Posted by Noon-Air on May 11, 2007, 5:16 pm
>
>> My house is 4200 sq.ft. My installer installed a EZ072 split heat
>> pump. 3 zones. We have had problems from the start. My total Duct
>> leakage Corrected to 25Pa is 536 CFM's. This is after he corrected
>> my problems? My supply is 14'' round. Return is 9x16 . The unit
>> never stops at 30F or above 85F. We have been in our new home 1
>> year. I've had another Waterfurnace dealer, do a blower door test,
>> and two load cal.
>> which said we needed a 4.1 ton at 1940 cfm. Waterfurnace has been no
>> help. The State inspectors can't get our problem fixed.
>> Any suggestions?
>
> Are the numbers a typo? 4,200 sq ft. @ 4.1 tons of cooling?
SQFT doesn't mean anything..... I have a home that I did here in south
Mississippi that has 3,000 sqft of floor space and is heated and cooled with
nothing more than a 14 SEER 2 ton heat pump.
|