TPDT blower relay Gary 07-13-2008
If you were  Registered and logged in, you could reply and use other advanced thread options
Posted by Gary on July 13, 2008, 4:01 pm
I'm looking for a TPDT relay with 24 volt coil rated for at least 6 amps
preferably more. I'll be using it on a 3/4 h.p blower motor & I'd like to
at least have the rated relay amps double the actual running amps.
So far all I can find is the small glass relays but the amp ratings aren't
high enough. I could put two DPDT in parallel if I had to but I'd rather
not. Anyone have any ideas?

Posted by Noon-Air on July 13, 2008, 5:09 pm

> I'm looking for a TPDT relay with 24 volt coil rated for at least 6 amps
> preferably more. I'll be using it on a 3/4 h.p blower motor & I'd like to
> at least have the rated relay amps double the actual running amps.
> So far all I can find is the small glass relays but the amp ratings aren't
> high enough. I could put two DPDT in parallel if I had to but I'd rather
> not. Anyone have any ideas?

Yeah... use a simple SPST fan relay to control a 3 pole contactor....or is
that too simple??


Posted by on July 13, 2008, 5:12 pm
wrote:

>
>> I'm looking for a TPDT relay with 24 volt coil rated for at least 6 amps
>> preferably more. I'll be using it on a 3/4 h.p blower motor & I'd like to
>> at least have the rated relay amps double the actual running amps.
>> So far all I can find is the small glass relays but the amp ratings aren't
>> high enough. I could put two DPDT in parallel if I had to but I'd rather
>> not. Anyone have any ideas?
>
>Yeah... use a simple SPST fan relay to control a 3 pole contactor....or is
>that too simple??

        Depends what he needs the other side of the throw for.


--
Click here every day to feed an animal that needs you today !!!
www.theanimalrescuesite.com/

Paul ( pjm @ pobox . com ) - remove spaces to email me
'Some days, it's just not worth chewing through the restraints.'
'With sufficient thrust, pigs fly just fine.'
HVAC/R program for Palm PDA's
Free demo online at www.pmilligan.net/palm/
Free 'People finder' program now at www.pmilligan.net/finder.htm

Posted by Gary on July 13, 2008, 6:42 pm
> Yeah... use a simple SPST fan relay to control a 3 pole contactor....or is
> that too simple??

No that wouldn't work.
What I'm doing is designing a relay system for a three zone system
with a three speed blower motor that will call for a different speed
depending on how many zones are in use.
1 zone - low
2 - zones - med.
3 - zones - high

Here is my diagram.
http://www.oldnewtimer.com/zone_three_speed.jpg

I have to use t-stats where the fan gets energized whenever
there is a call for heat or cool. If anyone sees any discrepencies let me
know. I haven't tried it out yet but will in a couple weeks.

Posted by Gary on July 13, 2008, 6:31 pm
> Gee that was hard...
>
> http://www.grainger.com/Grainger/categories/electrical/relays/relays

Thanks, you'd be surprised I couldn't find anything like it in all the
supply houses around. All their glass relays were 3 amps or less.

Page 1 of 2       1 2 > last >>
Similar ThreadsPosted
relay fan October 10, 2007, 4:11 pm
relay suppliers September 21, 2006, 2:40 pm
WHY RELAY for Humidifier? November 6, 2006, 7:58 am
totaltouch DH-BK-Y1 relay part question September 18, 2006, 9:03 am
Has anyone used a Universal Potential Relay? Do they work? November 25, 2006, 6:41 pm
Heat pump fan/relay question July 31, 2007, 2:16 am
Current Sensing Relay Mod A50 (24 volt). January 21, 2008, 11:44 pm
Need Blower Controller July 31, 2006, 2:32 am
Blower On Delay October 16, 2006, 7:56 am
Weak blower? December 24, 2006, 6:00 pm

Contact Us | Privacy Policy

XML SitemapXML Sitemap