490 V Clamping Volt For MOV: Seems High ? Robert11 08-09-2005
If you were  Registered and logged in, you could reply and use other advanced thread options
Posted by Robert11 on August 9, 2005, 1:53 pm


Hello,

Thinking of installing an Intermatic AG series surge protector across a
single 110 V
line to help protect a circuiit board in a furnace.

Clamping voltage is given as 490 V.

Seems awfully high.

Wouldn't most solid state devices blow (well) before this level ?

Thanks,
B.




Posted by Chris Lewis on August 9, 2005, 6:14 pm


> Hello,
>
> Thinking of installing an Intermatic AG series surge protector across a
> single 110 V
> line to help protect a circuiit board in a furnace.

> Clamping voltage is given as 490 V.

> Seems awfully high.

It does. Are you _sure_ it's not intended for a 240V circuit?

IIRC, a MOV for 120V should clamp somewhere around 180-200V.

It might be worth calling Intermatic, it may be a communication
goof between engineering and tech writers.
--
Chris Lewis, Una confibula non set est
It's not just anyone who gets a Starship Cruiser class named after them.


Posted by Pop on August 9, 2005, 7:15 pm



> Hello,
>
> Thinking of installing an Intermatic AG series surge
> protector across a single 110 V
> line to help protect a circuiit board in a furnace.
>
> Clamping voltage is given as 490 V.
>
> Seems awfully high.
>
> Wouldn't most solid state devices blow (well) before
> this level ?
>
> Thanks,
> B.
>

That's a decent figure, actually, considering that
there is already protection there on the ckt board,
even though you're getting storm damage or whatever.
It should help substantially, but that's not the
primary protection figure.

In my experience they were 375V, but it varies by
manufacturer and purpose, level of protection,
application, etc.. "clamping voltage" is the steady
state voltage that will occur across the protective
device during a fault condition, and the fault
conditions are specced to be able to exist for a period
of time, usually in microseconds, sometimes
milliseconds. instead of thousands of volts, this
component will only allow 490V to the secondary
protection ckts already present in a standard ckt board
design.
At that voltage, the part is about to become an open
ckt after x amount of time. If the load goes away in
time, you still have a good part. If not, the part is
no longer functional and can no longer protect
anything. Other things fried, too, but they lasted a
lot longer than they would have. This is a typical
scenario for trying to protect against lightning
surges, etc..
In a system, the rating of the intermatic has to be
higher than the protective devices already present in
the ckt board. Otherwise they cannot share the load
during a surge, and successfully direct current away
from the protected equipment.

The more important figure is the "knee" voltage, the
point at which the device begins to conduct current
away from the equipment being protected. Then there is
a time/current and energy curve, detailing what happens
as the part becomes overloaded and nears its own
destruction.
The two most important figures are the joules of
energy it can absorb (basically watts, but not exactly)
and for how long it can handle that level of energy,
which is measured in anything from micro to milli
seconds. 1,000 milliseconds - 1.0 second. If the
clamping voltage is reached across the part, that
probably would indicate, based on design, that the
actuall applied voltage is in the order or many
thousands of volts. So, say a 15,000 volt spike will
clamp at 490 volts due to the component being there,
and only 490 V is left for the remianing protective
cktry to handle. It's sort of a staging cycle in most
good designs.
The switch you have isn't as simple as an MOV, but
it operates almost like one. Try a google for MOV or
Metal Oxide Varistor and you'll get a feeling for what
the part you have can do.

Hope I haven't just made things more confusing!


Pop




Posted by Robert11 on August 9, 2005, 8:02 pm


Hi,

Thanks for such good info.

BTW: When an MOV fails due to being unable to dissipatge too many Joules,
or overcurrent, how does it fail ? As an open or as a short between the
lines it was trying to protect ?

Thanks,
Bob
-------------------
> Hello,
>
> Thinking of installing an Intermatic AG series surge protector across a
> single 110 V
> line to help protect a circuiit board in a furnace.
>
> Clamping voltage is given as 490 V.
>
> Seems awfully high.
>
> Wouldn't most solid state devices blow (well) before this level ?
>
> Thanks,
> B.
>




Posted by PrecisionMachinisT on August 9, 2005, 6:11 pm



> Hi,
>
> Thanks for such good info.
>
> BTW: When an MOV fails due to being unable to dissipatge too many Joules,
> or overcurrent, how does it fail ? As an open or as a short between the
> lines it was trying to protect ?
>

These short the line so that the fuse blows out, thus effectively
disconnecting the load from the power source.

--

SVL







Page 1 of 2       1 2 > last >>
Similar ThreadsPosted
Clamping wire in pancake box? September 13, 2007, 6:51 pm
Connecting a 110 Volt 300 watt generator to a 220 Volt panel November 18, 2005, 10:49 pm
Clamping Wires Used With Electrical PVC Pipe ? September 16, 2005, 6:06 pm
Clamping new armored cable run to existing conduit August 13, 2008, 10:59 am
Adapter plug for a 230 volt 4 prong Dryer Outlet to a 230 volt 3 prong Outlet June 17, 2007, 7:37 pm
High efficiency, high recovery water heaters July 24, 2008, 2:43 pm
how high is too high for residential water pressure? December 14, 2005, 12:32 am
220 volt to 110 volt November 19, 2007, 11:58 pm
12 volt DC thermostat July 19, 2006, 3:48 pm
220 volt oven December 27, 2006, 8:06 pm

Contact Us | Privacy Policy

XML SitemapXML Sitemap