Single vs. double pipe loop providing hydronic heat to radiators.

HVAC Discussions - Heating, ventilation and air conditioning. 

Bookmark this page:  YahooMyWeb Yahoo!  Google Google  Windows Live Favorites Windows Live  del.icio.us del.icio.us  digg digg  Add to Netscape Netscape
Subject Author Date
Single vs. double pipe loop providing hydronic heat to radiators. anthonymmfalcone 11-07-2007
If you were  Registered and logged in, you could reply and use other advanced thread options
Posted by on November 7, 2007, 9:17 am
My hydronic heat system has one large loop around the basement
perimeter from which two tees feed each radiator on the upper
floors.

An HVAC friend of mine suggested that the one single large loop is the
old way and the modern way is to have two loops (one supply and one
return) in the basement, and that this new way is more efficient.

Perhaps this alternate way may provide more even temperature
distribution?
But how would you regulate water flow to each radiator in an even
manner? The single loop way I'm familiar with is to use venturi tees
to encourage circulation through its respective radiator.
What's typically installed for similar type systems these days?

Anyone have an opinion to offer?

-Anthony


Posted by geothermaljones on November 8, 2007, 8:44 pm
A reverse return system is one of the most effective, in most cases.
The first unit supplied becomes the first unit to return, & starts the
return loop, the last unit supplied is the end of the supply line & is the
last on the return circuit.
These systems are typically self balancing & require no "veturis" etc... for
flow control as long as the units in each room are sized reasonably for the
sq.ft. of the room (a 20 strip of baseboard will deliver the same btu's in a
100 sq ft bedroom as it will in a 300 sqft living room) (& yes I know air &
BB delta T will cause variations in heat delivery... so don't...)

The inherent problem with a single loop system like yours, is that the lower
water temps delivered to each of the down stream spaces, as the return from
each previous unit cools the supply to the next, lowers the heat output
capacity of the space heating unit.
Individual control valves or circulators will help resolve this issue & is
probably much more cost effective than repiping the entire system.
Note also, some series type systems were sized with larger output capacity
farther downstream to account for the cooler water temps delivered.
If a new system is being installed, reverse return is one of the best
options, in retrofit... maybe not.

goodluck
geothermaljones
stpaulmn



> My hydronic heat system has one large loop around the basement
> perimeter from which two tees feed each radiator on the upper
> floors.
> An HVAC friend of mine suggested that the one single large loop is the
> old way and the modern way is to have two loops (one supply and one
> return) in the basement, and that this new way is more efficient.
> Perhaps this alternate way may provide more even temperature
> distribution?
> But how would you regulate water flow to each radiator in an even
> manner? The single loop way I'm familiar with is to use venturi tees
> to encourage circulation through its respective radiator.
> What's typically installed for similar type systems these days?
> Anyone have an opinion to offer?
> -Anthony



Similar ThreadsPosted
Heating,Radiators November 30, 2006, 1:16 pm
Mitsubishi 2-Pipe Simultaneous Heat/Cool Energy Recovery VRF System January 25, 2009, 12:43 pm
radiators, baseoard vs column January 8, 2008, 12:10 am
Change convector radiators to cast iron? October 4, 2008, 11:44 pm
HELP I need 2 new furnaces!! Single or dual 80% or 90% single or variable speed fan September 10, 2006, 7:57 pm
Heat Pump System - Single Stage or 2 Stages? May 11, 2008, 12:29 pm
Data Aire 277V Single Phase running on 240V Single Phase? September 10, 2007, 7:34 pm
Thinking of setting thermostat for single stage heat pump instead of two stage October 31, 2009, 12:14 pm
Directional Drilling a Ground Loop June 19, 2007, 12:16 am
Reasonable price for glycol loop tie-in... April 15, 2008, 12:57 am

Contact Us | Privacy Policy

XML SitemapXML Sitemap