Posted by Steve on December 29, 2008, 8:48 am
> ddutton had written this in response to
>
http://www.thestuccocompany.com/hvac/Re-Rheem-Heat-Pump-blowing-Reversing-Solenoid-36084-.htm
> :
> Model # RPMA-042JAZ
> Serial# 5104G409600055
> The first solenoid looked melted around the harness and it took out the
> thermostat and transformer through the common when it went. The tech put
> an in- line fuse in to prevent that from happening again. Both times
> afterward the Solenoid appeared to be just cracked. He thought the initial
> replacement might have been just a bad one from the supplier. The unit ran
> initially after each replacement. Sometime around 5-6 hours later I would
> realize that it wasn't working again. The tech called me today and came
> out on his day off to look it over again. He checked the operation of the
> defrost board and went over all the wiring again. He is still stumped.
The correct number for the solenoid coil is 61-22883-81. The tech needs to
make sure he has the correct coil. Has the defrost board ever been
replaced?? If so, was it the correct OEM board?? or did the tech use a
generic or "fitzall" board?? There are only 2 boards that are correct for
that heat pump... the timed defrost board, and the demand defrost upgrade.
|
>