commercial carbon monoxide detectors... daytona 09-12-2006
If you were  Registered and logged in, you could reply and use other advanced thread options
Posted by daytona on September 13, 2006, 4:40 pm
This system has Gray Box with a 30 minute timer....so for 3 minutes each 1/2
hr the fans runs for 3 minutes and then if the CO goes above the set point
on the detectors the fans come and run until the detector gets below the
safe range. Fans ON....intakes also OPEN
One detector senses the north end of the garage and the other the south end


> "daytona" wrote:
>>The two that are in the building now are 120v and are
>>in parallel to bring in a 120v contactor coil for the fans. The Macurco
>>has
>>24v circuits
> my situation was that the existing 3 phase fans were controlled by a
> fused disconnect, like a Square D 321 NRB. So they were on 24/7.
> I installed a 12x12 j-box next to the disco and wired in a 208/24 xfmr
> and 3 pole contactor which was controlled by the CO sensor. So yeah,
> a few xtra bux but then again, they got a top shelf sensor.



Posted by Jake on September 13, 2006, 7:39 pm
>>> a few years ago I had a job installing two such systems in an
>>> underground parking garage. I used detectors made by these guys to
>>> control the fans:
>>> http://www.macurco.com/codetectors.html
>>> very easy to setup & calibrate....
>> this is the one I used....
>> http://www.macurco.com/shcm21a.pdf
>
>

Daytona...

Looks like the unit needs 24 Vac or dc but will switch 5A on a dry
relay. More than enough for a contactor.

Use one of those "piggyback" 120 x 24 v transformers that'll mount to a
4x4 and you're good to go....

I'd talk them into using the alarm contacts too.

Jake

Posted by daytona on September 14, 2006, 7:24 am
I alos ran acroos a Valcain unit...wow....BIG BUCKS no wammy's


>>>> a few years ago I had a job installing two such systems in an
>>>> underground parking garage. I used detectors made by these guys to
>>>> control the fans:
>>>> http://www.macurco.com/codetectors.html
>>>> very easy to setup & calibrate....
>>> this is the one I used....
>>> http://www.macurco.com/shcm21a.pdf
> Daytona...
> Looks like the unit needs 24 Vac or dc but will switch 5A on a dry relay.
> More than enough for a contactor.
> Use one of those "piggyback" 120 x 24 v transformers that'll mount to a
> 4x4 and you're good to go....
> I'd talk them into using the alarm contacts too.
> Jake



Page 2 of 2       << first < 1 2
Similar ThreadsPosted
Moisture and Carbon Monoxide May 20, 2007, 7:36 pm
Leak Detectors July 15, 2007, 11:38 pm
H-10 leak detectors. Who can fix mine? May 9, 2008, 11:23 am
410A leak detectors June 3, 2008, 11:34 am
need help with a commercial ice machine January 2, 2008, 12:11 pm
Commercial hood and furnace July 7, 2006, 3:54 am
question for the commercial guys January 9, 2007, 12:37 am
What are commercial hvac systems like? April 1, 2007, 4:03 am
Is a rooftop commercial HVAC R22 still usable? May 23, 2007, 1:50 pm
Hardware Requirements for Commercial AC unit. May 24, 2007, 10:18 am

Contact Us | Privacy Policy

XML SitemapXML Sitemap