Posted by on March 31, 2008, 6:48 pm
Hi,

We got a new thermostat to replace the old mercury bulb (or whatever's
in there) type. The person who set it up doesn't know if it's right.

The thermostat is a FocusPRO TH5220D.

The outside unit:
TRANE BTB718A 100A1
Compr. Mot. 10.2 44 LRA
O.D. Mot. 1.9 1/8 HP
Regrig 22 2 lbs 4 oz
min CKT 16 amps
CTK BRKR 20 amps
230 V 60 HZ
MFR DATE 3/85

The inside unit:
TRANE BLU055E924B1
Gas fired forced air furnace
115 V 12 Amp 1 PH 60 HZ
55.00 BTU/HR
Air temp MSE 50-80 deg. F.
Max outlet air temp 190 deg. F.

The wires that are hooked up on the thermostat are G W Y R-RC
(R and RC have a connecter joining them). The only other wire, blue,
is not connected to anything.

The wiring matches the diagram (thermostat manual) for a 1H/1C System
with 1 transformer, where wire C - "optional 24VAC common connection"
- is unhooked.

The thermostat system type is set to '0' - 1 heat/1 cool conventional.
Other options are for a heat pump, heat or cool only, and then
2 heat /2 cool conventional, 2 heat/1 cool conventional, and 1 heat/2
cool conventional.

Other settings:
3- Fan Control - set to Gas furnace equipment controls fan in heating.
(Other option is electric furnace controls fan in heating.)
5- Stage 1 Heat Cycle - set to 5, for Gas furnaces with < 90%
efficiency. (other options are > 90% and electric)
9- Stage 1 Compressor cycle rate - set to 3, recommended for most.
(Other options are1 - 6.)
12- Manual/Auto changeover - set to 1, Auto
changeover-heat/cool/auto/off. (Other options are Manual changeover-
heat/cool/off and Auto changeover only- Auto.
15- Compressor protection - 5 minute compressor off time. (Other
options are 0 - 4.)
Other options are not selectable with system type set to '0' - such as
changeover valve, stage 2 heat cycle, auxilliary heat cycle, emergency
heat cycle, and stage 2 compressor.

Does everything look okay? (Heating and cooling is working...)
Thanks

Similar ThreadsPosted
Correct vent sizing January 13, 2007, 12:41 pm
Correct settings for t-stat and h-stat for power roof vent August 18, 2006, 10:41 am
New Heat Pump - Setup question December 14, 2007, 2:59 pm
Advice on Electric backup for Oil DHW -- custom setup. May 18, 2008, 8:17 pm
home buyer with questions about a strange heating setup March 7, 2007, 8:55 pm
Looking for a new thermostat? June 29, 2007, 1:41 pm
2nd thermostat May 3, 2007, 2:54 pm
Digital Thermostat July 9, 2006, 12:26 pm
replacement thermostat March 19, 2007, 7:54 am
Thermostat recommendations July 11, 2007, 8:23 am

Contact Us | Privacy Policy

XML SitemapXML Sitemap