|
Posted by daytona° on January 10, 2007, 9:14 pm
Can you go up the chimney with the PVC?
> We need to replace our 20 yr old furnace, and were considering getting a
> 90+ efficiency furnace. But then they'd have to vent it out of the wall,
> and we have a big deck above where it would come out of the wall. Code
> requires that the venting cannot end under a deck, so the options are to
> put a hole in the deck and run it above the deck (which wouldn't look that
> great when we're on the deck), or to run it under the deck and extend it
> about 12 ft under the deck, so it vents at the end of the deck.
>
> Problem is we live in Minnesota, so the venting in this last method would
> have to be heavily insulated.
>
> Some contractors say this running the venting under the deck for 12 feet
> with insulation would be no problem, they do it all the time, it never
> freezes and they say it's listed as an acceptable method in their
> installation manuals (i.e., for a Carrier furnace), it meets code, and
> they don't have problems when its done properly.
>
> Other contractors say to never do that because the piping would surely
> freeze when that much of it is in the open, leading to all kinds of
> problems.
>
> Which contractors should we believe? Is the under the deck method OK to
> do, or would it freeze? If we did the venting above the deck, is there an
> easy way to make it so it doesn't look so out of place and so we don't
> bump into it and risk the piping breaking (especially in cold weather)?
>
> --
> DK
>
|