Posted by Bipolar_Bear on December 27, 2008, 3:02 pm

> I have a 12yo Rheem Heat Pump that the HVAC tech can't figure why it is
> shorting out the reversing valve solenoid. It has been replaced twice and
> is out again. The tech is saying that he can't find any other electrical
> problem and that they are done trying to fix it. He says They'll give me
> credit from the repair bill toward a new system. Does anyone have any
> ideas on the cause?

http://www.thefreelibrary.com/Solving+solenoid+burnout-a011845237

--



Posted by zero on December 27, 2008, 4:37 pm

>> I have a 12yo Rheem Heat Pump that the HVAC tech can't figure why it is
>> shorting out the reversing valve solenoid. It has been replaced twice and
>> is out again. The tech is saying that he can't find any other electrical
>> problem and that they are done trying to fix it. He says They'll give me
>> credit from the repair bill toward a new system. Does anyone have any
>> ideas on the cause?
> http://www.thefreelibrary.com/Solving+solenoid+burnout-a011845237

.. And now with pictures! (source document) Good tech Document.

http://www.detroitcoil.com/PAGES/What%20Is%20A%20Solenoid.pdf

-zero



Posted by Noon-Air on December 27, 2008, 5:31 pm

>>> I have a 12yo Rheem Heat Pump that the HVAC tech can't figure why it is
>>> shorting out the reversing valve solenoid. It has been replaced twice
>>> and
>>> is out again. The tech is saying that he can't find any other electrical
>>> problem and that they are done trying to fix it. He says They'll give me
>>> credit from the repair bill toward a new system. Does anyone have any
>>> ideas on the cause?
>> http://www.thefreelibrary.com/Solving+solenoid+burnout-a011845237
> .. And now with pictures! (source document) Good tech Document.
> http://www.detroitcoil.com/PAGES/What%20Is%20A%20Solenoid.pdf
> -zero

Thats all well and good *IF* the coil is the correct voltage in the first
place.


Posted by Noon-Air on December 27, 2008, 5:29 pm

>I have a 12yo Rheem Heat Pump that the HVAC tech can't figure why it is
> shorting out the reversing valve solenoid. It has been replaced twice and
> is out again. The tech is saying that he can't find any other electrical
> problem and that they are done trying to fix it. He says They'll give me
> credit from the repair bill toward a new system. Does anyone have any
> ideas on the cause?

Rheem uses different voltage coils...depending on the application...
Post model and serial number so I can make sure you have the correct part
number for the coil


Posted by ddutton on December 28, 2008, 11:55 pm
ddutton had written this in response to
http://www.thestuccocompany.com/hvac/Re-Rheem-Heat-Pump-blowing-Reversing-Solenoid-36084-.htm
:
Model # RPMA-042JAZ
Serial# 5104G409600055

The first solenoid looked melted around the harness and it took out the
thermostat and transformer through the common when it went. The tech put
an in- line fuse in to prevent that from happening again. Both times
afterward the Solenoid appeared to be just cracked. He thought the initial
replacement might have been just a bad one from the supplier. The unit ran
initially after each replacement. Sometime around 5-6 hours later I would
realize that it wasn't working again. The tech called me today and came
out on his day off to look it over again. He checked the operation of the
defrost board and went over all the wiring again. He is still stumped.
-------------------------------------
Noon-Air wrote:

> message
>>I have a 12yo Rheem Heat Pump that the HVAC tech can't figure why
>> it is
>> shorting out the reversing valve solenoid. It has been replaced
>> twice and
>> is out again. The tech is saying that he can't find any other
>> electrical
>> problem and that they are done trying to fix it. He says They'll
>> give me
>> credit from the repair bill toward a new system. Does anyone have
>> any
>> ideas on the cause?

> Rheem uses different voltage coils...depending on the application...
> Post model and serial number so I can make sure you have the correct
> part
> number for the coil






##-----------------------------------------------##
Delivered via
http://www.thestuccocompany.com/
Building Construction and Maintenance Forum
Web
and RSS access to your favorite newsgroup -
alt.hvac - 27388 messages and
counting!
##-----------------------------------------------##

Page 2 of 3       < 1 2 3 > last >>
Similar ThreadsPosted
Rheem Heat Pump December 16, 2008, 1:51 pm
Rheem heat pump defrost June 15, 2009, 1:22 pm
thermostat calling for heat, not blowing then thermostat switches to heat 2 October 24, 2008, 8:37 am
Rheem switching to heat in Auto A/C mode July 26, 2009, 3:30 pm
Upside down Liquid Line Solenoid January 31, 2007, 9:16 pm
possible to replace solenoid in Goodman gas valve April 30, 2007, 12:44 am
first time home owner electirc base heat no ac or heat pump what to do? April 4, 2007, 8:08 pm
air source heat pump, split system, supply water for slab heat/cool February 15, 2008, 8:27 pm
Goodman Heat Pump Emergency Heat doesn't work January 29, 2007, 8:38 am
Bad A/C reversing valve? August 31, 2007, 6:04 pm

Contact Us | Privacy Policy

XML SitemapXML Sitemap