Posted by on February 7, 2007, 12:37 pm
Please Help......New tradesman trying to diagnose this
problem.....This system was installed may of 06 and since we have had
3 txv valves go bad. Before I change this valve again, this just
sounds to weird..... Am I missing something? Any help would be
greatly appreciated.....Thanks in advance!!!!
|
|
Posted by on February 7, 2007, 1:58 pm
On 7 Feb 2007 09:37:10 -0800, brent@jandwheatingandair.com wrote:
>Please Help......New tradesman trying to diagnose this
>problem.....This system was installed may of 06 and since we have had
>3 txv valves go bad.
No, you haven't. Trust me, you have had no such thing.
Utterly and completely impossible. What you HAVE done is missed the
problem.
> Before I change this valve again, this just
>sounds to weird..... Am I missing something?
Apparently so.
> Any help would be
>greatly appreciated.....Thanks in advance!!!!
First, learn to take a complete set of readings. Next, learn
to include them when you ask a question, if you want anything other
than random guesses. If you don't know what 'a complete set of
readings' is, you have no earthly business touching a piece of
equipment by yourself.
--
Click here every day to feed an animal that needs you today !!!
http://www.theanimalrescuesite.com/
Paul ( pjm @ pobox . com ) - remove spaces to email me
'Some days, it's just not worth chewing through the restraints.'
'With sufficient thrust, pigs fly just fine.'
HVAC/R program for Palm PDA's
Free demo now available online http://pmilligan.net/palm/
|
|
Posted by AKS on February 7, 2007, 5:57 pm
Brent; PJ is right if you want some one perhaps try to help you
you need to give little more info.
what type system is this
does unit have solenoid in liquid line
does unit run constantly
does unit cycle on and off
does unit have hot gas bypass
does unit have auto. pump down
what temperature is this system design for
what is the application
what refrigerant is use on
what type control does it work of: ON/OFF or PID
what is temp. deviation if works on ON/OFF controll
what is pressure running
what is pressure stand by
what is pressure beginning of cycle
what is the pressure at the end of cycle
what position is TXV mounted vertical or horizontal
what type of TXV is this internal or external equalized
what is temp. at thermal bulb beginning of cooling cycle
what is temp. at thermal bulb at the end of cooling cycle
you answer all these questions and perhaps some one
will be able to gave some idea to the cause of your problem
Good luck from Dido
> Please Help......New tradesman trying to diagnose this
> problem.....This system was installed may of 06 and since we have had
> 3 txv valves go bad. Before I change this valve again, this just
> sounds to weird..... Am I missing something? Any help would be
> greatly appreciated.....Thanks in advance!!!!
>
|
|
Posted by Bob_Loblaw on February 7, 2007, 6:58 pm
> what type system is this
> does unit have solenoid in liquid line
> does unit run constantly
> does unit cycle on and off
> does unit have hot gas bypass
> does unit have auto. pump down
> what temperature is this system design for
> what is the application
> what refrigerant is use on
> what type control does it work of: ON/OFF or PID
> what is temp. deviation if works on ON/OFF controll
> what is pressure running
> what is pressure stand by
> what is pressure beginning of cycle
> what is the pressure at the end of cycle
> what position is TXV mounted vertical or horizontal
> what type of TXV is this internal or external equalized
> what is temp. at thermal bulb beginning of cooling cycle
> what is temp. at thermal bulb at the end of cooling cycle
>
> you answer all these questions and perhaps some one
> will be able to gave some idea to the cause of your problem
>
> Good luck from Dido
And don't forget to tell him about CLOSING the return air vents upstairs so
the hot air on the second floor will flow down the stairs with the cooler
air!
Dildo...our A/C newsgroup expert!
ROTFLMAO!!!!
--
Respectfully, Bob
|
|
Posted by on February 7, 2007, 7:43 pm
On Wed, 07 Feb 2007 23:58:08 GMT, "Bob_Loblaw"
>> what type system is this
>> does unit have solenoid in liquid line
>> does unit run constantly
>> does unit cycle on and off
>> does unit have hot gas bypass
>> does unit have auto. pump down
>> what temperature is this system design for
>> what is the application
>> what refrigerant is use on
>> what type control does it work of: ON/OFF or PID
>> what is temp. deviation if works on ON/OFF controll
>> what is pressure running
>> what is pressure stand by
>> what is pressure beginning of cycle
>> what is the pressure at the end of cycle
>> what position is TXV mounted vertical or horizontal
>> what type of TXV is this internal or external equalized
>> what is temp. at thermal bulb beginning of cooling cycle
>> what is temp. at thermal bulb at the end of cooling cycle
>>
>> you answer all these questions and perhaps some one
>> will be able to gave some idea to the cause of your problem
>>
>> Good luck from Dido
>And don't forget to tell him about CLOSING the return air vents upstairs so
>the hot air on the second floor will flow down the stairs with the cooler
>air!
>Dildo...our A/C newsgroup expert!
>ROTFLMAO!!!!
What a complete fucking putz. He gives perfectly good fake
penis's a bad reputation.
--
Click here every day to feed an animal that needs you today !!!
http://www.theanimalrescuesite.com/
Paul ( pjm @ pobox . com ) - remove spaces to email me
'Some days, it's just not worth chewing through the restraints.'
'With sufficient thrust, pigs fly just fine.'
HVAC/R program for Palm PDA's
Free demo now available online http://pmilligan.net/palm/
|
Page 1 of 8 1 2 3 > last >>
| Similar Threads | Posted | | problems with heating system for steam/hyronic system | October 13, 2006, 11:02 pm |
| Installing split AC system | July 20, 2006, 5:06 pm |
| Trying to source a split system... | November 1, 2006, 9:19 am |
| 2 ton amana split system | January 18, 2009, 7:21 pm |
| Split system topping-up | August 7, 2009, 1:32 pm |
| XR13 clearance from house | July 26, 2007, 3:59 pm |
| Split system Heat Pump | July 9, 2006, 2:54 pm |
| rooftop vs. split system in Phoenix | August 8, 2006, 9:24 pm |
| (UK) Smallest outdoor unit for split system? | February 5, 2007, 6:44 pm |
| Installation of 5ton Bryant 694A Split System Heat Pump - R-22 | July 5, 2006, 4:27 pm |
|
|
>problem.....This system was installed may of 06 and since we have had
>3 txv valves go bad.