Rheem Heat Pump blowing Reversing Solenoid ddutton 12-27-2008
If you were  Registered and logged in, you could reply and use other advanced thread options
Posted by Steve on December 29, 2008, 8:48 am


> ddutton had written this in response to
>
http://www.thestuccocompany.com/hvac/Re-Rheem-Heat-Pump-blowing-Reversing-Solenoid-36084-.htm
> :
> Model # RPMA-042JAZ
> Serial# 5104G409600055
> The first solenoid looked melted around the harness and it took out the
> thermostat and transformer through the common when it went. The tech put
> an in- line fuse in to prevent that from happening again. Both times
> afterward the Solenoid appeared to be just cracked. He thought the initial
> replacement might have been just a bad one from the supplier. The unit ran
> initially after each replacement. Sometime around 5-6 hours later I would
> realize that it wasn't working again. The tech called me today and came
> out on his day off to look it over again. He checked the operation of the
> defrost board and went over all the wiring again. He is still stumped.

The correct number for the solenoid coil is 61-22883-81. The tech needs to
make sure he has the correct coil. Has the defrost board ever been
replaced?? If so, was it the correct OEM board?? or did the tech use a
generic or "fitzall" board?? There are only 2 boards that are correct for
that heat pump... the timed defrost board, and the demand defrost upgrade.



Posted by ddutton on December 29, 2008, 12:03 pm
ddutton had written this in response to
http://www.thestuccocompany.com/hvac/Re-Rheem-Heat-Pump-blowing-Reversing-Solenoid-36160-.htm
:


-------------------------------------
Steve wrote:

> The correct number for the solenoid coil is 61-22883-81. The tech needs
> to
> make sure he has the correct coil. Has the defrost board ever been
> replaced?? If so, was it the correct OEM board?? or did the tech use a
> generic or "fitzall" board?? There are only 2 boards that are
> correct for
> that heat pump... the timed defrost board, and the demand defrost
> upgrade.


The defrost board had been replaced a couple of years ago. I'm sure it was
a generic board because they had to come back out a second time to ground
it and it is wired in a little different than originally. The tech was
looking hard at that but when he forced it in to defrost mode he said it
worked right and had the correct voltage. He was talking about replacing
it anyhow with an OEM. Thanks to all with constructive feedback. I'll pass
this information on to the tech.




##-----------------------------------------------##
Delivered via http://www.thestuccocompany.com/
Building Construction and Maintenance Forum
Web and RSS access to your favorite newsgroup -
alt.hvac - 27400 messages and counting!
##-----------------------------------------------##

Posted by ddutton on December 29, 2008, 12:19 am
ddutton had written this in response to
http://www.thestuccocompany.com/hvac/Re-Rheem-Heat-Pump-blowing-Reversing-Solenoid-36084-.htm
:
Model # RPMA-042JAZ
Serial # 5104G409600055

The called me today and came out on his day off to go back over
everything. He checked the operation of the defrost board and then went
over the wiring again. The first solenoid looked melted around the
connection to the harness. The other 2 were just cracked. Each of the
replacements initially worked but would go out within 5-6 hours.

-------------------------------------
Noon-Air wrote:

> message
>>I have a 12yo Rheem Heat Pump that the HVAC tech can't figure why
>> it is
>> shorting out the reversing valve solenoid. It has been replaced
>> twice and
>> is out again. The tech is saying that he can't find any other
>> electrical
>> problem and that they are done trying to fix it. He says They'll
>> give me
>> credit from the repair bill toward a new system. Does anyone have
>> any
>> ideas on the cause?

> Rheem uses different voltage coils...depending on the application...
> Post model and serial number so I can make sure you have the correct
> part
> number for the coil






##-----------------------------------------------##
Delivered via http://www.thestuccocompany.com/
Building Construction and Maintenance Forum
Web and RSS access to your favorite newsgroup -
alt.hvac - 27388 messages and counting!
##-----------------------------------------------##

Page 3 of 3       << first < 1 2 3
Similar ThreadsPosted
Rheem Heat Pump December 16, 2008, 1:51 pm
Rheem heat pump defrost June 15, 2009, 1:22 pm
thermostat calling for heat, not blowing then thermostat switches to heat 2 October 24, 2008, 8:37 am
Rheem switching to heat in Auto A/C mode July 26, 2009, 3:30 pm
Upside down Liquid Line Solenoid January 31, 2007, 9:16 pm
possible to replace solenoid in Goodman gas valve April 30, 2007, 12:44 am
first time home owner electirc base heat no ac or heat pump what to do? April 4, 2007, 8:08 pm
air source heat pump, split system, supply water for slab heat/cool February 15, 2008, 8:27 pm
Goodman Heat Pump Emergency Heat doesn't work January 29, 2007, 8:38 am
Bad A/C reversing valve? August 31, 2007, 6:04 pm

Contact Us | Privacy Policy

XML SitemapXML Sitemap