Posted by Bubba on April 21, 2008, 9:33 pm
wrote:
>
>>I know I should be using a 2-stage thermostat. This is only temporary.
>> I have a Honeywell Round thermostat (CT87B) hooked up to our new
>> American Standard air handler (2TEC). The problem is when I turn the A/
>> C on, warm air is coming out of vents. Here's how the thermostat is
>> wired:
>>
>> brown/yellow (jumpered).........Y
>> white/orange (jumpered)........W
>> green...................................G
>> red...................................RC / RH (jumpered)
>>
>> I know it's not going to be as efficient as using a 2-stage
>> thermostat, I just need to be able to use it this way until Friday.
>> Any ideas on what's wrong?
>> Bryan
>
>Yes, tell him Bubba.
>
You have too many wires jumpered.
You need a C terminal.
You should jumper the C terminal to the RC/RH.
Do this slowly. If you do it too fast, you will let out the factory
smoke.
Bubba
|