheat G20 with standing pilot DANgER / danger 10-16-2006
If you were  Registered and logged in, you could reply and use other advanced thread options
Posted by on October 16, 2006, 12:42 am
I agree, no point in replacing the heat exchanger unless your gonna
convert to spark igniton. Dont worry about the rust too much, the
heat exchangers all crack in the same place, standing pilot or not.

I have probably written 30+ red tags on defective G20 and G8 heat
exchangers. Both models use the same style heat exchanger and I
find small hairline cracks at the back on the sbend. I take the
heat exchanger out and fill the cell with water and show the
customer it leaks.

Get rid of the lennox POS.

Buy a Trane

-CanadianHeat


--
--------------------------------- --- -- -
Posted with NewsLeecher v3.7 Final
Web @ http://www.newsleecher.com/?usenet
------------------- ----- ---- -- -


Posted by Bubba on October 16, 2006, 12:28 pm
On 16 Oct 2006 04:42:03 GMT, DANgER / danger@heat.com wrote:

>I agree, no point in replacing the heat exchanger unless your gonna
>convert to spark igniton. Dont worry about the rust too much, the
>heat exchangers all crack in the same place, standing pilot or not.
>
>I have probably written 30+ red tags on defective G20 and G8 heat
>exchangers. Both models use the same style heat exchanger and I
>find small hairline cracks at the back on the sbend. I take the
>heat exchanger out and fill the cell with water and show the
>customer it leaks.
>
Just a FYI for you.................
You can take most new heat exchangers out (especially the crimped
one), fill them with water and they too will leak. Brand new right out
of the box.
Bubba

>Get rid of the lennox POS.
>
>Buy a Trane
>
>-CanadianHeat

Posted by danger@heat.com on October 17, 2006, 8:10 pm
Yeah our local codes allow for a 3% loss in a heat exchanger. When
you water test the g8 and g20 heat exchangers you will see water
leak thru the actual metal at the sbend. I'm starting to see alot
fo cracks in g26 as well, different heat exchanger though.
York makes a crappy crimped heat exchanger. They wouldn't hold
water LOL



--
--------------------------------- --- -- -
Posted with NewsLeecher v3.7 Final
Web @ http://www.newsleecher.com/?usenet
------------------- ----- ---- -- -


Similar ThreadsPosted
Water Heater Pilot Light Keeps Going Out October 17, 2006, 7:52 pm
Carrier 58 furnace pilot gas valve January 24, 2007, 11:23 am
Intermittent Pilot will not shut down after heat cycle December 2, 2006, 12:25 pm
Will non-lennox brands work for independent humidity control in a Lennox system May 2, 2007, 4:34 pm
Coleman 7900b Presidential Electronic pilot retrofit , also any service bulletins December 24, 2006, 11:25 am
lennox a/c June 29, 2007, 7:41 pm
Why (again) would you own a Lennox? February 15, 2007, 6:37 pm
Lennox pulse 21 December 30, 2006, 6:56 pm
Lennox Heater Fan.. April 15, 2007, 11:55 am
Central Air- Lennox? May 25, 2007, 4:05 pm

Contact Us | Privacy Policy

XML SitemapXML Sitemap