220 over 12 gauge roger61611 12-17-2006
If you were  Registered and logged in, you could reply and use other advanced thread options
Posted by on December 17, 2006, 10:24 pm


Is 220 over 12 gauge wire ever legit ? I had a live 220 plug (per the
tester) in the garage of a house I recently bought, one of those with
weird prongs but not anywhere near the size of a dryer plug. It had
about 4 extra miles of wire that led to a junction box that connected
to a switch that also had some 3-way component to it. I ripped it all
out cause it was ridiculous and served no purpose.


PexSupply QuikTrak 468x60
Posted by RBM on December 17, 2006, 10:32 pm


Of course, that's why they make those "weird" outlets. Compressors, air
conditioners, shop equipment, large portable heaters, and lots of other
things use 20 amp 240 volts


> Is 220 over 12 gauge wire ever legit ? I had a live 220 plug (per the
> tester) in the garage of a house I recently bought, one of those with
> weird prongs but not anywhere near the size of a dryer plug. It had
> about 4 extra miles of wire that led to a junction box that connected
> to a switch that also had some 3-way component to it. I ripped it all
> out cause it was ridiculous and served no purpose.
>



Posted by on December 18, 2006, 11:15 pm


Thanks all, I learned something today. The rest of the install was so
messed up that even if I had a need for 220 out there, I would have
wanted to redo it. My inspector missed the extra several feet of
wiring just tucked into the eaves. And the use of a light switch above
the garage door (7' off the floor) to somehow control the outside
lights, though I'm not sure how.

Also, if you're taking notes, running romex on top of a board in your
garage eaves and holding it in place by laying a piece of drywall on
it, is not the best way to secure it.

When amateur electricians get inventive we do some crazy things.


Posted by Steve Barker LT on December 19, 2006, 1:11 pm


There's no problem with the extra wiring or the switch above the door.
That's why it was "missed" because it's not a problem.

--
Steve Barker


> Thanks all, I learned something today. The rest of the install was so
> messed up that even if I had a need for 220 out there, I would have
> wanted to redo it. My inspector missed the extra several feet of
> wiring just tucked into the eaves. And the use of a light switch above
> the garage door (7' off the floor) to somehow control the outside
> lights, though I'm not sure how.
>
> Also, if you're taking notes, running romex on top of a board in your
> garage eaves and holding it in place by laying a piece of drywall on
> it, is not the best way to secure it.
>
> When amateur electricians get inventive we do some crazy things.
>



Posted by dpb on December 19, 2006, 2:23 pm



roger61611@yahoo.com wrote:
> Thanks all, I learned something today. The rest of the install was so
> messed up that even if I had a need for 220 out there, I would have
> wanted to redo it. My inspector missed the extra several feet of
> wiring just tucked into the eaves. And the use of a light switch above
> the garage door (7' off the floor) to somehow control the outside
> lights, though I'm not sure how.
>
> Also, if you're taking notes, running romex on top of a board in your
> garage eaves and holding it in place by laying a piece of drywall on
> it, is not the best way to secure it.
>
> When amateur electricians get inventive we do some crazy things.

Nothing you've described so far comes even close to "crazy" in the
sense of being any safety hazard whatsoever. I'd suspect from the
sounds of it the previous owner probably had a reason for the switch
being where it was, and as for a few extra feet of wire coiled up in an
eave space and the wire tucked up out of the way, as previously noted,
it was in all likelihood done that way on purpose w/ the idea of being
able to move the outlet at some future time. I've many such similar
"features" in shop/barn/shed areas as we speak (although I will admit I
don't have anything being held anywhere by a piece of drywall :)) ,
but doesn't sound like the situation you describe would be any worse if
the wire were simply laying there. If there's no access, I don't
believe there's any code requirement that the wire be fastened.

Not that neatness isn't a desirable trait and is quite important for a
whole-house installation and has advantages even in adding a branch
circuit, lack of it doesn't by and in of itself, constitute a hazard.


Page 1 of 2       1 2 > last >>
Similar ThreadsPosted
Can I stick two 4 gauge and one 6 gauge wire into a 3/4" conduit September 11, 2006, 2:41 pm
How can I tell if the wires are 14 gauge or 12 gauge? September 19, 2007, 3:18 pm
12 gauge -> 14 gauge May 23, 2008, 4:57 pm
12 gauge -> 14 gauge May 23, 2008, 4:58 pm
wire gauge June 29, 2007, 8:42 am
I need a 2-CYCLE OIL GAUGE April 19, 2006, 3:16 pm
Contour Gauge September 2, 2006, 12:17 am
18 or 16 gauge nailer April 18, 2008, 9:48 am
What to do with the rain gauge water? June 26, 2006, 8:13 am
What gauge is this extension cord August 24, 2006, 12:46 am

Contact Us | Privacy Policy

XML SitemapXML Sitemap