Home Page link

zoned hot water system problem

HVAC Discussions - Heating, ventilation and air conditioning. 

Page 3 of 4       < 1 2 3 > last >> Bookmark this page:  YahooMyWeb Yahoo!  Google Google  Windows Live Favorites Windows Live  del.icio.us del.icio.us  digg digg  Add to Netscape Netscape
Subject Author Date
zoned hot water system problem RayV 11-01-2006
If you were  Registered and logged in, you could reply and use other advanced thread options
Posted by RayV on November 3, 2006, 6:18 am

Steve Scott wrote:
>
> >
> >Steve Scott wrote:
> >> Where are the fill valves located on the systems you see?
> >
> >At the same level as the boiler inlet or lower.
>
> On the boiler return side? Same side as a lot of circs you're seeing?
> Is the fill valve before the circ? Replace many expansion tanks?
>
> >> You're right about less air problems with the circ on the supply side.
> >> Do you know why that is?
> >
> >Higher pressure from the hotter water raising the boiling point?
>
> The expansion tank is the point of no pressure change in the system.
> The circ causes pressure differential. So, the expansion tank is the
> point of no pressure change and the suction side of the circ is close
> to the tank the circ adds to the static system pressure. That causes
> the pressure to be as high as possible at the highest point in the
> system.
>
> If the circ is on the return side and the expansion tank is on the
> supply side the highest points of the loops can be under negative
> pressure causing air to migrate into the water...even from water tight
> solder joints.
>
> >> Where should the fill valve be?
> >
> >Close to the boiler inlet.
> >
> >> Why?
> >
> >Because it is easier to run the piping?
>
> The fill valve should be near the expansion tank because it's the
> point of no pressure change.
>
> What we all commonly see is the expansion tank of the supply side, the
> circ on the return side (cause the boiler manufacturer stuck it there)
> and the fill on the suction side of the circ. This is a guaranteed
> revenue stream as you will be replacing the expansion tanks regularly
> and maybe the relief and fill valves trying to figure out what the
> heck is going on.
>
> The problem is this:
> Fill valve and tank factory set at 12psi. Who changes them?
> Virtually no one.
>
> So the circ is off and the system is full there's 12psi at the fill
> and at the expansion tank.
>
> Let's assume the circ creates 6psi differential. The expansion tank
> is the point of no pressure change so that stays at 12psi. There's
> maybe 1psi loss through the boiler so the outlet side of the circ is
> at 13psi (12psi at the tank + 1psi through the boiler). The circ
> creates 6 psi differential so the suction side is 7psi. Which is what
> the fill valve is seeing cause it's on the suction side of the circ.
>
> Wait a minute. The fill valve is set at 12psi and now it's seeing
> 7psi? What's it gonna do?
>
> Add water?
>
> Yep.
>
> Where's the water go?
>
> The only place it can go is the expansion tank. The rest of the
> system is already full.
>
> What happens when the expansion tank has too much water in it?
>
> The diaphragm ruptures.
>
> And that's the short version of why in a correctly piped system the
> expansion tank goes in the supply near the boiler with the feed near
> the expansion tank and the circ right after the tank. With very few
> exceptions.
>
Thanks for the explanation. Easy to understand and makes perfect sense
the way you explained it. A welcome difference from the way most posts
are written.

I'm going to disconnect the pump on the return side of his system and
run the zones to see if that cures the problem of non-calling zones
always getting hot.

Thanks again.


Posted by Steve Scott on November 1, 2006, 6:51 pm
Flow checks are open or failed if the pumps are operating properly.

Is the supply and return manifold piped completely separate or are
they connected at some point other than through the loops?

What is used for heat emitters? Baseboard?


