|
Posted by daytona° on August 30, 2007, 5:17 am
After washing the coil, probably charged it with a wet condensor
coil.....need more freezone
> wrote:
>
>>
>>> wrote:
>>>
>>>>
>>>>> wrote:
>>>>>
>>>>>>We have an apartment with a rheem air conditioner, split type with the
>>>>>>condenser unit outside and indoor coil in furnace. We recently had the
>>>>>>outdoor unit cleaned. The unit runs for about 10 to 15 minutes and
>>>>>>then
>>>>>>stays off for about 5 to 10 minutes. Inside is stuffy and the air
>>>>>>coming
>>>>>>out
>>>>>>of the registers is 72 degrees. The gauge readings are 60/300, most of
>>>>>>our
>>>>>>other units run 70/225. Could the TEV valve be defective?
>>>>>>
>>>>>
>>>>> Could be. Along with lots of other things. Pressures alone
>>>>> won't answer the question.
>>>>
>>>>What else should I check? Does it sound like a restriction on the high
>>>>side?
>>>>
>>>
>>> Can not be answered without FULL readings.
>>>
>>> All temps & pressures
>>> SH
>>> SC
>>
>>The ambient temp outside the condenser unit is 100 degrees F. I took the
>>suction line temp through insulation about 5 inches from where it goes
>>into
>>the condenser - 86 degrees F. On my gauge the low side showed 32 degrees F
>>R-22 scale, is that the boiling point? The wet bulb at the indoor return
>>grille was 86 degrees F.
>>
>
> Its got a bad muffler valve in the compressor, the oil needs to be
> changed and the refrigerant needs to be rotated to the top of the
> condenser. Then install a new thermostat and it all should be good to
> go.
> Bubba
|