|
Posted by Jones on January 26, 2007, 10:10 am
UPDATE #2: PROBLEM SOLVED!
I just figured out, by dumb luck, that the wires between the
thermostats and the aquastat were being shorted out by the staples I
put in with a staple gun several weeks ago to keep the wires "out of
the way" in the utility room.
Whew! I'm glad I had the sense to "check what I fixed that wasn't
broken"! That might have been a nightmare to figure out!
Lessons (almost) learned:
1. If it ain't fixed, BREAK IT!
2. Always suspect the last thing you "fixed" or otherwise messed with
as your culprit.
Thanks for your reply, Steve.
Jones.
> UPDATE: I just tried closing the four gate valves for the zone 1
> outgoing and return and the zone 2 outgoing and return. After I did
> that, the propane burner cycled back on until it was about 220°F and 25
> psi, and then the burner shut off. Yet, even with all those gate valves
> closed, the water circulation pump continued to run. This suggests to
> me that the zone valves are OK and that the problem is with the
> aquastat. What do you folks think? Thanks again, Jones.
>
>
>
>
>> Hello, all,
>>
>> We have a propane-fired hot-water baseboard heating system (with 2
>> zones) that we don't use all that much because of its inefficiency. (We
>> heat mostly with wood and kerosene.) We've only used it once or twice
>> this season.
>>
>> Today, because it was so cold and windy, I lit the furnace to make sure
>> the pipes don't freeze under the house. Everything seemed to work fine
>> -- except that the water circulation pump for the system never shuts
>> off.
>>
>> The air temperature at the two thermostats (upstairs and downstairs)
>> was above where they should have been "calling" for heat. The furnace
>> was up to operating temp and pressure, with temp of 200°F and pressure
>> of about 22 psi, according to the gauge.
>>
>> The propane burner cycles on and off, but the water circulation pump
>> never quits.
>>
>> The water return lines for both zones are hot, so it appears that both
>> zone valves are open.
>>
>> Can anyone clue me in on why the circulation pump just runs and runs and runs?
>>
>> Might it be the aquastat? Could bad/sticking zone valves cause this? (I
>> replaced one zone valve a few years ago, but it seems odd that both
>> zone valves would go bad at the same time.)
>>
>> Where would you experts begin to diagnose this?
>>
>> Thanks very much in advance for any advice.
>>
>> Jones.
|