>My BIL has a problem with his system, here's the current setup:
>Boiler in basement
>
>Split level house with all zone loops higher than basement
>
>Three zones - all thermostats working properly
>
>Circulator pump on the cold/return side of boiler mounted just above
>boiler inlet
> comes on with furnace (zone independent)
>
>Flo-control valve on the hot/supply side of boiler mounted near ceiling
>
>Air separater right after main flo-control valve with bladder expansion
>tank
>
>Three additional zone circulator pumps connected to the thermostat
>relays
>
>Three zone flo-control valves, one right after each zone pump
>
>The problem is that whenever any zone calls for heat there is flow thru
>all three zones. I verified that each of the zone pumps are working
>independently and correctly. He told me that the system has always
>operated this way and he just sets the thermostat on the upper level to
>50 so it never kicks on because he always gets heat up there.
>There are no zone valves on any of the zones, only the flo-control
>valves. The zone pumps, flo-control valves and thermostats appear to
>be add-ons to the original system.
>
>I would like to hear ideas on possible repairs or system changes that
>would get the system to only heat the zone(s) that is calling for heat.


--
My problem is drinking Coke in the
Pepsi generation





Posted by RayV on November 1, 2006, 10:12 pm

Steve Scott wrote:
> Flow checks are open or failed if the pumps are operating properly.
I cranked the flo-controls to the full open position and ran all of the
pumps to flush out any sediment that might be on the seats then closed
them. I did just change one of the zone pumps for him and the
flo-control for that zone held the water in the pipes while I changed
the pump.
>
> Is the supply and return manifold piped completely separate or are
> they connected at some point other than through the loops?
The supply pipes are teed right after the air separator and the returns
don't come back together until right before they go to the inlet
circulator pump.
>
> What is used for heat emitters? Baseboard?
Yes, standard baseboard around the perimeter of each level.


Posted by Steve Scott on November 1, 2006, 11:05 pm
The purpose of the flow check isn't to hold the water when you pull
the valve, it's to keep other circs from moving water through a loop
that isn't calling.

That said, if the system worked properly at some point in the past,
loops are heating up now when that circ isn't firing then either the
flow checks are open or they're not working.


>
>Steve Scott wrote:
>> Flow checks are open or failed if the pumps are operating properly.
>I cranked the flo-controls to the full open position and ran all of the
>pumps to flush out any sediment that might be on the seats then closed
>them. I did just change one of the zone pumps for him and the
>flo-control for that zone held the water in the pipes while I changed
>the pump.
>>
>> Is the supply and return manifold piped completely separate or are
>> they connected at some point other than through the loops?
>The supply pipes are teed right after the air separator and the returns
>don't come back together until right before they go to the inlet
>circulator pump.
>>
>> What is used for heat emitters? Baseboard?
>Yes, standard baseboard around the perimeter of each level.

You most likely don't need a return pump then.

--
My problem is drinking Coke in the
Pepsi generation





Posted by RayV on November 2, 2006, 6:18 am

Steve Scott wrote:
> The purpose of the flow check isn't to hold the water when you pull
> the valve, it's to keep other circs from moving water through a loop
> that isn't calling.
>
> That said, if the system worked properly at some point in the past,
> loops are heating up now when that circ isn't firing then either the
> flow checks are open or they're not working.
>
The system hasn't worked properly in the 8 years since he has been
there. It may have never worked properly.

Could have been the previous owner had it 'zoned' because it was colder
in some parts and was sold all these extra circulator pumps and relays
when all he needed were a few zone valves.


Page 3 of 4       < 1 2 3 > last >>
Similar ThreadsPosted
zoned hot water problem resolved November 28, 2006, 8:23 am
Zoned heating system January 4, 2008, 8:11 pm
Gas Burner / Hot water system problem November 20, 2006, 9:56 am
Re: Intermittent high pressure in hot water heating system system February 3, 2007, 9:46 am
Re: Intermittent high pressure in hot water heating system system February 4, 2007, 3:49 pm
Re: Intermittent high pressure in hot water heating system system February 4, 2007, 3:54 pm
Re: Intermittent high pressure in hot water heating system system February 4, 2007, 3:43 pm
Re: Intermittent high pressure in hot water heating system system February 4, 2007, 3:06 pm
Re: Intermittent high pressure in hot water heating system system February 4, 2007, 3:05 pm
Re: Intermittent high pressure in hot water heating system system February 2, 2007, 10:20 am

Contact Us | Privacy Policy

XML SitemapXML Sitemap